46
RMWH-SVX001C-EN
Maintenance
Obey the following warnings and cautions for all
maintenance procedures.
NOTICE
Electrostatic Discharge!
Electrostatic discharge can short equipment circuitry.
Ensure that you are properly grounded before handling
sensitive electronic equipment.
Under routine operating conditions, the device requires
the following scheduled maintenance procedures:
•
Examine and replace end-of-line filters
•
Examine and replace internal inline filters
Scheduled Maintenance
Examine and Replace End-of-Line Filters
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on
the tags, stickers, and labels could result in death or
serious injury.
Technicians, in order to protect themselves from
potential electrical, mechanical, and chemical hazards,
MUST follow precautions in this manual and on the
tags, stickers, and labels, as well as the following
instructions: Unless specified otherwise, disconnect all
electrical power including remote disconnect and
discharge all energy storing devices such as capacitors
before servicing. Follow proper lockout/tagout
procedures to ensure the power can not be
inadvertently energized. When necessary to work with
live electrical components, have a qualified licensed
electrician or other individual who has been trained in
handling live electrical components perform these
tasks.
WARNING
Risk of Asphyxiation!
Failure to follow instructions below could cause
inaccurate readings and improper gas monitoring
which could result in death or serious injury.
Use and maintain end-of-line filters to ensure proper
readings and prevent damage to internal components.
Make additional servicing necessary.
Examine the end-of-line filters periodically for dirt and
particulate buildup.
Replace dirty filters when necessary. For a list of approved
parts and how to order them, refer to
If an end-of-line filter becomes severely clogged with
particulates, the flow rate for that sample line will decrease
and eventually cause a flow rate fault.
Do the following procedure to replace an end-of-line filter:
1. Disconnect the dirty filter from the sample line tubing.
2. Discard the dirty filter.
3. Remove the new end-of-line filter from the bag.
4. Slide the end of the end-of-line filter with flexible
tubing onto the sample line tubing. Make sure the
arrow on the body of the filter points in the direction of
air flow into the sample line.