background image

Tracer XM30, XM32, XM70, and 
XM90 Expansion Modules

Installation, Operation, and Maintenance 

March 2020

BAS-SVX46E-EN

SAFETY WARNING

Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of 
heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. 
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. 
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are 
attached to the equipment.

Summary of Contents for Tracer XM30

Page 1: ...tion starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by...

Page 2: ...result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or property damage only accidents W WA AR RN NI...

Page 3: ...is sk k o of f e en ne er rg gi iz ze ed d e el le ec ct tr ri ic ca al l c co on nt ta ac ct t a ar rc c o or r f fl la as sh h t te ec ch hn ni ic ci ia an ns s M MU US ST T p pu ut t o on n a al l...

Page 4: ...ion and Power Wiring 14 IMC Harness Pins 15 Communication Wiring Examples 15 Remote Mounting 19 AC Power Warnings and Notices 21 Terminal Wiring Requirements 21 Transformer Requirements 21 Wiring AC P...

Page 5: ...aximum of 12 VA for each binary output Output 24 Vdc 10 device max load 600 mA XM90 Input 18 30 Vac 24 Vac nominal 50 or 60 Hz 50 VA 2 08A max 500mA load on 24 Vdc output terminals plus a maximum of 1...

Page 6: ...umulator Minimum 20 milliseconds open or closed Outputs Current 0 to 20 mA 16V Voltage 0 to 16 Vdc 20mA Table 3 XM32 device connections Connection Quantity Types Range Notes Binary output BO1 to BO4 4...

Page 7: ...to two expansion modules XM30 32 Inputs 6 Thermistor 10k Type II 10k Type III 2252 Type II 20k Type IV 100 k Resistive Setpoint 100 to 1M RTD 1k 385 375 platinum Balco or 672 nickel Current 0 to 20 mA...

Page 8: ...RTD 1k 385 375 platinum Balco or 672 nickel Current 0 to 20 mA linear Voltage 0 to 20 Vdc linear Binary Dry contact Pulse Accumulator Minimum 20 ms opened or closed Universal inputs require the follow...

Page 9: ...be installed on a DIN rail use the following standard DIN Standard 43 880 standard profile Built in Equipment for Electrical Installations Overall Dimensions and Related Mounting Dimensions One DIN un...

Page 10: ...mm 1 93 in 49 02 mm 4 00 in 101 6 mm 2 82 in 71 63 mm XM32 BO1 BO2 BO3 BO4 ADDRESS x10 x1 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 IMC SERVICE RX TX RELAYS BO1 BO2 BO3 BO4 NO NC C NO NC C NO NC C NO NC...

Page 11: ...Consider the following when budgeting DC power for a UC400 In most applications the UC400 can support a maximum of two expansion modules without any issues provided that all terminations are NOT conf...

Page 12: ...itional devices see Communication Wiring Examples p 15 Table 7 Expansion module power input and power draw Module Power Input Power Draw mA XM30 expansion module 24 Vdc 120 XM32 expansion module 24 Vd...

Page 13: ...En nc cl lo os su ur re e D Da am ma ag ge e F Fa ai il lu ur re e t to o f fo ol ll lo ow w i in ns st tr ru uc ct ti io on ns s b be el lo ow w c co ou ul ld d r re es su ul lt t i in n d da am ma...

Page 14: ...thead screwdriver Valid address are 01 99 Figure 5 Setting rotary switches ADDRESS 0 1 2 3 4 5 6 7 8 9 x1 0 1 2 3 4 5 6 7 8 9 x10 0 1 2 3 4 5 6 7 8 9 x100 Use a 1 8 in 3 mm flathead screwdriver to set...

Page 15: ...IMC link that is connected to the UC400 UC600 Figure 7 Example of a typical installation two expansion modules and one UC600 controller AO6 UI14 AO5 UI13 AO4 UI12 AO3 UI11 AO2 UI10 AO1 UI9 BO4 BO3 BO2...

Page 16: ...RELAYS BO1 BO2 BO3 BO4 NO NC C NO NC C NO NC C NO NC C 1 A B IMC 24 VDC ADDRESS 0 1 2 3 4 5 6 7 8 9 x1 0 1 2 3 4 5 6 7 8 9 x10 4 3 2 1 UI AO IMC 1 IMC IMC 24 VDC SERVICE IMC RX TX XM30 ADDRESS 0 1 2 3...

Page 17: ...C 24 VDC OUT 24 VAC XFMR 24 VAC SERVICE IMC RX TX XM70 ADDRESS 0 1 2 3 4 5 6 7 8 9 x1 0 1 2 3 4 5 6 7 8 9 x10 BO4 BO3 BO2 BO1 IMC IMC TRANE XM32 BO1 BO2 BO3 BO4 ADDRESS x10 x1 1 2 3 4 5 6 7 8 9 0 1 2...

Page 18: ...I8 UI7 UI6 UI5 UI4 UI3 UI2 UI1 IMC 24 VDC OUT 24 VDC 24 VDC OUT 24 VAC XFMR 24 VAC SERVICE IMC RX TX ADDRESS 0 1 2 3 4 5 6 7 8 9 x1 0 1 2 3 4 5 6 7 8 9 x10 BO4 BO3 BO2 BO1 XM70 XM70 UC600 controller R...

Page 19: ...ICE RX TX RELAYS BO1 BO2 BO3 BO4 NO NC C NO NC C NO NC C NO NC C 1 A B IMC 24 VDC ADDRESS 0 1 2 3 4 5 6 7 8 9 x1 0 1 2 3 4 5 6 7 8 9 x10 4 3 2 1 UI AO IMC 1 IMC IMC 24 VDC SERVICE IMC RX TX XM30 ADDRE...

Page 20: ...thod Remove the 24 Vdc wire from both the expansion module and the PM014 power supply module Run both IMC and 24 Vdc Remotely mounted expansion modules must have a common ground plane Ensure that the...

Page 21: ...f fo ol ll lo ow w i in ns st tr ru uc ct ti io on ns s b be el lo ow w c co ou ul ld d r re es su ul lt t i in n d da am ma ag ge e t to o t th he e c co on nt tr ro ol ll le er r p po ow we er r t...

Page 22: ...C transformer to the chassis ground terminal 3 Connect the other secondary wire to the 24 Vac terminal N No ot te e A pigtail connection is necessary between the earth ground and chassis ground if the...

Page 23: ...dule in the A Ad dd dr re es ss s field If not set the appropriate rotary addresses A rotary dial setting of 0 01 1 e eq qu ua al ls s 1 1 in the A Ad dd dr re es ss s field For help refer to Troubles...

Page 24: ...y output is On Energized LED not illuminated Binary output is Off De energized Troubleshooting This section describes possible solutions for communication and status errors that may occur after the mo...

Page 25: ...l le em m An expansion module was discovered on the IMC link that was not configured S So ol lu ut ti io on n configure the module see Configuring the Expansion Modules p 22 N No ot te e An un configu...

Page 26: ...ltage across the resistive termination VAC 0 0 V AC voltage will affect further measurement Step 2 Measure DC voltage across the resistive termination Refer to the charts below 2 5 3 3 5 4 1 5 0 0 5 1...

Page 27: ...put resistance of a DMM in current measurement mode However this method affects the value that the expansion module will use while controlling outputs When the meter is set to current mode the current...

Page 28: ...ar Current Input mA 10 12 4 6 0 2 16 18 8 20 14 Voltage Measured Across Input Vdc Binary Inputs 24 Vac Detect Methods 1 or 2 General Information and Checkout Procedure Measurement Expected Value Metho...

Page 29: ...nput Vac 0 0 V AC voltage will affect further measurement Step 2 Measure DC voltage across the binary input Vdc 2 0 V state ON Vdc 2 0 V state OFF Voltage Analog Output Measurement Procedure Expected...

Page 30: ...n request from controller This request may be based on an override of the output value Method 2 Measuring current directly this method is most the typical way to measure current and has the advantage...

Page 31: ...BAS SVX46E EN 31 N No ot te es s...

Page 32: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...