Overview and Specifications
Power
The transformer must meet the following minimum requirements for the controller and its output
devices:
•
19–30 Vac (24 Vac nominal)
•
50/60 Hz
•
9 VA and 12 VA maximum per binary output utilized
Agency Listing/Compliance
CE—Immunity:
EMC Directive 89/336/EEC
EN 50090-2-2:1996
EN 50082-1:1997
EN 50082-2:1995
EN 61326-1:1997
CE—Emissions:
EN 50090-2-2:1996 (CISPR 22) Class B
EN 50081-1:1992 (CISPR 22) Class B
EN 55022:1998 (CISPR 22) Class B
EN 61326-1:1997 (CISPR 11) Class B
UL and C-UL listed:
Energy Management Equipment—PAZX (UL 916)
UL 94-5V (UL flammability rating for plenum use)
FCC Part 15, Subpart B, Class B