Controls
37
RT-SVX19A-E4
Fire thermostat
There are two sensors in the fire
thermostat Kit: Sensor X13100040-
01 is factory-set to open at 57°C.
Sensor X13100040-02 is set to open
at 115°C.
Sensors are mounted directly in the
ductwork. They should be installed
where elements can respond quickly
to air temperature changes. If not
possible, the sensor may be
installed on a suitable bracket so
the air is drawn across the element.
Sensor X13100040-01 has to be
mounted in the return air duct.
Sensor X13100040-02 has to be
mounted in the supply air duct.
Note: Do not permit element guard
to touch internal parts. Do not
locate sensor where the air
circulation is restricted by baffles.
Connection of the fire thermostat
with TCI board : Refer to the wiring
diagram provided in the unit.
Connection without TCI board
Connect according to the standard
wiring diagram provided on the
unit.
Remove sensor cover and fasten
control securely with screws. Loads
connected must not exceed 2 amps,
30V Ac.
Figure 17 - Duct mounting of fire thermostat
1 = Fire thermostat
2 = Hole in the duct