Installation
19
RT-SVX19A-E4
RT-SVX19A-E4
Table 9 - WKD/WKH Pressure drop through accessories
Airflow
Filter
EU2/G2
Filter
EU4/G4
Economizer
100%
outside air
Economizer
100%
return air
Electric
heater
Hot water coil
Downflow only
WKD/WKH 125
5720
9
21
6
5
4
37
6430
11
24
7
6
6
45
7140
14
27
9
6
7
53
7850
17
30
10
7
9
62
8560
20
33
12
8
12
72
WKD/WKH 155
6800
13
27
8
6
7
33
7650
16
30
10
7
9
40
8500
19
34
12
8
11
48
9350
22
37
14
9
13
56
10200
26
40
16
10
16
65
WKD 200
8970
12
26
29
6
13
33
10090
15
30
37
8
17
40
11210
19
33
45
9
21
48
12330
23
37
55
11
25
56
13450
27
41
65
13
30
65
WKH 200
8970
11
23
33
6
13
-
10090
14
26
41
8
17
-
11210
17
29
51
9
21
-
12330
20
33
61
11
25
-
13450
23
36
72
13
30
-