Installation
17
RT-SVX19A-E4
Component air pressure drops
Table 7 - YKD/YKH Pressure drop through accessories
Filter
Filter
Economizer Economizer
Airflow
EU2/G2
EU4/G4
100%
outside air
100%
return air
YKD/YKH 155
6800
13
27
8
6
7650
16
30
10
7
8500
19
34
12
8
9350
22
37
14
9
10200
26
40
16
10
YKD/YKH 175
7870
17
30
10
7
8860
21
34
12
8
9850
25
38
15
9
10840
30
43
17
11
11830
35
47
20
12
YKD 200
8970
12
26
29
6
10090
15
30
37
8
11210
19
33
45
9
12330
23
37
55
11
13450
27
41
65
13
YKH 200
8970
11
23
33
6
10090
14
26
41
8
11210
17
29
51
9
12330
20
33
61
11
13450
23
36
72
13
YKD 250
11280
18
32
46
10
12690
24
36
58
12
14100
29
41
71
14
15510
36
46
86
17
16920
43
51
102
19
YKH 250
11280
17
30
52
10
12690
21
34
65
12
14100
26
38
80
14
15510
31
43
96
17
16920
36
47
114
19