SRV-SVX04B-EN
5
Desiccant Dehumidification Unit Overview
Introduction
This Installation, Operation and Maintenance (IOM)
manual covers the desiccant dehumidification units (DHU)
available to rent from Trane Rental Services for temporary
dehumidification solutions. This includes DHU technical
information, start-up information and unit maintenance.
The information contained in this manual is provided to
ensure the safe installation and operation of the
equipment and its surroundings.
The information provided in this IOM is to be used as a
reference for each DHU to aid in determining unit size,
power requirements, or lifting requirements. If additional
information regarding a particular unit is required, please
contact Trane Rental Services.
Contact Trane Rental Services Marketing for availability of
equipment (including ancillary items: electrical cable,
flexible duct, etc.) prior to securing rental equipment.
Equipment is available on a first-come, first-serve basis,
but can be reserved with a signed rental agreement.
Call Rental Services 24/7 at 1-800-755-5115 for specific
questions.
Units Affected
RSDH0012F0XX –Desiccant Dehumidification Unit (DHU)
with post cooling coil
Note:
Where XX represents the unique inventory
number.
General Information
The Trane Rental Services DHUs are highly efficient at
providing clean, dehumidified air with minimal electrical
power required. The DHUs can be used in free blow or
ducted applications. Each unit has a single horizontal
supply air connection and a single return air connection
and is equipped with a post-cooling coil to aid in reducing
leaving air temperatures when required. When used in
free blow applications, ducting on the front of the unit
must be removed. Flexible duct is available upon request.
Table 1.
Model
RSDH0012
Manufacturer
Munters™
Airflow
Orientation
Horizontal
Nominal Airflow
4,750 cfm
Blower RPM
3500
Max Static Discharge
Pressure
1.70 in. ESP
Post-cooling
Coil Water
Connection(s)
1
Type
Flanged
Size
3 inches
Supply Air
Connection(s)
Type
Round
Quantity
1
Size
17.75 inches
Return Air
Connection(s)
Type
Round
Quantity
1
Size
17.75 inches
Reactivation Air
Connection (s)
None (Free Blow)
Pre Filter
Type
30% efficient
Quantity and
Dimensions
(2) 12 in x 24 in
(2) 24 in x 24 in
Inlet Delta P
0.21 in. WC
Final Delta P
0.42 in. WC
1 Unit can be provided with reducer to provide either 2.5 inch or 4 inch
grooved water connection to allow connection to our flexible water hose
accessories.
Summary of Contents for RSDH0012
Page 13: ...SRV SVX04B EN 13 Fan Curve Figure 10...
Page 14: ...14 SRV SVX04B EN Wiring Diagrams Figure 11 Figure 12...
Page 15: ...Wiring Diagrams SRV SVX04B EN 15 Figure 13 Figure 14...
Page 16: ...Wiring Diagrams 16 SRV SVX04B EN Figure 15 Figure 16...
Page 17: ...Wiring Diagrams SRV SVX04B EN 17 Figure 17 Figure 18...
Page 18: ...Wiring Diagrams 18 SRV SVX04B EN Figure 19 Figure 20...