background image

When hooking a vacuum pump to a refrigeration system,
it is important to connect the pump to both the high and
low side of  the system.
Follow the pump manufacturer’s directions as to the
proper methods of  using the vacuum pump .
The lines used to connect the pump to the system should
be copper and of  the largest diameter that can pratically
be used. Using larger line sizes with minimum flow
resistance can significantly reduce evacuation time.
Rubber or synthetic hoses are not acceptable for unit
evacuation because they have moisture absorbing
characteristics which result in excessive rates of
outgassing and pressure rise during standing vacuum
test. This makes it impossible to determine if  the unit has
a leak.
An electronic thermopile vacuum gauge should be installed
in the common line ahead of  the vacuum pump shutoff
valve as shown in Figure 2. Close Valve B and open
Valve A. After several minutes, the gauge reading will
indicate the minimum blank-off  pressure the pump is
capable of pulling . Rotary pump should produce vacuum
of  less than 100 microns.
Open Valve B and evacuate the system to a pressure of
500 microns  or less. Valve A must be closed when taking
this reading. Once 500 microns or less is obtained, with
Valve A closed, a time versus pressure rise should be
performed. The maximum allowable rise over a 15 minute
period is 200 microns. If  pressure rise is greater than
200 microns but levels off  to a constant value, excessive
moisture is present. If  the pressure steadily continues to
rise, a leak is indicated.

5

Figure 2
Vacuum pump connection.

Electrical Connections

Wiring diagrams are furnished with the units, but extra
copies may be obtained from the local Trane sales office.
The installing contractor is to provide and install fused
disconnect switches and the wiring up to the unit control
panel. Check all wiring connections and trace the circuits
to make sure that they agree with the wiring diagrams.

Caution :

1. All wiring should comply with local and national
   codes. Type and location of  disconnect switches
    should comply with local and national codes. Install
    disconnect switch near unit, within sight, for safety.
2. Use copper conductors only for installation wiring.
    Unit terminals are not designed to accept other type
   of  wiring. The use of  aluminium wire may cause
  galvanic corrosion and/or overheating at the
   connection points with resultant equipment failure.

Unit Start-Up

Preparation for start-up
Before starting the unit, use the following procedures
to ensure that the unit is completely and
properly installed and ready for start-up.
The installer must make sure that the following points
are checked before the initial start-up.
1. Inspect all wiring connections. Connections should
    be clean and tight. Trace circuits to ensure that wiring
    agrees with wiring diagrams provided with the unit.
    Information in the title block of  the wiring diagram
    should match the data that appears on the unit
    nameplate.
2. Close the unit power fused disconnect switch and
    the manual disconnect switch.
3. Check the unit supply voltage to ensure that the
     voltage is within the utilization range.
4. Check the compressor oil level.
5. Check with a phase-meter the direction of  rotation
    of  scroll Trane compressors or check the good
    operation of  the discharge and suction pressures.
6. As the various motors of  the system are started,
    check the direction of  rotation and make sure that
    the driven equipment is operating satisfactorily.
7. Ensure sufficient cooling load available at day of
    start-up (minimum of  50% of  design load).

Preparation

Before putting the system into operation, perform these
service and check-out procedures :
1. Before making any electrical power connections make
    sure that the insulation resistance of  all power terminal
    to earth is in accordance with the international electrical
    codes. Measure the insulation of  all electrical motors
    using a 500 V DC tester and refer to the manufacturer’s
    specifications.

Warning :

No motor should be started if  the insulation resistance
is less than 2 mega ohms. Under no circumstances
should any voltage be applied to a motor while it is
under vacuum.

2. Check the unit supply voltage to ensure that the voltage
    is within the utilization range.

Caution :

Phase unbalance must not exceed 2% . Supply for all
motors is to be within plus or minus 5% of  the voltages
specified on the compressor nameplate.

3. Place all refrigerant circuit valves in operating position.

Installation

Summary of Contents for RAUP 250

Page 1: ...Installation Operation Maintenance Split System Condensing Units 20 55 Tons Models RAUP 400 RAUP 500 RAUP 600 RAUP 250 RAUP 300 RAUP IOM002 0806 August 2006 ...

Page 2: ... the goods within 72 hours of delivery Notify the local Trane Sales Office at the same time The unit should be totally inspected within 15 days of delivery If any concealed damage is discovered stop unpacking the shipment Take photos of the damaged material if possible Notify the Carrier immediately by phone and registered mail Notify the local Trane Sales office Concealed damage must be reported ...

Page 3: ...ion 3 Electrical Connections 5 Unit Start up 5 Operation Maintenance Unit Operation 7 Seasonal start up procedure 7 Maintenance Maintenance 7 Weekly Maintenance 7 Maintenance Inspections 8 Compressor Motor Winding Thermostat 9 Compressor Manifold Piping 9 10 to 12 Dimensional Data Dimensional Data Condensing Unit Trouble Analysis Installation Checklist Commissioning Log Sheet Wiring Diagram Schema...

Page 4: ... Installed Shipped Options 0 None 1 Corrosion Resistant Coated Fin 2 Suction Liquid Line Service Valves 3 Crankcase Heater 4 1 and 2 Corrosion Resistant Coated Fin Service Valves 5 1 2 and 3 Corrosion Resistant Coated Fin Service Valves Crankcase Heater 6 1 and 3 Corrosion Resistant Coated Fin Crankcase Heater 7 2 and 3 Service Valves Crankcase Heater A Service Indicator MODEL NOMENCLATURE EG 1 2 ...

Page 5: ... Propeller Propeller Propeller No used 2 3 3 4 6 Diameter in mm 28 710 28 710 28 710 28 710 28 710 No of Blade 4 4 4 4 4 Pitch Angle degree 29 29 29 29 29 Drive Type Direct Direct Direct Direct Direct Nominal Airflow3 cfm cmh 11 500 19 539 15 000 25 485 17 100 29 053 22 280 37 853 29 400 49 950 MOTOR No of Motor 2 3 3 4 6 Motor hp each hp kW 0 4 0 3 0 4 0 3 0 4 0 3 0 4 0 3 0 4 0 3 No of Speed 1 1 ...

Page 6: ... sufficient strength to support the unit s weight Lifting of the unit Four lifting lugs are provided at the base of each unit for crane lift Attach cable slings to each lug refer to Figure1 and install a spreader bar between the cable to protect the unit Make sure that the lifting equipment is capable of handling the weight of the unit Table 1 Clearances Provide sufficient clearance around the uni...

Page 7: ...r leak testing a violent explosion may result 3 Always use a pressure regulator valves and gauges to control drum and line pressures when pressure testing the system Excessive pressures may cause line ruptures equipment damage or an explosion resulting in personal injury Pressure test the liquid line and suction line at pressures dictated by local codes Charge enough refrigerant into the system to...

Page 8: ...unit within sight for safety 2 Use copper conductors only for installation wiring Unit terminals are not designed to accept other type of wiring The use of aluminium wire may cause galvanic corrosion and or overheating at the connection points with resultant equipment failure Unit Start Up Preparation for start up Before starting the unit use the following procedures to ensure that the unit is com...

Page 9: ...compressors Oil level Oil should be visible in the compressor under full load in the compressor oil level sight glass The unit was charged with the proper amount of oil before shipping Under normal operation compressor oil is always expected to return to compressor oil sump and no additional oil should be added For oil level indication refer to compressor oil sight glass as per Figure 3 If oil is ...

Page 10: ...LS Figure 3B EXPANSION VALVE CAPILLARY TUBES SIGHT GLASS STRAINER LIQUID LINE FROM RECEIVER EXPANSION VALVE SOLENOID LIQUID VALVE EXPANSION VALVE EXPANSION VALVE THERMAL BULBS EXPANSION VALVE EQUALIZER LINES SUCTION LINE TO COMPRESSOR Figure 3A Maintenance The following maintenance are given as an essential part of the required maintenance of this equipment However the services of a qualified serv...

Page 11: ...es The following procedures should be carried out by a qualified service technician as part of a maintenance contract The first and last visit will include the seasonal shut down and start up procedures when applicable as detailed on the section on operation The visits should include the following procedures Inspect contacts of motor contactors Check setting and function of each system control Per...

Page 12: ...red install it a minimum of 18 upstream of the compressor manifold piping See Figure 4 Caution Altering the original manifold piping may cause oil compressor failure This sequence is of most importance because it maximizes lubrication and ensure proper oil return Secondly the design of the oil return with equalizer is critical The lead compressor must always be in the lead in the sequence Should i...

Page 13: ...ide or fuse Voltmeter does not read proper voltage Motor starter holding coil is not energized Compressor will not operate Open contact on high pressure switch Discharge pressure above cut in setting Probable cause Burned out motor Burned out holding coil or broken contacts Safety control of thermal overload relays has cut outs a Power failure b Disconnect switch open Fuse down Replace fuse Low vo...

Page 14: ...nt oil charge Clogged filter drier Liquid flooding back to compressor Recommended action All oil Replace Readjust superheat setting and verify correct bulb mounting F Compressor is noisy Problems and symptoms Abnormally cold suction line compressor knocks Valve bulb attachment Compressor noisy Probable cause a Liquid flood back b Expansion Valve stuck in open position Incorrect direction of rotati...

Page 15: ...far a Adjust superheat and check flood back to compressor bulb attachment b Expansion valve stuck in open b Repair or replace position L Discharge pressure too high Problems and symptoms Probable cause Recommended action Bubbles in sight glass Lack of refrigerant Repair leak add refrigerant High pressure drop across Clogged filter drier Replace filter drier No refrigerant flow through Expansion va...

Page 16: ...13 ...

Page 17: ...14 ...

Page 18: ...15 ...

Page 19: ...16 ...

Page 20: ...17 ...

Page 21: ... SWITCH FUSED L2 L1 N L3 INPUT MCB T1 J2 SUPPLY POWER 0 240 33 30 T3 32 30 31 MODULE STARTER CONTROLLER STEP 1 COMPR 1 STEP 2 COMPR 2 C1 C2 CF1 CF2 J1 EVF C AUX A C2 A C1 0L2 C5 TB START STOP MCB FUSED DISCONNECT SWITCH EVF C EVF OL EVF C EVF OL EVF SEE UNIT NAMEPLATE FOR LINE VOLTAGE 5T3 5T2 5T1 E 240 V CONTROL WIRING SCHEMATIC TERMINATION DIAGRAM RAUP250 DISCONNECT ALL ELECTRIC POWER INCLUDING R...

Page 22: ...ABB 1P 6A DESCRIPTION DESCRIPTION COMP 1 POWER LINE COMP 2 POWER LINE 1 4 3 1 1 QTY QTY CONTROL LINE CONTROL LINE COMP 1 ADD FOR CCH OPTION ADD FOR CCH OPTION 9 9 8 8 4 4 390mm 390mm 14 12 A C1 A C1 12 14 A C2 A C2 C5 C5 MCB 11 11 CONTROLLER CONTROLLER MODULE MODULE STARTER STARTER 255mm 6 6 7 7 1 1 J2 J2 TB T2 T1 T7 T6 T3 T4 T5 J1 J1 800mm L1 L1 L2 L2 L3 L3 N E E 200mm 3 3 13 1TB5 1TB5 5T1 E E 5T...

Page 23: ...D SW3 BUTTON FOR 4 SECONDS TO 4 EVF INTERLOCK T1 T2 TB T3 MCB TERMINATION CONTROL 32 33 30 N TO TEMP CONTROLLER STEP 2 TO TEMP CONTROLLER STEP 1 RAUP MODEL ONLY NO AC SIGNALAT INPUTS CONTACT INPUTS ONLY WARNING COM 0 JUMPER JUMPER HMWT 4 COM 0 HMWT 3 OL 4 OL 3 HPCO 2 COM 0 JUMPER JUMPER JUMPER S4 LPCO 2 COM 0 COM 0 S3 S2 COMP START UP TIMING A CIRCUIT A C1 ON DELAY TIME 1 min A CIRCUIT A C2 ON DEL...

Page 24: ... J2 31 OUTPUT J3 INPUT J1 L2 L1 PT SWITCH DISCONNECT FUSED L2 L1 STEP 2 COMPR 2 STEP 1 C1 COMPR 1 C2 0L1 CF1 CF2 0L2 A C1 A C2 N L3 EVF C AUX CF3 C5 TB MCB FUSED DISCONNECT SWITCH N L3 STOP START EVF OL EVF C EVF C EVF OL EVF 240 V CONTROL WIRING SCHEMATIC TERMINATION DIAGRAM RAUP300 DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING FAILURE TO DISCONNECT POWER BEFORE SERV...

Page 25: ...TOTAL 8 8 9 9 7 7 5 5 6 6 4 4 2 2 1 2 1 1666 7 700 1 4 1 1 TRANSFORMER 240V 21V 8V 30VA STARTER CONTROLLER VERSION 1 1 2 2 NO NO 1 1 DESCRIPTION DESCRIPTION COMP 1 POWER LINE OL 1 OL 1 OL 2 OL 2 12 12 8 8 4 4 6 6 7 7 11 11 COMP 2 POWER LINE 385mm 1 1 255mm J2 J2 J4 J4 J5 J5 COMP 1 CONTROL LINE CONTROL LINE 1 QTY QTY 1 CONTROL LINE CONTROL LINE 240V 24V TX1 226mm COMP 2 L1 L1 FOR ILLUSTRATION ONLY ...

Page 26: ...CONDS TO CLEAR THE MEMORABLE ERROR 4 EVF INTERLOCK MCB T3 T1 T2 TB TERMINATION CONTROL 30 N 32 33 ALM NO ALM NC COM COM 5 COM 4 B C4 COM 2 B C3 A C2 COM 1 A C1 OUTPUT COM 3 JUMPER JUMPER JUMPER JUMPER JUMPER TO TEMP CONTROLLER STEP 2 TO TEMP CONTROLLER STEP 1 COM 0 S1 S4 7 SEGMENT DISPLAY CODE TABLE 7 Segment Display COM 0 S4 O3 O4 t4 t3 H2 HMWT 4 COM 0 HMWT 3 OL 4 S3 S2 S1 COM 0 L1 H1 O1 O2 L2 t1...

Page 27: ... T2 STARTER CONTROLLER J5 30 0 POWER SUPPLY J4 MODULE OUTPUT 30 J2 T1 32 STEP 3 MCB 31 STEP 2 INPUT STEP 4 CF1 COMPR 1 C1 A C1 OL1 FUSED DISCONNECT SWITCH PT L3 L1 L2 N OL4 C2 C3 OL2 A C2 OL3 B C3 C4 COMPR 4 B C4 EVF C AUX MCB STOP START EVF OL EVF C FUSED DISCONNECT SWITCH L3 SEE UNIT NAMEPLATE FOR LINE VOLTAGE L2 L1 N EVF C EVF OL EVF J3 FOR RAUP500 ONLY J1 CF3 CF4 C5 TB 5T3 5T2 5T1 E 240 V CONT...

Page 28: ...V 8 V 30 VA 6mm COMP 1 COMP 2 6mm 6mm 2 2 SIZE CABLE 2 POWER 3 _ _ _ 6 5 4 LENGTH TOTAL 1 2 NO COMPRESSOR 4 POWER LINE COMPRESSOR 3 POWER LINE 374mm 6 3 4 1 1 QTY 1 1 COMPRESSOR 2 POWER LINE ADD FOR CCH OPTION CIRCUIT A CONTROL LINE FOR ILLUSTRATION ONLY 1TB5 500 mm T3 MODULE STARTER CONTROLLER CIRCUIT B CONTROL LINE J1 10 J3 1000mm TX1 240V 21 8V 1 J2 9 T2 T1 TB 9 J5 J4 2 8 L3 PT 7 L1 L2 COLOR IS...

Page 29: ...2 30 N CIRCUIT A CIRCUIT B COM 1 A C2 A C1 B C4 B C3 C5 COM ALM NO COM 4 COM 2 COM 3 ALM NC COM 5 OUTPUT THERMOSTAT STATUS S1 S4 44 TO TEMP CONTROLLER STEP 1 TO TEMP CONTROLLER STEP 2 TO TEMP CONTROLLER STEP 4 TO TEMP CONTROLLER STEP 3 46 45 45 41 40 40 39 LPCO 2 NORMAL 7 SEGMENT DISPLAY CODE TABLE Error Description OL 1 Error OL 2 Error OL 3 Error OL 4 Error HPCO 2 Error HMWT 3 Error HMWT 4 Error...

Page 30: ...C5 TB C1 C2 C3 C4 COMPRESSOR TERMINATION BLOCK CONTROL TERMINATION BLOCK STARTER CONDENSOR FAN FACTORY INSTALLED POWER TERMINALS CIRCUIT BREAKER SYSTEM SWITCH FAN CONDENSOR TRANSFORMER 240V 21V 8V EVAPORATOR FAN CF 1 2 3 4 5 6 S1 EVF C5 PT MCB TB TX1 CRANKCASE HEATER CCH 35 L2 240 V CONTROL WIRING STARTER CONTROLLER MODULE EVF INTERLOCK T2 33 SUPPLY 30 3 T3 T1 32 240V 30 33 POWER MCB 31 J2 0 240 T...

Page 31: ... 1 4 516 2646 2 4 4 1 3 1 QTY 1 1 COMPONENT LAY OUT POWER WIRING RAUP600 J5 COMPRESSOR 4 POWER LINE COMPRESSOR 3 POWER LINE E 7 CONTROL LINE 374mm CIRCUIT B CONTROLLER MODULE J1 J2 STARTER 1000mm 10 J3 J4 PT L3 N L1 L2 POWER CABLES SHOWN IN COLOR COLOR IS BLACK OR RED THE ACTUAL POWER CABLE FOR ILLUSTRATION ONLY 3 10 COMPRESSOR 2 POWER LINE 9 345mm 6 T3 T2 T1 T7 T4 T6 T5 ADD FOR CCH OPTION TX1 240...

Page 32: ...ONTR OL 30 B C M 32 33 58 TO TEM P CONTR OLLER STE P 3 TO TEM P CONTR OLLER STE P 4 TO TEM P CONTR OLLER STE P 2 TO TEM P CONTR OLLER STE P 1 42 50 55 56 57 57 54 51 53 54 52 51 47 46 43 43 46 44 45 39 41 40 40 HMWT 4 THERMOS TAT S TATUS S1 S4 S3 COM 0 S4 COM 0 S2 S1 HMWT 4 Error OL 3 Error HPCO 2 Error LPCO 2 Error HMWT 3 Error OL 4 Error t4 t3 O4 O3 H2 L2 LPCO 1 Error HPCO 1 Error HMWT 1 Error H...

Page 33: ...e Check oil traps presence on discharge line if there vertical risers 3m Check pitch for horizontal lines 1cm m Check refrigerant presence Electrical equipment Check direction of rotation of compressors and fan motors Check installation and rating of mains power switch fuse Check that electrical connections comply with specification Check that electrical connections match information on manufactur...

Page 34: ... 1 Comp No 2 Comp No 3 Comp No 4 T1 T1 T1 T1 T2 T2 T2 T2 T3 T3 T3 T3 Voltage Imbalance Comp 1 Comp 3 Comp 2 Comp 4 B Amp Draw Comp No 1 Comp No 2 Comp No 3 Comp No 4 T1 T1 T1 T1 T2 T2 T2 T2 T3 T3 T3 T3 3 Operating Conditions A Circuit A Discharge Pressure Liquid Line Pressure Liquid Line Temp Subcooling Amblent Temp Suction Pressure Suction Line Temp SuperHeat Evap Entering Air Temp DB WB Evap Dis...

Page 35: ...06 RAUP IOM002 0705 Trane has a policy of continuous product and product data implement and reserves the right to change design and specifications without notice http www tranethailand com A Business of American Standard Company ...

Reviews: