23
HMWT1
HMWT2
OL2
OL1
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS
BEFORE SERVICING.
FAILURE TO DISCONNECT POWER
BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
IMPORTANT
USE COPPER CONDUCTORS ONLY
TO PREVENT EQUIPMENT DAMAGE.
UNIT TERMINALS ARE NOT DESIGNED
TO ACCEPT ANY OTHER WIRING.
WARNING
HAZARDOUS VOLTAGE!
3
REMOVE JUMPER WHEN TEMPERATURE CONTROLLER
CIRCUITRY OR AVAILABLE SALES OPTIONS.
COMPONENTS PROVIDED BY THE FIELD. PHAN TOM
AND/OR DASHED DEVICE OUTLINES INDICATE
WIRING BY OTHERS. DASHED LINE ENCLOSURES
DASHED LINES INDICATE RECOMMENDED FIELD
REMOVE JUMPER TO INTERFACE WITH EVF
SOLID LINE INDICATES FACTORY WIRING.
LINE ENCLOSURES INDICATE ALTERNATE
INTERLOCK
IS INSTALLED
3
2
NOTES:
1
2
2
THE 7-SEG WILL OFF FOR 2 SECONDS BEFORE DISPLAY THE
EACH LOCKOUT. AFTER THAT THE 7-SEG WILL OFF FOR
MOMORABLE ERROR CODES THAT ARE THE CAUSES OF
PRESS SW3 BUTTON FOR SHOW THE MEMORABLE ERROR.
2 SECONDS AND RETURN TO DISPLAY THE EXISTING
THEY ARE DISPLAYED 2 SECOND EACH.IF THERE IS NOT ANY
ERROR/STATUS CODES.IF MORE THAN 1 ERROR HAPPENS,
MEMORABLE ERRORS,THE NORMAL CODE WILL BE DISPLAYED.
PRESS AND HOLD SW3 BUTTON FOR 4 SECONDS TO
CLEAR THE MEMORABLE ERROR.
4
EVF INTERLOCK
MCB
T3
T1 T2
TB
TERMINATION (CONTROL)
30
N
32
33
ALM/NO
ALM/NC
COM
COM 5
COM 4
B-C4
COM 2
B-C3
A-C2
COM 1
A-C1
OUTPUT
COM 3
JUMPER
JUMPER
JUMPER
JUMPER
JUMPER
TO TEMP. CONTROLLER STEP 2
TO TEMP. CONTROLLER STEP 1
COM 0
S1 - S4
7 SEGMENT DISPLAY CODE TABLE
7 Segment Display
COM 0
S4
O3
O4
t4
t3
H2
HMWT 4
COM 0
HMWT 3
OL 4
S3
S2
S1
COM 0
L1
H1
O1
O2
L2
t1
t2
--
OL 4 Error
OL 3 Error
HMWT 4 Error
HMWT 3 Error
HPCO 2 Error
THERMOSTAT STATUS
CIRCUIT B
LPCO 1 Error
OL 2 Error
OL 1 Error
LPCO 2 Error
HPCO 1 Error
HMWT 1 Error
HMWT 2 Error
NORMAL
Error Description
CIRCUIT A
WARNING :
COMP. : START-UP TIMING
RESET 2
RESET 1
A CIRCUIT A-C1 ON DELAY TIME = 1 min
A CIRCUIT A-C2 ON DELAY TIME = 2 min
SYSTEM RESET : = RESET SYSTEM ON ERROR
SYSTEM RESET
RESET 2 = RESET CIRCUIT B ON ERROR
RESET 1 = RESET CIRCUIT A ON ERROR
-
OL 3
HPCO 2
LPCO 2
COM 0
-
COM 0
HMWT 1
HMWT 2
46
45
45
44
OL 1
COM 0
HPCO 1
COM 0
LPCO 1
INPUT
OL 2
39
41
42
42
39
40
43
38
J1
RAUP MODEL ONLY
- NO AC SIGNAL AT INPUTS
- CONTACT INPUTS ONLY
FAN FOR
COMPRESSORS
TYPICAL WIRING FOR RAUP 300
A CIRCUIT
J5
LIGHT
TRIP
N
L (240 V)
J4
C5
33
36
T3
T2
C5
33
35
33
J3
34
A-C2
A-C1
RESET 3
STARTER CONTROLLER MODULE - I/O WIRING :-RAUP300
INPUT: USE BLACK COLOR 0.5 SQMM.
C1
CONTR
O
L BO
X
C2
OUTPUT: USE BLACK 1 SQMM.
HPCO1
LPCO1
240V/21, 8V
TX1
Termination Diagram
Schematic &
RAUP 300