Table 2 - R134a Units Characteristics 

RAU 190

RAU 260

RAU 300

RAU 350

RAU 400

RAU 450

RAU 500

RAU 600

RAU 700

RAU 800

R134a

R134a

R134a

R134a

R134a

R134a

R134a

R134a

R134a

R134a

Performances (1)

Gross cooling capacity (1)

(kW)

43,8

53,2

63,9

75,4

85,1

93,6

106,3

127,9

153,8

172,7

Power input in cooling (1)

(kW)

12,1

15,8

18,5

21,3

24,3

27,7

31,5

37,0

47,1

53,9

Main Power supply

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

Sound Power Level (5)

(dB(A))

88

90

91

91

92

93

93

94

98

98

Units
Amps

Nominal (4)

(A)

25,4

32,4

39,4

45,1

52,1

59,1

64,8

78,8

90,2

104,2

Start-up Amps

(A)

137

193

202

210

219

228

236

255

271

289

Max supply cable size

(mm

2

)

35

35

35

50

50

95

95

95

150

150

Compressor

Number

2

2

2

3

3

3

4

4

6

6

Type

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Model

10T+10T

10T+15T

2x15T

2x10T+15T 10T+2x15T

3x15T

2x(10T+15T)

4x15T

4x10T+2x15T

2x10T+4x15T

Speeds number

1

1

1

1

1

1

1

1

1

1

Motors Number

1

1

1

1

1

1

1

1

1

1

Rated Amps (2)(4)

(A)

30

42

50

55

65

75

84

101

109

130

Locked rotor Amps (2)

(A)

120

175

175

175

175

175

175

175

175

175

Motor RPM

(rpm)

2900

2900

2900

2900

2900

2900

2900

2900

2900

2900

Sump Heater (2)

(W)

50W - 400V 50W - 400V 50W - 400V 50W - 400V 50W - 400V

50W - 400V

50W - 400V

50W - 400V

50W - 400V

50W - 400V

Liquid and Suction connection

Suction connection

brazed

1"5/8

1"5/8

1"5/8

1"5/8

1"5/8

1"5/8

1"5/8

1"5/8

2"1/8

2"1/8

Liquid connection

brazed

7/8"

7/8"

7/8"

7/8"

7/8"

7/8"

7/8"

7/8"

1"1/8

1"1/8

Coil

Type

Plate Fin

Plate Fin

Plate Fin

Plate Fin

Plate Fin

Plate Fin

Plate Fin

Plate Fin

Plate Fin

Plate Fin

Tube size

(mm)

9,52

9,52

9,52

9,52

9,52

9,52

9,52

9,52

9,52

9,52

Tube type

Smooth

Smooth

Smooth

Smooth

Smooth

Smooth

Smooth

Smooth

Smooth

Smooth

Height

(mm)

1219

1219

1219

1219

1219

1219

1219

1219

1219

1219

Length

(mm)

2743

2743

2743

3455

4115

4115

5486

5486

5486

5486

Face Area

(m

2

)

3,34

3,34

3,34

4,21

5,02

5,02

6,69

6,69

6,69

6,69

Rows

#

2,0

2,0

3,0

3,0

3,0

3,0

2,0

3,0

3,0

3,0

Fins per foot (fpf)

#

156,0

156,0

156,0

156,0

156,0

156,0

156,0

156,0

156,0

156,0

Fan

Type

Propeller

Propeller

Propeller

Propeller

Propeller

Propeller

Propeller

Propeller

Propeller

Propeller

Number

2

2

2

3

3

3

4

4

6

6

Diameter

(mm)

962

962

962

962

962

962

962

962

962

962

Drive type

Direct

Direct

Direct

Direct

Direct

Direct

Direct

Direct

Direct

Direct

Speeds number

1

1

1

1

1

1

1

1

1

1

Air flow

(m

3

/h)

27000

27000

25300

35900

37900

37900

54000

50700

89100

89100

Motors Number

2

2

2

3

3

3

4

4

6

6

Motor HP (2)

(kW)

0,85

0,85

0,85

0,85

0,85

0,85

0,85

0,85

1,88

1,88

Rated Amps (2)

(A)

2,4

2,4

2,4

2,4

2,4

2,4

2,4

2,4

4,2

4,2

Locked rotor Amps (2)

(A)

6,8

6,8

6,8

6,8

6,8

6,8

6,8

6,8

14,7

14,7

Motor RPM

(rpm)

680

680

680

680

680

680

680

680

915

915

Dimensions

Height

(mm)

1582

1582

1582

1582

1582

1582

1584

1584

1598

1598

Length

(mm)

2061

2061

2061

2921

2921

2921

2225

2225

3090

3090

Width

(mm)

995

995

995

995

995

995

1865

1865

1948

1948

Weight uncrated

(kg)

514

584

650

810

900

926

1040

1168

1575

1634

Weight crated

(kg)

555

625

691

869

959

985

1123

1251

1695

1754

System Data

Refrigerant  circuit

1

1

1

2

2

2

2

2

2

2

Refrigerant Charge (3)

Circuit A & B

(kg)

(1) at 7°C SST and 35°C ambiant
(2) per motor
(3) per circuit
(4) 5°C sat suction temp. - 60°C sat discharge temp.
(5) In accordance with ISO 3746

Split

system

Split

system

Split

system

Split

system

Split

system

Split

system

Split

system

Split

system

Split

system

Split

system

Summary of Contents for RAU-SVX01B-E4

Page 1: ...Installation Operation Maintenance RAU Air Cooled Condensing Unit Sizes 190 260 300 350 400 450 500 600 700 800 RAU SVX01B E4 To be used with the manual of SMM module Reference L80 IM 022 E...

Page 2: ...st to the last carrier of the goods within 72 hours of delivery Notify the local Sales Office at the same time The unit should be totally inspected within 7 days of delivery If any concealed damage is...

Page 3: ...acteristics 7 Electrical connections 10 General start up Preparation 11 Start up 11 Operation Control and unit operation 13 Seasonal shutdown and start up 13 Weekly start up and week end shutdown 13 M...

Page 4: ...does not allow to install spring isolators Clearance Respect recommended clearance around the unit to allow maintenance operation to take place without obstruction and recommended clearance around co...

Page 5: ...ing itself to avoid transmission to building structure of vibrations normally caused by pipework Also avoid bypassing the unit s damping system by fixing the refrigerant lines or the electrical ducts...

Page 6: ...alist who has performed this start up The quantiy of refrigerant and oil added are at the client s charges Refrigerant charge all split system types After system pressure and vacuum testing fill up un...

Page 7: ...e size mm 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 Tube type Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Height mm 1219 1219 1219 1219 1219 1219 1219 1219 1219 1219...

Page 8: ...ate Fin Tube size mm 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 Tube type Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Height mm 1219 1219 1219 1219 1219 1219 1219 1219...

Page 9: ...9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 9 52 Tube type Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Height mm 1219 1219 1219 1219 1219 1219 1219 1219 1219 1219 Length mm 2743...

Page 10: ...s the transformer If the transformer is not ordered it is necessary to foresee the power supply of the electronic module separately Warranty reserves will be formulated if a transformer not supplied b...

Page 11: ...ing the isolators located under the rails supporting the compressor Put the plexiglass supplied by Trane in front of the power terminal Ensure all refrigerant valves are in service positions Ensure th...

Page 12: ...C With 407c it should be 20 to 23 C Final check When the unit is operating correctly Check that the unit is clean and clear of any debris tools etc All valves are in operating position Close control...

Page 13: ...g pressures temperatures amperages and voltage Check operation of machines compare conditions of operation against original commissioning data Push button O of the module Insure that all safeties are...

Page 14: ...ck operation of all safety devices Inspect contacts tighten terminals Megger the motor compressor windings Record operating pressures temperatures amperages and voltage Carry out leak test Check confi...

Page 15: ...dryer and sight glass presence Check oil traps presence on discharge line if there vertical risers 3m Check pitch for horizontal lines 1cm m Check refrigerant presence Electrical equipment Check direc...

Page 16: ...circuit open Compressor sticking damaged or sticking components Discharge pressure too high Discharge pressure too high a Voltage too low b Cooling demand too high or condensing temperature too high N...

Page 17: ...neven liquid flow b Expansion valve locked in open position Not enough refrigerant Drier filter clogged Superheat not properly adjusted Presence of uncondensable liquids in system or excess refrigeran...

Page 18: ...too low Excessive pressure drop through filter drier Refrigerant does not flow through thermostatic expansion valve Loss of power Superheat too low Excess cooling demand on evaporator a Expansion valv...

Page 19: ...15 8 4 1 17 3 4 1 4 C 16 2 4 4 18 2 4 4 20 4 4 4 22 8 4 4 13 0 4 4 14 1 4 4 15 4 4 4 16 8 4 4 2 C 16 6 4 7 18 6 4 7 20 8 4 7 23 2 4 7 12 8 4 7 13 9 4 7 15 1 4 7 16 5 4 7 18 0 4 7 0 C 17 0 5 0 19 0 5...

Page 20: ...3 6 8 29 1 6 8 19 3 6 8 21 4 6 8 23 8 6 8 26 3 6 8 29 0 6 8 Saturated suction temperature Table 5 RAU 700 R22 RAU 800 R22 Outdoor AmbientTemperature C 25 C 30 C 35 C 40 C 45 C 25 C 30 C 35 C 40 C 45...

Page 21: ...1 2 2 6 C 10 1 2 3 10 9 2 3 11 9 2 3 13 4 2 3 15 1 2 3 9 9 2 3 10 8 2 3 11 7 2 3 12 6 2 3 13 7 2 3 4 C 9 9 2 5 10 7 2 5 12 0 2 5 13 6 2 5 15 3 2 5 9 8 2 5 10 5 2 5 11 4 2 5 12 4 2 5 13 4 2 5 2 C 9 8 2...

Page 22: ...12 3 4 2 13 9 4 2 15 6 4 2 17 4 4 2 10 9 4 2 12 3 4 2 13 8 4 2 15 5 4 2 17 3 4 2 Saturated suction temperature Table 10 RAU 700 R134a RAU 800 R134a Outdoor AmbientTemperature C 25 C 30 C 35 C 40 C 45...

Page 23: ...7 1 9 22 9 29 6 4 4 1 3 7 6 19 0 48 2 43 2 44 0 85 5 83 0 2 0 21 7 28 4 4 5 0 6 7 0 20 0 50 3 45 4 45 0 86 6 84 2 2 1 20 5 27 2 4 6 0 0 6 3 21 0 52 3 47 5 46 0 87 6 85 4 2 2 19 4 26 1 4 7 0 6 5 7 22...

Page 24: ...15 1 3 7 16 6 3 7 18 2 3 7 4 C 16 4 4 0 18 6 4 0 21 0 4 0 23 6 4 0 26 5 4 0 12 3 4 0 13 4 4 0 14 7 4 0 16 1 4 0 17 7 4 0 2 C 16 8 4 3 19 0 4 3 21 4 4 3 24 0 4 3 27 0 4 3 12 1 4 3 13 2 4 3 14 4 4 3 15...

Page 25: ...6 6 4 30 6 6 4 19 7 6 4 22 0 6 4 24 6 6 4 27 4 6 4 30 4 6 4 DewTemperature At Evaporating Pressure Table 16 RAU 700 R407C RAU 800 R407C Outdoor AmbientTemperature C 25 C 30 C 35 C 40 C 45 C 25 C 30 C...

Page 26: ...control validation B08 Auxiliary set point validation B09 Current date display B091 Day B092 Month B093 Year B10 Current time display B101 Hours B102 Minutes B103 Seconds B11 Set this parameter to 0...

Page 27: ...27 RAU SVX01B E4 Notes...