12

PTAC-SVX002A-EN

Voltage Supply

Check voltage supply at outlet. For satisfactory results, the voltage range must always be within
the ranges specified on the data information plate. Power cord does not ship with the unit. The
cord to order is determined by the unit voltage and the desired electric heat capacity.

Cord/Connected Units

The 250 Vac field supplied outlet must match the plug for standard 208/230V units and be within
reach of the service cord.

N

No

otte

e:: Do NOT use 30 amp cord with size 07 units.

Table 2.

Electric Heater and Cord Information, PTEF07xxx and PTHF07xxx

Voltage

230 Vac

265 Vac

Amps

15

20

15

20

Heater Size

2.5 kW

3.5 kW

2.5 kW

3.5 kW

Plug Layout

G

G

G

W

G

W

NEMA Plug

6-15P

6-20P

7-15P

7-20P

Cord #

PWR00286

PWR00288

PWR00287

PWR00289

Table 3.

Electric Heater and Cord Information, PTEF and PTHF Size 09, 12, and 15

Voltage

230 Vac

265 Vac

Amps

15

20

30

15

20

30

Heater Size

2.5 kW

3.5 kW

5.0 kW

2.5 kW

3.5 kW

5.0 kW

Plug Layout

G

G

G

G

W

G

W

G

W

NEMA Plug

6-15P

6-20P

6-30P

7-15P

7-20P

7-30P

Cord #

PWR00286

PWR00288

PWR00290

PWR00287

PWR00289

PWR00291

Power Cord Protection

N

No

otte

e:: Power cord does not ship with the unit.

The power cord for 230/208V units provide protection from fire. The unit power automatically
disconnects when unsafe conditions are detected. Power to the unit can be restored by pressing
the reset button on plug head. Upon completion of unit installation for 230/208V models, an
operational check should be performed using the TEST/RESET buttons on the plug head.

N

No

otte

e:: Models with 265V do not incorporate this feature because they require use of an electrical

sub-base accessory. Connection to a wall socket is not permitted for 265V units. All 265V
units must be hard wired using the hard wire kit or make use of the plug-in receptacle in
the standard sub-base.

E

Elle

eccttrriicca

all

Summary of Contents for ProSpace PTEF

Page 1: ...es specific knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precaut...

Page 2: ...rants that contain Chlorine Fluorine and Carbon CFCs and those containing Hydrogen Chlorine Fluorine and Carbon HCFCs Not all refrigerants containing these compounds have the same potential impact to...

Page 3: ...l P PP PE E i in n a ac cc co or rd da an nc ce e w wi it th h O OS SH HA A N NF FP PA A 7 70 0E E o or r o ot th he er r c co ou un nt tr ry y s sp pe ec ci if fi ic c r re eq qu ui ir re em me en nt...

Page 4: ...revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks referenced in this document are the...

Page 5: ...11 All Units 11 Grounding 11 Voltage Supply 12 Cord Connected Units 12 Power Cord Protection 12 Installation 13 Trane Wall Sleeve and Grille 13 Considerations for Use of Existing Sleeves 13 Installing...

Page 6: ...6 PTAC SVX002A EN Front Panel and Case 27 Outdoor Coil 27 Base Pan 27 Air Filter 27 Troubleshooting 29 T Ta ab bl le e o of f C Co on nt te en nt ts s...

Page 7: ...oling with Electric Heat H Heat Pump with Electric Heat D Di ig gi it t 4 4 D De ev ve el lo op pm me en nt t S Se eq qu ue en nc ce e F D Di ig gi it t 5 5 t th hr ro ou ug gh h 7 7 S Si iz ze e a an...

Page 8: ...or optimum quietness The indoor fan always runs at a minimum of 10 seconds before the compressor in order to reduce the sound of the compressor starting Random Compressor Restart The compressor is equ...

Page 9: ...s the Dual 8 displays a ten digit the unit digit at first and then displays BLANK hundred digit Fan Configuration Optimization for Selected Application The unit can be optimized for selected applicat...

Page 10: ...ed from a different location If the unit detects 24 Vac on this input it automatically turns itself OFF If no voltage is detected on the input the unit runs normally Wall Thermostat Control a wired wa...

Page 11: ...erage requirements for example electric heater size The unit ships without a power cord N No ot te e Ensure the outlet matches the appropriate prong configuration on the plug It should be within reach...

Page 12: ...e 09 12 and 15 Voltage 230 Vac 265 Vac Amps 15 20 30 15 20 30 Heater Size 2 5 kW 3 5 kW 5 0 kW 2 5 kW 3 5 kW 5 0 kW Plug Layout G G G G W G W G W NEMA Plug 6 15P 6 20P 6 30P 7 15P 7 20P 7 30P Cord PWR...

Page 13: ...s c co ou ul ld d r re es su ul lt t i in n d de ea at th h o or r s se er ri io ou us s i in nj ju ur ry y W Wh he en n i it t i is s n ne ec ce es ss sa ar ry y t to o w wo or rk k w wi it th h l li...

Page 14: ...lity for costs or damage due to defects in the sleeve or for improper installation Remove any existing foam baffles installed on competitor s outdoor grille General Electric Metal Wall Sleeve intercha...

Page 15: ...ab bo ov ve e t th he e u un ni it t t to o p pr re ev ve en nt t t th he e s st tr ra ap ps s f fr ro om m c cr ru us sh hi in ng g t th he e u un ni it t c ca ab bi in ne et t o or r d da am ma ag g...

Page 16: ...ts firmly against front of wall sleeve 5 Secure with four screws supplied through the unit flange holes 6 Re install front panel by first hooking tabs over top rail of unit and then pushing in on the...

Page 17: ...Direction Only for Duct Installations 1 Remove front panel 2 Remove louver screws that hold the louver insert in place on the back side of the front panel 3 Turn louver insert and rotate it 180 4 Repl...

Page 18: ...y Heating Electric Heat Only Heat Pump Down For only heat pump units 2 Wall Thermostat Enable A wired wall thermostat can be connected to the unit The dip switch must be adjusted accordingly in order...

Page 19: ...simultaneously either the S Se et tp po oi in nt t or S Se et tp po oi in nt t buttons Choose from the following four 4 options F Fa ah hr re en nh he ei it t C Ce el ls si iu us s D Di is sp pl la ay...

Page 20: ...nd E Em me er rg ge en nc cy y A Au ut to o C Co oo ol li in ng g R Re ej je ec ct te ed d displays as CD 7 When activating Auto Cooling Operation and room temperature reaches 85 F while the unit is i...

Page 21: ...nd di iv vi id du ua al l w wh ho o h ha as s b be ee en n p pr ro op pe er rl ly y t tr ra ai in ne ed d i in n h ha an nd dl li in ng g l li iv ve e e el le ec ct tr ri ic ca al l c co om mp po on n...

Page 22: ...ATUS LED indicator on main board 5 Reinstall terminal connector 6 Ensure that unit is configured for wall thermostat enable 7 Replace control panel label with control panel guard 8 Power up the unit G...

Page 23: ...of diagnostic codes Table 5 Diagnostic Codes Diagnostic Code Code Description Explanation 1 Indoor air temp sensor open or short An 8 segment display Fl STATUS light flashes once an then OFF 3 seconds...

Page 24: ...me er r P Pr re ev vi ie ew w f fu un nc ct ti io on n use this function to preview the remaining time of timer S Sl le ee ep p f fu un nc ct ti io on n can only be set only using the remote controll...

Page 25: ...in size for each speed When initializing the fan the AUTO setting is default N No ot te e Only LOW Fan Mode can be selected in DRY mode Pressing this key can not adjust the fan speed but can send mess...

Page 26: ...TC CH H O ON NS SW WI IT TC CH H O OF FF F states The unit show the LOCK icon when in LOCK Mode in which case the lock icon flashes three 3 times upon operation of any key The LOCK icon does not disp...

Page 27: ...ned N No ot te e Never use a high pressure sprayer on the coil Base Pan Periodically check the base pan and clean if required Air Filter I Im mp po or rt ta an nt t Do not the operate unit without fil...

Page 28: ...nt filter Clean outdoor orifice and fan Clean indoor coil Never use high pressure spray on coils Clean indoor fan wire screen and front panel Clean or install new indoor air inlet filter s Clean wall...

Page 29: ...been turned OFF to prevent tripping of the compressor overload Ensure that curtains blinds or furniture are not restricting or blocking unit airflow Reset to a lower or higher temperature setting Remo...

Page 30: ...ressor Restart whenever the unit is plugged in or the power has been restarted a random compressor restart occurs After a power outage the compressor restarts after approximately three 3 minutes Compr...

Page 31: ...PTAC SVX002A EN 31 N No ot te es s...

Page 32: ...folio of advanced controls and HVAC systems comprehensive building services and parts For more information visit www Trane com Trane has a policy of continuous product and product data improvements an...

Reviews: