Voltage Supply
Check voltage supply at outlet. For satisfactory results, the voltage range must always be within
the ranges specified on the data information plate. Power cord does not ship with the unit. The
cord to order is determined by the unit voltage and the desired electric heat capacity.
Cord/Connected Units
The 250 Vac field supplied outlet must match the plug for standard 208/230V units and be within
reach of the service cord.
N
No
otte
e:: Do NOT use 30 amp cord with size 07 units.
Table 2.
Electric Heater and Cord Information, PTEF07xxx and PTHF07xxx
Voltage
230 Vac
265 Vac
Amps
15
20
15
20
Heater Size
2.5 kW
3.5 kW
2.5 kW
3.5 kW
Plug Layout
G
G
G
W
G
W
NEMA Plug
6-15P
6-20P
7-15P
7-20P
Cord #
PWR00286
PWR00288
PWR00287
PWR00289
Table 3.
Electric Heater and Cord Information, PTEF and PTHF Size 09, 12, and 15
Voltage
230 Vac
265 Vac
Amps
15
20
30
15
20
30
Heater Size
2.5 kW
3.5 kW
5.0 kW
2.5 kW
3.5 kW
5.0 kW
Plug Layout
G
G
G
G
W
G
W
G
W
NEMA Plug
6-15P
6-20P
6-30P
7-15P
7-20P
7-30P
Cord #
PWR00286
PWR00288
PWR00290
PWR00287
PWR00289
PWR00291
Power Cord Protection
N
No
otte
e:: Power cord does not ship with the unit.
The power cord for 230/208V units provide protection from fire. The unit power automatically
disconnects when unsafe conditions are detected. Power to the unit can be restored by pressing
the reset button on plug head. Upon completion of unit installation for 230/208V models, an
operational check should be performed using the TEST/RESET buttons on the plug head.
N
No
otte
e:: Models with 265V do not incorporate this feature because they require use of an electrical
sub-base accessory. Connection to a wall socket is not permitted for 265V units. All 265V
units must be hard wired using the hard wire kit or make use of the plug-in receptacle in
the standard sub-base.