background image

18-GE20D1-1E-EN

9

Outline Drawings

Table 3. 14.5” Width Cabinet

Summary of Contents for P0V0 Series

Page 1: ... working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to the equipment November 2021 1 18 8 G GE E2 20 0D D1 1 1 1E E E EN N Modular Blowers No Heat P0V0A000M30SCA P0V0B000M40SCA P0V0C000M50SCA P0V0D000M50SCA The P0V0 series modular blower is designed for installation in a closet utility room alcove basement crawlspace or attic Th...

Page 2: ...ti io on n t te es st ti in ng g s se er rv vi ic ci in ng g a an nd d t tr ro ou ub bl le es sh ho oo ot ti in ng g o of f t th hi is s p pr ro od du uc ct t C CA AU UT TI IO ON N I IM MP PR RO OP PE ER R V VO OL LT TA AG GE E C CO ON NN NE EC CT TI IO ON N F Fa ai il lu ur re e t to o f fo ol ll lo ow w t th hi is s C Ca au ut ti io on n c co ou ul ld d r re es su ul lt t i in n p pr ro op pe er...

Page 3: ...o o t to o w ww ww w P P6 65 5W Wa ar rn ni in ng gs s c ca a g go ov v I Im mp po or rt ta an nt t Installation of this unit shall be made in accordance with the National Electric Code NFPA No 90A and 90B and any other local codes or utilities requirements N No ot te e The modular blowers have been evaluated in accordance with Intertek ETL UL1995 2011 Ed 4 SUITABLE FOR MOBILE HOME USE N No ot te ...

Page 4: ...3 Panel Removal 13 Horizontal Installation in an Attic or Crawlspace 13 Duct Connections 14 Return Air Filters 23 Electrical Connections 25 Field Wiring 25 Integrated Modular Blower Control Menu 27 Integrated Modular Blower Control IMBC Display Codes 30 Fault Code Recovery 31 Sequence of Operation 32 Checkout Procedures 34 Table of Contents ...

Page 5: ... Cabinet modular blowers BAYLIFTC Dual Return Kit C size extension C Cabinet modular blowers BAYLIFTD Dual Return Kit D size extension D Cabinet modular blowers BAYFLTR206 Filter Access Door Kit Downflow only All modular blowers in Downflow orientation BAYSF1165AA a 1 SlimFit Box with MERV 4 Filter All modular blowers BAYSF1255BA 1 SlimFit Filter and Insulated Frame All modular blowers when used i...

Page 6: ...6 18 GE20D1 1E EN Location and Clearances Minimum clearance to combustible materials MODULARBLOWER O 21 O ...

Page 7: ...dditional air flows Be sure to check the air flow and the temperature drop across the evaporator coil to ensure sufficient air flow 5 W Wi ir ri in ng g Consult all schematic and pictorial wiring diagrams of this unit and the outdoor equipment to determine compatibility of wiring connections and to determine specific requirements All field wiring to the modular blower should be installed in accord...

Page 8: ...cedures p 34 9 M Ma ai in nt te en na an nc ce e The system air filter s should be inspected cleaned or replaced at least monthly Make certain that the access panels are replaced and secured properly before placing the unit back in operation This product is designed for dependable service however periodic maintenance should be scheduled and conducted by trained professional service personnel This ...

Page 9: ...18 GE20D1 1E EN 9 Outline Drawings Table 3 14 5 Width Cabinet ...

Page 10: ...10 18 GE20D1 1E EN Table 4 17 5 Width Cabinet O Ou ut tl li in ne e D Dr ra aw wi in ng gs s ...

Page 11: ...18 GE20D1 1E EN 11 Table 5 21 Width Cabinet O Ou ut tl li in ne e D Dr ra aw wi in ng gs s ...

Page 12: ...12 18 GE20D1 1E EN Table 6 24 5 Width Cabinet O Ou ut tl li in ne e D Dr ra aw wi in ng gs s ...

Page 13: ...ic should be on a service platform large enough to allow for proper clearances on all sides and service access to the front of the modular blower See Location and Clearances p 6 Line contact is only permissible between lines formed by intersections of the top and two sides of the modular blower casing and building joists studs or framing The modular blower may be placed horizontally in a crawl spa...

Page 14: ...longer guide holes located on the modular blower flange 4 Seal per local codes and requirements Modular Blower in Horizontal Left with Coil 1 Bend modular blower flanges up 2 Support the modular blower and coil independently 3 Screw through the coil cabinet into the modular blower flange Guide holes are located on the coil Note There are no longer guide holes located on the modular blower flange 4...

Page 15: ...modular blower 4 Seal per local codes and requirements Note Flat or dedicated horizontal coils may require flanges to be bent upward Downflow Modular Blower with Coil 1 Bend modular blower flanges down 2 Set the modular blower on top of the coil so that it is flush with the back of the modular blower 3 Seal per local codes and requirements G Ge en ne er ra al l I In ns st ta al ll la at ti io on n...

Page 16: ...0D1 1E EN Horizontal Right and Downflow Modular Blower no Coil 1 Bend modular blower flanges up 2 Attach ducting 3 Seal per local codes and requirements G Ge en ne er ra al l I In ns st ta al ll la at ti io on n ...

Page 17: ...ed separately An external overflow drain pan must be installed in all applications over a finished ceiling to prevent property damage Upflow Modular Blower with Bottom Return in Closet with Remote Filter 1 Remove the bottom plate 2 Set the modular blower on the base inside closet 3 Install remote filter 4 Seal per local codes and requirements Upflow Modular Blower with Bottom Return in Closet with...

Page 18: ...ducted air from a remote location 3 Install filter at a remote location 4 Seal per local codes and requirements Upflow Modular Blower with Bottom Return Mounted on a Ducted Pedestal with Filter Box 1 Remove the bottom plate 2 Set the modular blower on the filter box The ducted pedestal will use ducted air from a remote location 3 Seal per local codes and requirements FILTER G Ge en ne er ra al l I...

Page 19: ...l BAYLIFT kit to lift modular blower Follow kit instructions Note The modular blower bottom pedestal must be a minimum of 6 in height 3 Match the filter cabinet flush to the back and bottom sides of the modular blower cabinet and secure in place with screws 4 Mark the two areas to be cut out for the return air 5 Cut out the two sections of the cabinet and BAYLIFT kit to be removed 6 Attach ducting...

Page 20: ...er with Two Side Returns Important One of the sides must have a transition to allow the thermostat wiring to exit the cabinet Important If a transition is not a viable option a hole will need to be drilled in the side of the cabinet for the thermostat wiring to exit Important Make sure not to cut the cabinet in the No Cut area Important Remove Blower Assembly and Panel Loop before cutting cabinet ...

Page 21: ...he top of the modular blower 3 Install remote filter 4 Seal per local codes and requirements Downflow Modular Blower with Top Return and Plenum 1 Remove the top plate 2 Attach the plenum ducting to the top of the modular blower 3 Install remote filter 4 Seal per local codes and requirements G Ge en ne er ra al l I In ns st ta al ll la at ti io on n ...

Page 22: ...nflow Modular Blower with Top Return and Plenum with Filter Box 1 Remove the top plate 2 Attach the filter box to the top of the modular blower 3 Attach ducting 4 Seal per local codes and requirements FILTER G Ge en ne er ra al l I In ns st ta al ll la at ti io on n ...

Page 23: ...uld provide for installation of return air filters Important Remove Blower Assembly and Panel Loop before cutting cabinet to avoid cutting wires 1 Determine the appropriate position to set the modular blower in order to connect to existing supply and return ductwork 2 For upflow side return installations remove the insulation around the opening in the blower compartment 3 The side panels of the up...

Page 24: ...the modular blower If only the front of the modular blower is accessible it is recommended that both supply and return air plenums are removable 3 When replacing an modular blower old duct work should be cleaned out Thin cloths should be placed over the registers and the modular blower fan should be run for 10 minutes Don t forget to remove the cloths before you start the modular blower 4 The hori...

Page 25: ...rol IMBC and connect wiring 2 The factory Y1 O jumper must remain in place for proper LED read out in cooling mode 3 Y1 and Y2 wiring from the thermostat must connect to the IMBC for proper airflow and LED readout 4 Single compressor and two compressor airflow is auto matically set with the IMBC Menu optionsin ODU section 2 1 2 stage 1 compressor 1st stage airflow 80 2 2 2 stage 2 compressors 1st ...

Page 26: ... COOLING HP D R B Outdoor Unit NOTES 1 Cut the BK jumper at the indoor unit After cutting the jumper power must be off or cycled on off on for the IMBC to work properly 2 Requires an 850 control with software version 3 0 or 1050 Not a valid combination with 950 control CPC CFM Ton cooling Must be set to 400 Control Board LED s will read CoF continous fan during cooling and heat pump operation 24 V...

Page 27: ... 5T P0V0C 5T 5T 3 5T 4T 4 5T P0V0D 5T 5T 3 5T 4T 4 5T Designated Maximum 1st Stage Heat Pump Airflow Se ng ODU 2 1 1st stage airflow is 80 of the total airflow ODU 2 2 1st stage airflow is 50 of the total airflow Total airflow CPH x Tonnage 400 x 3 1200 Model Number Hea ng CFM P0V0A000M30SCA 1000 Total 1240 P0V0B000M40SCA 1200 Total 1440 P0V0C000M50SCA 1400 Total 1680 P0V0D000M50SCA 1400 Total 168...

Page 28: ...layed is solely dependent on the input of 24VAC that is applied to the low voltage terminal strip 2 The status will alternate between the system mode and the airflow request every 2 seconds 3 If an error occurs an E will alternately flash with the system mode and airflow request 4 Some units will show demand airflow while others will show calculated airflow Calculated airflow will gradually ramp u...

Page 29: ...sequence will repeat two more mes unless the Run Test Mode is exited see above Important The Run Test Mode does not bring the outdoor unit on It is designed to allow the technician to observe each mode to ensure the IMBC circula ng blower are performing as intended The run test for the blower will take approximately 70 seconds to begin Note During run test mode depressing the option key will allow...

Page 30: ...lay Seconds 0dt Outdoor Tonnage 0du Outdoor Unit COF Blower Constant Fan Airflow Multiplier Percentage CpC Cooling CFM Ton CpH Heat Pump Heating CFM Ton Xod Not Applicable sd Not Applicable gXC Not Applicable run Run Test Mode Error Codes Alarm Error Code Alarm Explanation e0 Loss of the IRQ or other internal failures Internal IMBC error e6 Voltage reversed polarity e6 2 Bad grounding e 2 Open fus...

Page 31: ...irms the faults have been cleared Resetting Factory Defaults 1 Display must be in Idle Mode 2 Push the Menu and Option buttons at the same time for 15 seconds then release 3 The 7 segment will flash FD 3 times This confirms the unit has been reset to the factory defaults Motor Communications Personality Module Low Voltage Terminal Strip 12 Pin Connector LINE Connections EAC HUM Dry Contacts Neutra...

Page 32: ... unit via thermostat wiring 4 The indoor airflow ramps to 2nd stage cooling airflow The seven segment LED for example will read CL2 Cooling Stage 2 ARF Airflow 160 1600 calculated cfm value shown x 10 5 When the temperature is lowered enough to satisfy the thermostat setting contacts R Y1 Y2 G will open 6 The OD unit shuts off and the indoor blower shuts off unless a blower off delay has been enab...

Page 33: ...ed enough to satisfy the thermostat setting contacts R Y1 Y2 G will open 6 The OD unit shuts off and the indoor blower shuts off The seven segment LED will read IDL Idle no thermostat demand S Se eq qu ue en nc ce e o of f O Op pe er ra at ti io on n ...

Page 34: ...ltage and running current are within limits Ductwork is sealed and insulated Supply registers and return grilles are open unobstructed and air filter is installed Indoor blower and outdoor fan are operating smoothly and without obstruction Indoor blower motor set on correct speed setting to deliver required CFM Blower and fan set screws are tight Cover panels are in place and properly tightened Sy...

Page 35: ...18 GE20D1 1E EN 35 N No ot te es s ...

Page 36: ...plications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice We are committed to using environmentally conscious print practices 18 GE20D1 1E EN 22 Nov 2021 Supersedes 18 GE20D1 1D EN March 2021 2021 ...

Reviews: