background image

3.8.4 MOTOR SPEED

• Low voltage control connections are made to low voltage pigtails
extending  from  top  of  air  handler  (see  Figure  1).  Connections  for
control wiring are made with wire nuts. Control wiring knockouts (7/8˝)
are  also  provided  on  the  right  and  left  side  of  the  unit  for  side
connection.

• See wiring diagrams attached to indoor and outdoor sections to be
connected.

•  Make sure, after installation, separation of control wiring and power
wiring has been maintained.

3.8.3 GROUNDING

The unit must be permanently grounded. Failure to do so can 
result in electrical shock causing personal injury or death.    

•  Grounding may be accomplished when installed in accordance with
electrical codes by bonding the metal conduit to the unit cabinet or by
attaching ground wire(s) to ground lug(s) provided in the unit wiring
compartment.

• Ground lug(s) are located close to wire entrance on left side of unit
(upflow).  Lug(s)  may  be  moved  to  marked  locations  near  wire
entrance on right side of unit (upflow) if alternate location is more
convenient.

• Use of multiple supply circuits require grounding of each circuit to
lug(s) provided in unit.

• If required, install a branch circuit disconnect of adequate size,
located within sight of, and readily accessible to the unit.

IMPORTANT

:  After  the  Electric  Heater  is  installed,  units  are

equipped with one 60 amp. circuit breaker. These breaker(s) protect
the  internal  wiring  in  the  event  of  a  short  circuit  and  serve  as  a
disconnect. Circuit breakers installed within the unit do not provide
over-current  protection  of  the  supply  wiring  and  therefore  may  be
sized larger than the branch circuit protection.

Supply  circuit  power  wiring  must  be  75°C  minimum  copper

conductors  only.  See  Electrical  Data  in  this  section  for  ampacity,
wire size and circuit protector requirements. Supply circuit protective
devices may be either fuses or “HACR” type circuit breakers.
• Power wiring may be connected to either the right or left side

.

Two 7/8” dia. concentric knockouts are provided for connection of
power wiring to unit.
• Power  wiring  is  connected  to  the  power  terminal  block  in  unit
electric cabinet.

3.8.2 CONTROL WIRING

IMPORTANT: Class 2 low voltage control wiring should not be run in 
conduit with main power wiring and must be separated from power 
wiring, unless class 1 wire of proper voltage rating is used. 

Select  a  thermostat  that  is  commonly  used  with  HP  or  AC  single 
stage heating/cooling with electric heat. The thermostat will energize 
the fan on a demand for heating or cooling.

Install the thermostat on an inside wall, away from drafts, lights or 
other heat sources in a location that has sufficient air circulation from 
other  rooms  being  controlled  by  the  thermostat.  The  thermostat 
should be mounted 4 to 5 feet above the floor.

• Low  voltage  control  wiring  should  be  18 Awg.  color-coded.  For
lengths longer than 100 ft., 16 Awg. wire should be used.

ECM Motor Speed Taps(Model number 24

30

36)

Tap

Delay---off

Time (s)

24

30

36

Tap 1

30

---

---

---

Tap 2

90

---

Default

---

Tap 3

30

---

---

---

Tap 4

90

Default

---

Default

Tap 5

30

---

---

---

Field wiring must comply with the National Electric Code (C.E.C. in 
Canada) and any applicable local ordinance.  

Disconnect all power to unit before installing or servicing.  More 
than one disconnect switch may be required to de-energize the 
equipment. Hazardous voltage can cause severe personal injury 
or death.    

3.8.1 POWER WIRING

It is important that proper electrical power is available for connection 
to  the  unit  model  being  installed.  See  the  unit  nameplate,  wiring 
diagram and electrical data in the installation instructions.

WARNING

WARNING

3.5 Refrigerant Piping

Refrigerant  pipe  connections  are  located  on  the  top  of  the  unit. 
Refrigerant piping external to the unit shall be sized in accordance 
with  the  instructions  of  the  outdoor  equipment.  When  units  are 
recessed mounted in the wall, make certain that piping connections 
are pressure tested prior to the wall being closed. While brazing, be 
sure to protect the cabinet and grommets from heat damage.

3.6 Metering Device

All  units  are  shipped  and  installed  with  an  internally-checked, 
non-bleed  TXV  designed  for  air  conditioning  or  heat  pump 
operation.  Pressures  equalize  after  shut  down.  Some  outdoor 
models  may  require  a  start  assist  kit.  See  outdoor  unit  for  more 
information.

3.7 Blower

3.8 Wiring

3.10 Thermostat

An air filter must be installed before air enters the evaporator coil in 
order  to  protect  the  coil,  blower,  and  other  internal  parts  from 
excessive dirt and dust . A filter must be installed. Consult the filter 
manufacturer for proper sizing and maximum velocity requirements.

3.9 Air Filter

This  unit  is  supplied  with  a  multi-speed  motor  with  a  direct  drive 
blower wheel which can obtain various air flows. The unit is shipped 
with factory set cooling and heating speed taps. Airflow performance 
tables are available for additional speed taps. Disconnect all power 
to the unit before making any adjustments to the motor speed taps. 
Be sure to check the air flow and the temperature drop across the 
evaporator coil to ensure sufficient air flow.

Filter Sizes

  

24 

16Χ20[406Χ508] 

MODEL 

FILTER SIZE IN [mm]  

30/36 

20Χ20[508Χ508] 

6

Summary of Contents for OXBOX JMM5A0A24M21SAA

Page 1: ... versatile units are applicable to air conditioning and heat pump applications Field installed electric resistance heaters are available All aluminum coil Blower and coil slide out easily for maintenance Factory sealed cabinet certified to achieve 2 or less air leakage rate at 1 0 inch water column Front or bottom return air Painted finish on galvanized steel Sturdy polycarbonate drain pans Air ha...

Page 2: ... state electrical code on requirements for grounding Failure to follow this warning could result in property damage serious personal injury or death HAZARDOUS VAPORS Do not install an air handler with a non ducted return in the same closet alcove or utility room as a fossil fuel device Hazardous vapors can be distributed throughout the conditioned space and equipment damage can result Section 2 Sa...

Page 3: ...ins adhesives cleaning compounds and cement creates a corrosive condition which may cause rapid deterioration of the cabinet and internal components CAUTION SAFETY HAZARD Sharp Edge Hazard Be careful of sharp edges on equipment or any cuts made on sheet metal while installing or servicing Personal injury may result WARNING Make sure the blower motor support is tight 3 motor mount bolts then check ...

Page 4: ...t the air handler above the wall mounting bracket and attach the unit to the installed bracket Reference Figure 3 1 4 Install the additional bottom plate for extra support for this type mounting see figure 3 1 Note The additional plate is shipped in the bottom of the shipping carton 3 2 1 WALL MOUNT Fig 3 2 FRAME MOUNT 3 2 2 FRAME MOUNT PROVIDED WALL MOUNT BRACKET WALLMOUNT BRACKET WOOD SCREWS SUP...

Page 5: ...idential Winter and Summer Air Conditioning and Equipment Selection Latest editions are available from ACCA Air Conditioning Contractors of America 1513 16th Street N W Washington D C 20036 If duct system incorporates flexible air duct be sure pressure drop information straight length plus all turns shown in ACCA Manual D is accounted for in system Supply plenum is attached to the 3 4 duct flanges...

Page 6: ...gize the fan on a demand for heating or cooling Install the thermostat on an inside wall away from drafts lights or other heat sources in a location that has sufficient air circulation from other rooms being controlled by the thermostat The thermostat should be mounted 4 to 5 feet above the floor Low voltage control wiring should be 18 Awg color coded For lengths longer than 100 ft 16 Awg wire sho...

Page 7: ...pension if used is secure and there are no tools or loose debris in around or on top of the unit 2 Properly insulate suction lines and fittings 3 Properly secure and isolate all refrigerant lines 4 Verify that all electrical connections are tight 5 Check all duct outlets they must be open and unrestricted 6 Check drain lines and be sure all joints are tight 7 Be sure the return air filter is insta...

Page 8: ...COMPONENT ARRANGEMENT FM NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND NE CONVIENT PAS AUXINSTALLATIONS DE PLUS DE 150V ALA TERRE CAUTION ATTENTION JMM5A0A24M21SAA JMM5A0B36M31SAA Fig 4 1 8 ...

Page 9: ...COMPONENT ARRANGEMENT FM NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND NE CONVIENT PAS AUXINSTALLATIONS DE PLUS DE 150V ALA TERRE CAUTION ATTENTION Fig 4 2 JMM5A0B30M21SAA 9 ...

Page 10: ...8 1200 0 06 0 08 0 08 1100 0 06 0 08 0 08 1000 0 06 0 08 0 08 900 0 04 0 06 0 06 800 0 04 0 06 0 06 700 0 04 0 06 0 06 900 0 04 0 06 0 06 800 0 04 0 06 0 06 700 0 04 0 06 600 0 04 0 06 0 06 0 06 HEATER RACKS HEATER MODEL NO OF RACKS BAYHTRJ505BRKA 1 BAYHTRJ508BRKA 2 BAYHTRJ510BRKA 3 Accessory Heater Usage SIZES USED WITH kW INTERNAL CIRCUIT PROTECTION 1 5 Circuit Breaker 2 7 5 Circuit Breaker 3 24...

Page 11: ...on dry coil at 230V with no electric heat no filter For 24 30 and 36 sizes airflow at 208V is approximately the same as 230V because the mult tap ECM motor is a constant torque motor The torque doesn t drop off at the speeds in which the motor operates 2 Airflow is equivalent for front or bottom return configurations 3 SCFM is nearly the same with cooling performance airflow the gap is in the 1 to...

Page 12: ...ction 3 4 female pipe thread NPT Primary drain conncetion 3 4 female pipe thread NPT Front return shown Units may also be installed as bottom return See the applications section for more detail NOTE Hand tighten only Section 7 Dimensional Data DIMENSIONAL DATA Model Dimensions inch mm H W D UNIT WEIGHT SHIPPING WEIGHT LBS kg JMM5A0A24M21SAA W1 D1 JMM5A0B30M21SAA JMM5A0B36M31SAA 97 120 44 54 4 97 1...

Page 13: ...ION DATA Fig 2 BACK DIMENSIONS A B C JMM5A0A24M21SAA 24 9 10 150 10 1 8 61 119 1 20 717 JMM5A0B30M21SAA 24 9 10 150 10 1 8 61 132 795 JMM5A0B36M31SAA 24 9 10 150 10 1 8 61 132 795 Dimension inch mm Model number 13 ...

Page 14: ......

Page 15: ......

Page 16: ...nformation contact your local dealer distributor Since the manufacturer has a policy of continuous product and product data improvement it reserves the right to change the design and specification without notice 800 Beaty Street www oxboxhvac com 2019TwentyThreeC LLC ...

Reviews: