SSP-SVX001B-EN
23
Charging Levels
IIm
mp
po
orrtta
an
ntt:: For the correct line diameter, for line
lengths greater than 25 feet, see the
Odyssey Application Guide (SS-APG008*-
EN) available through e-Library or your
local sales office.
Table 6. Estimated charge levels at ARI rated line lengths (25 feet)
Matched Set
Refrigerant Charge
Per Circuit
Circuit 1
Circuit 2
Liquid Line Diameter
Vapor Line Diameter
TWA0604DA w/ TWE0764DA
16.6
N/A
0.5 (1/2”)
1.375 (1 3/8”)
TWA0604DD w/ TWE0724DB
11.1
12.4
0.5 (1/2”)
0.875 (7/8")
TWA0724*A w/ TWE0904*A
20.4
N/A
0.5 (1/2”)
1.375 (1 3/8”)
TWA0724*D w/ TWE0724*B
11.0
11.0
0.5 (1/2”)
0.875 (7/8")
TWA0764DA w/ TWE0764DA
19.0
N/A
0.625 (5/8”)
1.375 (1 3/8”)
TWA0764DD w/ TWE0764DB
11.7
11.7
0.5 (1/2”)
1.125 (1 1/8”)
TWA0904*A w/ TWE0904*A
19.0
N/A
0.625 (5/8”)
1.375 (1 3/8”)
TWA0904*D w/ TWE0904*B
11.8
11.8
0.5 (1/2”)
1.125 (1 1/8”)
TWA1014DA w/ TWE1014DA
34.7
N/A
0.5 (1/2”)
1.375 (1 3/8”)
TWA1014DD w/ TWE1014DB
14.0
14.0
0.5 (1/2”)
1.125 (1 1/8”)
TWA1204*A w/ TWE1204*A
34.7
N/A
0.5 (1/2”)
1.375 (1 3/8”)
TWA1204*D w/ TWE1204*B
14.0
14.0
0.5 (1/2”)
1.125 (1 1/8”)
TWA1564DD w/ TWE1564DB
19.2
19.9
0.5 (1/2”)
1.125 (1 1/8”)
TWA1804*D w/ TWE1804*B
27.2
24.5
0.5 (1/2”)
1.125 (1 1/8”)
TWA2014DD w/ TWE2014DB
18.6
18.4
0.625 (5/8”)
1.375 (1 3/8”)
TWA2404*D w/ TWE2404*B
23.5
23.5
0.625 (5/8”)
1.375 (1 3/8”)
Notes:
1
.
For line lengths other than 25', please refer to the Application Guide (SS-APG008*-EN) for charge levels, oil addition and line sizes.
2
.
For additional support with line lengths or refrigerant charge, refer to the Application Guide or contact Product Support.
3
.
TWA0604DA and TWA0724*A need a reducer for vapor line. (1.375 to 1.125) (1 3/8” to 1 1/8”).
4
.
TWA0604DD and TWA0724*D need a reducer for vapor line (1.125 to 0.875) (1 1/8" to 7/8").