8-50 Coasting Select
Option:
Function:
Select control of the coasting function via the terminals (digital input)
and/or via the bus.
[0]
Digital input
Activates Start command via a digital input.
[1]
Bus
Activates Start command via the serial communication port or serial
communication option.
[2]
Logic AND
Activates Start command via the serial communication bus/serial com-
munication port, AND additionally via one of the digital inputs.
[3] *
Logic OR
Activates Start command via the serial communication bus/serial com-
munication port OR via one of the digital inputs.
NOTE: This parameter is active only when par.8-01
is set to [0]
Digital and control word
.
8-51 Quick Stop Select
Select control of the quick stop function via the terminals (digital input) and/or via the bus.
Option:
Function:
[0]
Digital Input
[1]
Bus
[2]
Logic AND
[3] *
Logic OR
Note
This parameter is active only when par.8-01
is set to [0]
Digital and control word
.
8-52 DC Brake Select
Option:
Function:
Select control of the DC brake via the terminals (digital input) and/or via
the serial communication bus.
[0]
Digital input
Activates Start command via a digital input.
[1]
Bus
Activates Start command via the serial communication port or serial
communication option.
[2]
Logic AND
Activates Start command via the serial communication bus/serial com-
munication port, AND additionally via one of the digital inputs.
[3] *
Logic OR
Activates Start command via the serial communication bus/serial com-
munication port OR via one of the digital inputs.
NOTE: This parameter is active only when par.8-01
is set to [0]
Digital and control word
.
8-53 Start Select
Option:
Function:
Select control of the adjustable frequency drive start function via the ter-
minals (digital input) and/or via the serial communication bus.
[0]
Digital input
Activates Start command via a digital input.
[1]
Bus
Activates Start command via the serial communication port or serial
communication option.