112
RT-SVX36G-EN
Unit Start Up
Note:
Important:
Do not operate the compressors for extended periods of time without the condenser
fans; high head pressure will develop.
GAS HEAT
(Full Capacity)
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
STAGE 1
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
STAGE 2
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
(High Fire Adjustment)
FULL MODULATING
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
(Low Fire Adjustment)
LIMITED MODULATING
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
(High Fire Adjustment)
LIMITED MODULATING
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
(Low Fire Adjustment)
ELECTRIC HEAT
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
Stage 1
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
Stage 2
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
Stage 3
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
HYDRONIC HEAT
Closed
Closed
0%
Default
OFF
OFF
OFF
OFF
PRE-HEATER
Closed
Closed
0%
Default
OFF
OFF
OFF
OFF
FRESH AIR DAMPERS
100%
Closed
0%
Default
OFF
OFF
OFF
OFF
Open
EXHAUST DAMPERS
100%
100%
0%
Default
OFF
OFF
OFF
OFF
Open
REHEAT
Cooling Valve
Closed
Closed
0%
Default
100-0
OFF
OFF
OFF
Reheat Valve
Closed
Closed
0%
Default
0-100
OFF
OFF
OFF
Pumpout Solenoid
Closed
Closed
0%
Default
ON
OFF
OFF
OFF
EVAP COND
Sump Pump
Closed
Closed
0%
Default
OFF
ON
OFF
ON
Sump Heater
Closed
Closed
100%
Default
OFF
OFF
ON
OFF
Table 36. Service test guide for component operation — Part II of II (continued)
Component
Being Tested
Component Configuration
Occ
Unocc
Relay
Reheat
Sump
Pump
Sump
Heater
Dolphin
Econo
Damper
Exhaust
Damper
VFD
Output
Table 37. Service test guide component operation—evaporative condenser
Component Being Tested
Requirements (ON)
Requirements (OFF)
Compressors
Sump minimum level switch must be closed for a minimum of five minutes No Requirements
Sump Pump
Sump minimum level switch must be closed for a minimum of five minutes No Requirements
Condenser Fans
No Requirements
No Requirements
Fill Valve Relay
No Requirements
No Requirements
Drain Valve Actuator
No Requirements
No Requirements
Sump Heater
No Requirements
No Requirements
Notes:
1.
Sump freeze protection is active during AUTO but is inactive in service test modes (head pressure control set to MANUAL).
2.
Water treatment drain request will be ignored in service test.