44
RT-SVX072A-EN
Table 18.
LP gas – 2-stage and modulating gas heat settings (continued)
Propane
850 MBH Mod
0
1150
1150
10
3920
2.5
5
0.516
1000 MBH 2-stg
n/a
2600
2600
10
4430
2
5
0.516
1000 MBH Mod
0
1150
1150
10
4430
2
5
0.516
Note:
P0, P1, and P2 are fan speed settings in the Seimens controller. The default speeds have been preset at the factory and normally do not
need field adjustment.
(a)
binary input for 2-stage
(b)
800MBH is Horizontal Discharge. MBH is listed on gas heat rating plate.
Figure 20.
2-stage and Mod gas train for 235 to 500
MBh
High gas switch
Ratio regulator
Manual shut-off valve
To combustion
air sensor
Main gas
solenoid
valves
Manual shut-off
vavle with 3/4” field
connection
Low gas
switch
Figure 21.
2-stage and Mod gas train for 850 MBh
High gas switch
Ratio regulator
Manual shut-off valve
To combustion
air sensor
Main gas
solenoid
valves
Manual shut-off
vavle with 1” field
connection
Low gas
switch
Figure 22.
2-stage and Mod gas train for 1000 MBh
High gas switch
Ratio regulator
Manual shut-off valve
To combustion
air sensor
Main gas
solenoid
valves
Manual shut-off
vavle with 1” field
connection
Low gas
switch