38
OAU-SVX01K-EN
System Configuration and Pre-Start
The following procedure must be completed prior to
performing the startup procedure in
. This
section describes procedures to navigate the various
displays on the Unit Display and configure the Outdoor Air
Unit Main Unit Display system setpoints and operating
parameters.
Important:
This section is intended to provide
guidelines for navigation through the
remote operator display screens. For
additional control system information, refer
to Integration Guide: Tracer
®
UC600
Programmable Controller for Packaged
Outdoor Air Unit (BAS-SVP18*-EN).
Table 8.
Chart of analog and binary input/output
#
BACnet Point Name
Write
Default
Range
Units
Description
AI-01
Space Temperature
Local
40–95
°F
Hardwired input from field installed space
temperature sensor, wired to OAUTS-1 & -2
(SPTC).
AI-02
Space Humidity Local
0–100
%
Hardwired input from field installed space humidity
sensor,
wired to OAUTS-5 & -6 (SPHC).
AI-03
Supply Fan Piezo
Pressure Local
0–25
in.H
2
O
Hardwired input from factory installed piezo
differential
pressure sensor (SPZ).
AI-04
Outdoor Coil Leaving
Temperature
Circuit 1 Local
-50–270
°F
Hardwired input from factory installed temperature
sensor
located on the outdoor coil (CCTC1).
AI-05
Outdoor Coil Leaving
Temperature
Circuit 2 Local
-50–270
°F
Hardwired input from factory installed temperature
sensor
located on the outdoor coil (CCTC2).
AI-06
Return Air Temperature
Local
-40–135
°F
Hardwired input from factory installed temperature
sensor
located in the return air path (RTC).
AI-07
Outdoor Air Damper
Position Status
Local
0-100
%
Hardwired input that provides feedback status
from the
actuator located on the outdoor air damper (OAD).
AI-08
Space CO
2
Concentration Local
-
ppm
Hardwired input from field provided CO2.
AI-09
Exhaust Fan Piezo
Pressure Local
0–25
in.H2O
Hardwired input from factory installed piezo
differential
pressure sensor (EPZ).