2 Technical data
2.1 Heat pump technical data
Dimensions and weight
Measurements without
cover and extra feet
RE 210
RE 330
RE 420
Height (mm)
2056
2056
2056
Width (mm)
1550
2676
2676
Depth (mm)
900
900
900
Weight (kg)
1700
2400
2600
Connections
For information on pipe connections, see connection diagrams delivered with the heat
pump.
RE 210
RE 330
RE 420
Electrical connections
3 L / N / PE / 400 VAC 50
Hz, ask for other alternatives
Compressor start-up current (A)
332
498
496
Compressor maximum operating
current (A)
166
332
330
Fuse size (A)
3 x 200
3 X 400
3 x 400
Protection degree, control cabinet
IP44
Refrigerant circuit
The refrigerant charge values presented here are baseline values. The
actual refrigerant charge depends on the heat pump exchanger option,
other accessories, and the local conditions.
Always check the exact refrigerant charge from the heat pump’s type
plate.
RE 210
RE 330
RE 420
Refrigerant
R410A
R410A
R410A
Refrigerant charge (kg)
25
2 x 25
2 x 25
Water or brine circuits: Minimum water/brine outlet temperature from the evaporator: –
15 °C. Maximum water/brine inlet temperature to the evaporator: +50 °C.
EXERE01 2150EN
11 (61)