supplied with the condenser (typically located in the
condenser electric box).
As an option, control wiring may be installed between the
A/C system and the condenser for the system controller to
enable condenser operation only when the compressor is
running. You must remove the jumper from the remote
condenser terminal board (see the condenser wiring
diagram). Wire 24 Vac control conductors from the
terminal board within the A/C unit to the remote
condenser terminal board. If control wires aren’t installed
(and the jumper remains in place), the condenser is always
enabled and will turn on and off based on the condenser’s
pressure control settings. Refer to the electrical drawing
for the correct number of field wires needed and for the
appropriate wire terminations required specifically for
your system.
Figure 25.
Field Wiring Glycol Systems - Single Point Power Connection Shown for Drycooler & Pump Package
(TO BE INSTALLED IN ACCORDANCE
(GLYCOL UNITS ONLY)
ELECTRIC
24VAC
PUMP PACKAGE
BOX
SEE NOTE 1
WITH NFPA 70, N.E.C.)
INTERCONNECTING FIELD WIRING
MAIN POWER SUPPLY
208-575V/3PH/60Hz
(GLYCOL UNITS ONLY)
DRYCOOLER
2. NUMBER OF CONDUCTORS MAY VARY DEPENDING ON OPTIONS PROVIDED.
NOTES:
NFPA 70, N.E.C.)
208-575V/3PH/60Hz
MAIN POWER SUPPLY
IN ACCORDANCE WITH
INTERCONNECTING FIELD
WIRING (TO BE INSTALLED
L3
L1
L2
Model TR-CFS-105-D2G Shown for Reference
L3
L1
L2
1. PHANTOM WIRES ( ) NOT APPLICABLE FOR SINGLE PHASE POWER SUPPLIES.
Figure 26.
Field Wiring Air Cooled Systems
2. NUMBER OF CONDUCTORS VARY DEPENDING ON OPTIONS PROVIDED.
NOTES:
AIR COOLED CONDENSER
WITH NFPA 70, N.E.C.)
INTERCONNECTING FIELD WIRING
(TO BE INSTALLED IN ACCORDANCE
24VAC (OPTIONAL)
208-575V/3PH/60Hz
MAIN POWER SUPPLY
L2
L3
L1
SEE NOTE 1 & 2
NFPA 70, N.E.C.)
208-575V/3PH/60Hz
MAIN POWER SUPPLY
IN ACCORDANCE WITH
INTERCONNECTING FIELD
WIRING (TO BE INSTALLED
L3
L1
L2
Model TR-CFS-105-D2A Shown for Reference
1. PHANTOM WIRES ( ) NOT APPLICABLE FOR SINGLE PHASE POWER SUPPLIES.