10
SSC-SVN001H-EN
EVAPORATING UNIT
INCLINATION
SUCTION
LIQUID
CONDENSING
UNIT
EVAPORATING UNIT
INCLINATION
LIQUID
CONDENSING
UNIT
SUCTION
M
AX. 10 m
Fig. IV-02 - Assembly Condensing Unit over Evaporating Unit.
Fig. IV-01 - Assembly Evaporating Unit over Condensing Unit.
Refrigerant Piping
Units should be interconnected with
copper pipes.
Connection gauges of evaporating
units and remote condensing units
TRAE or TRCE, and suction and
liquid piping gauges recommended for
interconnecting both are indicated on
Table 04.
The corresponding lengths already in-
clude losses generated by valves, cur-
ves, elbows, reductions, etc.
Maximum distance (recommended)*
distance between units:
46 m
.
difference in levels between units:
18 m
.
(*) – Calculated distance, considering equivalent
length of connection elements.
For distances higher than the recom-
mended value, please contact
Trane
.
Evaporating Unit above the
Condensing Unit
- Build a 20 cm inverted siphon in the
suction line at the evaporating unit
outlet, after the regular oil accumulation
siphon.
- Horizontal sections in the suction line
should be inclined by 45 mm at every 10
m of line towards condensing unit.
Condensing Unit above the
Evaporating Unit
- Build a 10 cm siphon at rising and a
siphon at every 7.5 m of vertical line.
- Horizontal sections in the suction line
should be inclined by 45 mm at every 10
m of line towards condensing unit.
Refrigerating Tubing -
Interconnection
TRAE/TRCE
7,5 m
- 20 cm
Summary of Contents for CXPA 050
Page 27: ...SSC SVN001H EN 27 Fig 35 Dimensions Condensing Units TRAE 150 1 circuit TRAE Dimensional Data...
Page 28: ...28 SSC SVN001H EN Fig 36 Dimensions Condensing Units TRAE 150 2 circuits TRAE Dimensional Data...
Page 29: ...SSC SVN001H EN 29 Fig 37 Dimensions Condensing Units TRAE 200 1 Circuit TRAE Dimensional Data...
Page 30: ...30 SSC SVN001H EN TRAE Dimensional Data Fig 38 Dimensions Condensing Units TRAE 200 2 Circuits...
Page 31: ...SSC SVN001H EN 31 TRAE Dimensional Data Fig 39 Dimensions Condensing Units TRAE 250 1 Circuit...
Page 32: ...32 SSC SVN001H EN TRAE Dimensional Data Fig 40 Dimensions Condensing Units TRAE 250 2 Circuits...