52
Troubleshooting
Fault Alarm Table for Controller (H Type)
No.
Input Port
Fault Description
Code of
Single unit
controller
Code of
Centralized
Controller
Fault Handling
1
TH1
No.1 analog sensor fault (water inlet
temperature)
20
20
Switch off
2
TH2
No.2 analog sensor fault (water outlet
temperature)
21
21
Switch off
3
TH3
No.3 analog sensor fault (suction
temperature A)
22
22
Switch off
4
TH4
No.4 analog sensor fault (fin temperature A)
23
23
Switch off
5
TH5
No.5 analog sensor fault (coil heating outlet
temperature A-1)
24
24
Switch off
6
TH6
No.6 analog sensor fault (coil heating outlet
temperature A-2)
25
25
Switch off
7
TH7
No.7 analog sensor fault (ambient
temperature)
26
26
Switch off
8
TH8
No.8 analog sensor fault (suction
temperature B)
27
27
Switch off
2
9
TH9
No.9 analog sensor fault (fin temperature B)
28
28
Switch off
2
10
TH10
No.10 analog sensor fault (coil heating outlet
temperature B-1)
29
29
Switch off
2
11
TH11
No.11 analog sensor fault (coil heating outlet
temperature B-2)
2A
2A
Switch off
2
12
TH12
No.12 analog sensor fault (total water outlet
temperature)
2B
2B
Switch off
4
13
CN13
No.13 analog sensor fault (suction pressure
A)
2C
2C
Switch off
14
CN14
No.14 analog sensor fault (suction pressure
B)
2D
2D
Switch off
2
15
IND3
High-voltage switch trip of compressor 2
H2
65
Switch off
2
16
IND4
High-voltage switch trip of compressor 1
H1
64
Switch off
17
IND5
Water flow switch alarm
FL
6D
Switch off
18
IND6
Overload of water pump
OP
6A
Switch off
19
IND8
Overload of compressor 1
C1
68
Switch off
20
IND9
Overload of compressor 2
C2
69
Switch off
2
21
CN13
Low-voltage trip of compressor 1
L1
66
Switch off
22
CN14
Low-voltage trip of compressor 2
L2
67
Switch off
2
23
TH2 and
TH1-TH2
Refrigeration antifreezing
E3
8D
Switch off all compressors.
The water pump
continuously operates
1
24
TH3
、
TH8
Abnormal suction temperature
E4
91
Switch off all compressors.
The water pump
continuously operates.
1 2