NOTICE
Transformer Damage!
Connecting additional load to a factory supplied control
transformer may result in overloading the transformer.
Do not rewire the unit's individual components.Do not
connect any additional loads to the system control
transformers.
Installation
26
AH-SVX008C-EN
Remote Condenser
For systems equipped with a remote condenser, the
installer must provide main power wiring to the remote
condenser control box. A separate equipment ground lug
is provided within the control box for termination of the
earth ground wire. Refer to the electrical drawing supplied
with your system and the wiring diagram supplied with
the condenser (typically located in the condenser electric
box).
As an option, control wiring may be installed between the
A/C system and the condenser for the system controller to
enable condenser operation only when the compressor is
running.
You must remove the jumper from the remote condenser
terminal board (see the condenser wiring diagram). Wire
24 VAC control conductors from the terminal board within
the A/C unit to the remote condenser terminal board. If
control wires aren't installed (and the jumper remains in
place), the condenser is always enabled and will turn on
and off based on the condenser's pressure control
settings.
Remote Condensing Unit
Systems equipped with a remote condensing unit require
field wiring between the evaporator system and the
remote condensing unit. The number of conductors
required varies based upon the options provided. Refer to
the electrical drawing(s) supplied with your unit to
determine the exact number of field wires and proper wire
terminations required specifically for your system.
Glycol-cooled systems equipped with a pump package
require field wiring between the A/C unit and pump pack-
age. The installer must wire two control conductors from
the terminal board within the A/C unit to the pump package
electric box. Refer to the electrical drawing(s) supplied
with your unit to determine the exact number of field wires
and proper wire terminations required specifically for your
system.
Water/Glycol Systems
Glycol-cooled systems equipped with a pump package
require field wiring between the A/C unit and pump pack-
age. The installer must wire two control conductors from
the terminal board within the A/C unit to the pump pack-
age electric box. Refer to the electrical drawing(s) supplied
with your unit to determine the exact number of field wires
and proper wire terminations required specifically for your
system.
Remote Shut Down
The unit provides an interface that allows for remote shut
down. A normally-closed switch rated at 5 amperes at
24VAC is required for this purpose. Two conductors from
the normally closed switch must be connected to the
control terminal board located within the unit electric box.
Refer to the supplied electrical drawing for the appropriate
wire terminations.
Note:
All wiring must be provided in accordance with
National Electrical Code and local code
requirements for Class 2 circuits.
Optional Equipment
Condensate Pump
Systems supplied with a field installed condensate pump
require power and control field wiring. The control wires
from the terminal board in the electric box should be run
through the overflow switch in the condensate pump
housing.
After installing the condensate pump, connect two power
conductors from the condensate pump main power
terminals to the air conditioning unit and a ground wire to
the unit ground stud located within the unit electric box.
Two control conductors must be wired to the control
terminal board located within the unit electric box. The
condensate pump is provided with pigtail leads for splice-
type wire connections with twist-on connectors (wire
caps). Refer to the supplied electrical drawing for proper
wire terminations.
Humidistat/Dehumidistat
The humidistat/dehumidistat are mounted in the same
manner but are wired differently. The humidistat/
dehumidistat both require two conductors for connection
to the air conditioning system. The controls have pigtail
leads for splice type wire connections with twist on
connectors (wire caps). Refer to the supplied electrical
schematic for proper wire terminations.
Remote Water Detector
There are two types of water detector available with TR-
OHS units: Spot type and strip/cable type.
Spot Type
A remote spot type water detector requires three
conductors to be wired to the control terminal board in the
unit electric box. The wire insulation must be rated at 600V.
The water detector has pig-tail leads for splice type wire
connections with twist on connectors (wire caps). Refer to
the supplied electrical drawing for proper wire
terminations.
Strip/Cable Type
A remote strip/cable type water detector is provided with
a two conductor cable harness with a quick connect fitting
on the end. The harness mates to the fitting on the water
detector and connects it to the control board inside the