background image

26

CXRC-SVX01J-EN

Field Piping (Air-Cooled Discharge/Liquid
Lines)

1. Ensure all required field installed piping pressure

tests are completed in accordance with national
and/or local codes.

2. Close liquid line angle valve.

3. Connect R-410A refrigerant cylinder to high side

charging port (at Remote Condenser or field
supplied discharge line access port). Add
refrigerant to reach pressure of 12 to 15 psig.

4. Disconnect refrigerant cylinder. Connect dry

nitrogen cylinder to high side charging port and
increase pressure to 150 psig. Do not exceed high
side (discharge) unit nameplate design pressure.
Do not subject low side (suction) components to
high side pressure.

5. Check all piping joints, valves, etc. for leaks.

Recommend using electronic detector capable of
measuring 0.1 oz/year leak rate.

6. If a leak is located, use proper procedures to

remove the refrigerant/nitrogen mixture, break
connections and make repairs. Retest for leaks.

Ensure all service valves are open.

System Repair

1. If system is water cooled with service valves, or air

cooled, high and low side may be tested
independently by closing liquid line angle valve and
water cooled unit discharge line ball valve.
Otherwise leave all valves open and DO NOT
exceed low side design pressure.

2. Connect R-410A refrigerant cylinder to charging

port, add refrigerant to reach pressure of 12 to 15
psig.

3. Disconnect refrigerant cylinder. Connect dry

nitrogen cylinder to high side charging port and
increase pressure to 150 psig. DO NOT exceed unit
nameplate design pressures. If testing complete
system, low side design pressure is maximum.

4. Check piping and/or components as appropriate for

leaks.

5. Recommend using electronic detector capable of

measuring 0.1 oz/year leak rate.

6. If a leak is located, use proper procedures to

remove the refrigerant/nitrogen mixture, break
connections and make repairs. Retest for leaks.

Ensure all service valves are open.

System Evacuation Procedures

1. Each refrigeration circuit must be evacuated before

the unit can be charged and started.

2. Use a rotary type vacuum pump capable of pulling

a vacuum of 100 microns or less.

3. Verify that the unit disconnect switch and the

system control circuit switches are off.

4. Oil in the vacuum pump should be changed each

time the pump is used with high quality vacuum
pump oil. Before using any oil, check the oil
container for discoloration which usually indicates
moisture in the oil and/or water droplets. Moisture
in the oil adds to what must be removed from the
system, increasing pump down time.

5.

When connecting the vacuum pump to a

refrigeration system, it is important to manifold the
vacuum pump to both the high and low side of the
system (liquid line access valve and suction line
access valve). Follow the pump manufacturer’s
directions for the proper methods of using the
vacuum pump.

6. The lines used to connect the pump to the system

should be copper and of the largest diameter that
can practically be used. Using larger line sizes with
minimum flow resistance can significantly reduce
evacuation time.

IIm

mp

po

orrtta

an

ntt:: Rubber or synthetic hoses are not

recommended for system evacuation
because they have moisture absorbing
characteristics which result in excessive
rates of evaporation, causing pressure
rise during the standing vacuum test.
This makes it impossible to determine if
the system has a leak, excessive
residual moisture, or a continual or high
rate of pressure increase due to the
hoses.

7. An electronic micron vacuum gauge should be

installed in the common line ahead of the vacuum
pump shutoff valve, as shown in . Close Valves B
and C, and open Valve A.

8. Start the vacuum pump, after several minutes, the

gauge reading will indicate the maximum vacuum
the pump is capable of pulling. Rotary pumps
should produce vacuums of 100 microns or less.

N

NO

OT

TIIC

CE

E

M

Mo

otto

orr W

Wiin

nd

diin

ng

g D

Da

am

ma

ag

ge

e!!

F

Fa

aiillu

urre

e tto

o ffo

ollllo

ow

w iin

nssttrru

uccttiio

on

nss b

be

ello

ow

w cco

ou

ulld

d rre

essu

ulltt iin

n

cco

om

mp

prre

esssso

orr m

mo

otto

orr w

wiin

nd

diin

ng

g d

da

am

ma

ag

ge

e..

D

Do

o n

no

ott u

usse

e a

a m

me

eg

go

oh

hm

m m

me

ette

err o

orr a

ap

pp

plly

y v

vo

olltta

ag

ge

e

g

grre

ea

atte

err tth

ha

an

n 5

50

0 V

VD

DC

C tto

o a

a cco

om

mp

prre

esssso

orr m

mo

otto

orr

w

wiin

nd

diin

ng

g w

wh

hiille

e iitt iiss u

un

nd

de

err a

a d

de

ee

ep

p v

va

accu

uu

um

m..

9. Open Valves B and C. Evacuate the system to a

pressure of 300 microns or less. As the vacuum is
being pulled on the system, there could be a time
when it would appear that no further vacuum is
being obtained, yet, the pressure is high. It is
recommended that during the evacuation process,
the vacuum be broken to facilitate the evacuation
process.

10. To break the vacuum:

M

Ma

aiin

ntte

en

na

an

ncce

e

Summary of Contents for CCRC 20

Page 1: ...e and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literatu...

Page 2: ...a ar r p pr ro op pe er r P PP PE E f fo or r t th he e j jo ob b b be ei in ng g u un nd de er rt ta ak ke en n c co ou ul ld d r re es su ul lt t i in n d de ea at th h o or r s se er ri io ou us s...

Page 3: ...d de ea at th h o or r s se er ri io ou us s i in nj ju ur ry y D Di is sc co on nn ne ec ct t a al ll l e el le ec ct tr ri ic c p po ow we er r i in nc cl lu ud di in ng g r re em mo ot te e d di i...

Page 4: ...endations 19 Power Supply Wiring 19 System Interconnection Wiring 19 Unit Wiring Diagrams 19 Unit Voltage 19 Voltage Supply 19 Voltage Imbalance 20 Operating Principles 21 Control Sequences of Operati...

Page 5: ...minimized It is important that periodic maintenance be performed to help assure trouble free operation A maintenance schedule is provided at the end of this manual Should equipment failure occur cont...

Page 6: ...it 8 Unit Voltage 4 460 Volt 60 Hz 3 ph 5 575 Volt 60 Hz 3 ph 6 200 Volt 60 Hz 3 ph Digit 9 Control Option 0 No Low Ambient IPak A No Low Ambient T Stat B Low Ambient IPak C Low Ambient T Stat Note T...

Page 7: ...ouvered condenser grills are for coil protection and available as an option to order Direct drive vertical discharge fans are provided with built in current and overload protection Head pressure contr...

Page 8: ...e floor or foundation is level solid and sufficient to support the unit and accessory weights Level or repair the floor before positioning the unit if necessary N No ot te e For a detailed discussion...

Page 9: ...amper per Circuit Refrigerant Line Connections Frontal View AC AB AA Table 1 CCRC CIRC Unit Weights Unit Size Shipping Weight lbs kg Operating Weight lbs kg CCRC CIRC 20 2030 920 1906 865 CCRC CIRC 29...

Page 10: ...R 3 4 CONDUIT SUPPLY VOLTAGE WIRE ENTRY HOLE SIZED FOR 1 CONDUIT 66 7 8 1699mm 18 1 4 1 2 114mm 1 2 470mm Hot Gas Conn Refrig ckt 17 1 2 445mm 14 3 8 365mm Liq Line Conn Refrig ckt 1 24 3 4 629mm Liq...

Page 11: ...ances are doubled See for specific pit installation clearance instructions If multiple units are placed side by side the minimum distance between units must be twice the normal recommended side cleara...

Page 12: ...e 9 Recommended Clearances for Typical Pit Installation for All Unit Sizes Figure 10 Typical Side by Side Installation Recommended Clearances for All Unit Sizes D Di im me en ns si io on ns s a an nd...

Page 13: ...ty y l li if ft t p po oi in nt t T To o a av vo oi id d d dr ro op pp pi in ng g o of f u un ni it t r re ep po os si it ti io on n l li if ft ti in ng g p po oi in nt t i if f u un ni it t i is s n...

Page 14: ...shown in Figure 13 p 15 through Figure 15 p 16 Spring Isolators Unit mounting locations are shown in Figure 13 p 15 through Figure 15 p 16 Operating weights and weight loading at each mounting locati...

Page 15: ...lb 20 2030 463 463 463 517 1906 29 2084 490 463 490 517 1960 32 2138 490 490 490 554 2014 35 3018 463 463 463 463 463 518 2833 40 3072 463 463 490 463 463 518 2887 50 3995 490 490 490 490 490 350 490...

Page 16: ...near the condenser to facilitate refrigerant storage in the condenser during service procedures When optional discharge line ball valves are present in the indoor section installation of field suppli...

Page 17: ...of the indoor unit left side for SCRF SIRF right side for SCRG SIRG CCRC CIRC connections are located in the unit front at the top Remove cap with a tube cutter to minimize risk of getting chips insi...

Page 18: ...SXRG CXRC Size Circuit 1 Circuit 2 Liquid Discharge Liquid Discharge 20 20 5 8 in 7 8 in 5 8 in 7 8 in 25 29 5 8 in 1 1 8 in 5 8 in 7 8 in 32 32 5 8 in 1 1 8 in 5 8 in 1 1 8 in a Use 1 1 8 for vertica...

Page 19: ...ided in this manual Power Supply Wiring Run appropriately sized power wiring and field supplied conduit through the line voltage access opening provided on the front of the unit Refer to Figure 1 p 7...

Page 20: ...measured 227 V 221 230 227 3 2 2 N No ot te e L1 221 volts is the maximum deviation of the 3 voltages from the average of the 3 voltages Therefore the imbalance percentage is 100 226 221 226 2 2 The...

Page 21: ...ow If saturated condenser temperature continues to rise with damper modulated fully open K1 relay drops out and the IntelliPak controller pulls in K2 relay subsequently pulling in contactor Circuit 1B...

Page 22: ...operation on all units is interlocked with compressor start and stop They use customer provided compressor contactor auxiliary contacts and liquid line pressure if the thermostat controlled unit is u...

Page 23: ...he fan orifices and should be mounted securely on the motor shafts Check condenser coils Coil fins should be clean and straight There should be no restrictions to proper airflow through the condenser...

Page 24: ...n n t th he e c cr ra an nk kc ca as se e h he ea at te er rs s o on n f fo or r a a m mi in ni im mu um m o of f 2 24 4 h ho ou ur rs s b be ef fo or re e s st ta ar rt ti in ng g c co om mp pr re es...

Page 25: ...i io ou us s i in nj ju ur ry y o or r e eq qu ui ip pm me en nt t o or r p pr ro op pe er rt ty y o on nl ly y d da am ma ag ge e N Ne ev ve er r u us se e a an n o op pe en n f fl la am me e t to o...

Page 26: ...l check the oil container for discoloration which usually indicates moisture in the oil and or water droplets Moisture in the oil adds to what must be removed from the system increasing pump down time...

Page 27: ...ls off to a constant value this indicates that there is excessive moisture present If the pressure steadily continues to rise a leak is indicated Figure 18 p 27 illustrates three possible results of t...

Page 28: ...frigerant charging can begin Charge refrigerant into the system by weight Approximate operating refrigerant charge capacities for 20 through 60 ton CCRC CIRC condensing units are given in and Calculat...

Page 29: ...with fin comb as required 5 Mix the detergent with water according to the manufacturers instructions N No ot te e Observe all recommendations of the cleanser manufacturer The coil cleanser manufactur...

Page 30: ...en ns se ed d e el le ec ct tr ri ic ci ia an n o or r o ot th he er r i in nd di iv vi id du ua al l w wh ho o h ha as s b be ee en n p pr ro op pe er rl ly y t tr ra ai in ne ed d i in n h ha an nd...

Page 31: ...Power and Controls 20 60T IntelliPak 2313 1632 Schematic Power and Controls 20 32T Thermostat Controls 2313 1635 Connections Control Panel w Thermostat Controls 2313 1636 Connections Control Panel w v...

Page 32: ...or more information please visit trane com or tranetechnologies com Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications wi...

Reviews: