BAS-SVX45F-GB
45
Configuring Tracer UC600 with Tracer TU
Upgrading Firmware
Firmware upgrades require the use of Tracer TU (version 8.0 or higher).
To upgrade Tracer UC600 firmware:
1.
Connect Tracer TU to Tracer UC600 using a USB connection (direct connect).
It is not recommended that the firmware be updated using single-link access or connecting
through the Tracer SC.
2. Click the file transfer utility icon (
) located on the upper left portion of Tracer TU, which
opens the File Transfer wizard.
3. Select the Tracer UC600 from the Selected devices box. Click Next.
The Choose files to Transfer to each Device or Device Group dialog box appears.
4. Click Browse, which opens the Selected files dialog box.
5. Browse to the Tracer TU/Firmware/UC600 directory which is often found in My Documents.
6. Select the firmware file that has the .mod file extension. Version 2.0 firmware and higher uses
the .mod extension.
Important:
Selecting a lower version of firmware will clear all configuration in the controller.
7.
Click Open to open the file (the firmware file).
8. Click Start.
Do not close Tracer TU or navigate away from the File Transfer page until the File Transfer
Summary dialog box appears.
9. When the File Transfer Summary dialog box appears, click Finish.
Figure 22. Browsing for UC600 firmware