background image

Model: 

BAYECON103AA/AB/AC

BAYECON104AA/AB/AC

BAYRLAY006A

Down Discharge Economizer and Rain Hood

Used with:

*WCZ, YCZ, DCZ - 024, 036

*WCZ, YCZ, DCZ - 048, 060

(Required with *WCZ & *DCZ models)

General

The economizer is a multi-damper design. It is installed 

in the return air stream and is connected to the unit low 

voltage supply through wire leads. The economizer is fully 

accessible through the Coil access panel.

18-HE85D1-1D-EN

Installer’s Guide

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

WARNING:

 

HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING

Important: 

After the Economizer installation you must 

install an air filter rack ordered separately. Use:

BAYFLTR101B for *WCZ, YCZ, DCZ - 024, 036

BAYFLTR201B for *WCZ, YCZ, DCZ - 048, 060. 
When the economizer is installed in *WCZ & *DCZ 

models, relay accessory kit BAYRLAY006A is required. 

Refer to Figure 13 on page 9 to make your relay wiring 

connections in the Control Box.

IMPORTANT:

 In order to maintain a specific minimum 

fresh air cfm during each mode of operation, you must 

order and install a BAYOSAC001 (outside air control) 

accessory.

Inspect Contents

Y

ou must report damage and make claims to the trans

-

portation company immediately. Report missing parts to 

your supplier immediately and replace with authorized 

parts only.

Identify Economizer Kit Contents

Refer to Figures 1 & 2 on page 3 to identify the kit 

contents.

ELECTRIC SHOCK HAZARD

Open and lock out all unit disconnects prior to ac-

cessory installation or unit maintenance, to prevent 

injury or death from electrical shock or contact 

with moving parts.

SAFETY HAZARD

Do not remove end covers from economizer actua-

tor; the spring-return assembly may release and 

cause personal injury.

Install Economizer Kit

1.

 

Remove Power

     D

isconnect and verify that power is off.

2. Remove Access Panels

     Remove these four (4) access panels 

     (see Figure 3, page 3):

     • Control/Heat access panel

     • Blower access panel

     • Coil access panel

     • D

ownflow Return Air panel

3.  

BAYRLAY006A Installation (Required for 

*WCZ & *DCZ units only, for *YCZ units  

skip to step 4

)

1.  Remove wire harness that came attached to the 

BAYECON Logic Module being installed.

  IMPORTANT:  

Do NOT remove the resistors from 

the Logic Module.  Also, Do NOT remove the YL & 

YL/BK wires connected to 

S

O and + on the Logic 

Module

2.

  

 Locate the ICMC Board in the upper left hand 

corner of the unit control box and the DFC board in 

the upper center of the unit control box. See Figure 

8, page 6.

3.

  

 

Using the existing holes in the back of the unit 

control box, mount the relay bracket assembly using 

the 2 screws supplied with the BAYRLAY006A Kit. 

See Figure 8, page 6.

4.

  

 Route the BAYRLAY006A wire harness attached to 

the relays to the logic module as shown in Figure 11 

on page 7.

5.

  

 Connect the BAYRLAY006A to the economizer 

Logic Module and make the field connections as 

shown in Figure 13 on page 9. 

IMPORTANT — 

This Document is 

customer property

 

and is to remain with this unit.  Please return to service      

information pack upon completion of work.

Summary of Contents for BAYRLAY006A

Page 1: ...TRIC SHOCK HAZARD Open and lock out all unit disconnects prior to ac cessory installation or unit maintenance to prevent injury or death from electrical shock or contact with moving parts SAFETY HAZARD Do not remove end covers from economizer actua tor the spring return assembly may release and cause personal injury Install Economizer Kit 1 Remove Power Disconnect and verify that power is off 2 Re...

Page 2: ... left Blower partition using two sheetmetal screws See Figure 10 page 7 The male tabs on the Yellow and Yellow Black wires will connect to the Economizer wiring harness in a later step 2 Enthalpy Sensor If used install this option at this time per instructions provided in the sensor kit 7 Route Main Wiring 1 From the Economizer assembly pass the wire harness through the coil grommet See Figure 11 ...

Page 3: ...B AC Economizer Kit Components Top Sealing Flange Horizontal Return Air Panel Down Flow Return Air Panel Coils Access Panel Blower Access Panel Control Box Access Panel Figure 3 Remove Panels Mixed Air Sensor Logic Module Economizer Assembly Return Air Damper Flange Screw and two 2 Mixed Air Sensor Sheetmetal Screws not shown Mist Eliminator Filter Rainhood Assembly Figure 2 BAYECON104AA AB AC Eco...

Page 4: ...amper Economizer 2 Insert Assembly Screw Figure 5 Swing Down and Set Economizer Return Damper Figure 4 Insert Economizer in Shipping Position Dry bulb outside air temperature sensor Economizer actuator and Logic Module Insert economizer in folded shipping position ...

Page 5: ... and hood Economizer and Return Air Damper Figure 7 Mounting Rain Hood 3 Tighten the two 2 top screws and the two 2 side screws 2 Drive six 6 self tapping screws into the keyhole openings on each side of hood 1 Loosen the two 2 screws to allow hood to slide under the unit Economizer Rain Hood Unit s top sealing slides under HVAC unit s top sealing HVAC unit s top HVAC unit Hood Detail ...

Page 6: ...and Filter Economizer Rain Hood A Mist Eliminator Relief Damper Return Duct Roofcurb order separately Outside air dampers Return air dampers Economizer Unit Application Models A BAYECON103AA AB AC 20 1 8 BAYECON104AA AB AC 24 3 8 WCZ 024 036 DCZ 024 036 YCZ 024 036 WCZ 048 060 DCZ 048 060 YCZ 048 060 ...

Page 7: ...1 From economizer assembly pass wire harness through coil Grommet See View A 2 Continue routing behind compressor compartment and into Blower Compartment Coil Grommet 3 Pull the two 2 Mixed Air Sensor wires with female quick connects from the harness and route down near the Mixed Air Sensor Connect to sensor pigtail wire leads 4 Continue Routing the Remaining Harness Through the Grommet and into t...

Page 8: ...ure 12 YCZ Economizer Connection Diagram A A A A IMPORTANT Retain this wiring diagram please return this document to service information pack upon completion of work Wiring Diagram for Economizer Using a Honeywell W7459 Logic ...

Page 9: ... A IMPORTANT Retain this wiring diagram please return this document to service information pack upon completion of work Wiring Diagram for Economizer Using a Honeywell W7459 Logic Figure 13 WCZ DCZ Economizer Connection Diagram ...

Page 10: ...A A A A ACCESSORY MODELS BAYECON103AA AB AC BAYECON104AA AB AC BAYECON203AA AB AC BAYECON204AA AB AC IMPORTANT Retain this wiring diagram please return this document to service information pack upon completion of work Wiring Diagram for Economizer Using a Honeywell W7212 Logic ...

Page 11: ...A A A ACCESSORY MODELS BAYECON103AA AB AC BAYECON104AA AB AC BAYECON203AA AB AC BAYECON204AA AB AC IMPORTANT Retain this wiring diagram please return this document to service information pack upon completion of work Wiring Diagram for Economizer Using a Honeywell W7212 Logic ...

Page 12: ...and Dual Fuel models When outdoor air conditions are suf ficient for Free Cooling and the thermostat sends a signal for 2nd stage cooling G Y1 Y2 O for Heat Pumps 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 3 0 3 2 3 4 3 6 3 8 4 0 4 2 4 4 4 6 9 0 1 0 0 8 0 7 0 6 0 5 0 4 0 3 0 20 10 E N T H A L P Y B T U P E R P O U N D D R Y A I R 85 29 90 32 95 35 100 38 105 41 110 43 35 2 35 2 40 4 40 4 105 41 110 43 45...

Page 13: ... Connect 1 2K ohm 4074EJM Checkout Resistor across terminals So and 2 Turn enthalpy setpoint potentiometer to A LED turns on indicating low enthalpy Motor drives toward open 3 Turn enthalpy setpoint potentiometer to D LED turns off indicating high enthalpy Motor drives toward closed 4 Disconnect the 1 2K ohm checkout resistor D 1 To verify sensor operation reconnect the lead of the outdoorenthalpy...

Page 14: ...9 6 32 2 204 2 714 91 4 33 2 111 2 676 93 2 34 2 023 2 639 95 0 35 1 938 2 600 96 8 36 1 858 2 561 98 6 37 1 781 2 526 100 4 38 1 708 2 484 Temp vs OHM for MAS Mixed Air Sensor Table 3 Temp vs OHM Values for MAS Mixed Air Sensor 1 1 2 2 M9097 ENTHALPY CHANGEOVER SETPOINT LED LIGHTS WHEN OUTDOOR AIR IS SUITABLE FOR FREE COOLING INSERT DC MILLIAMMETER BETWEEN SO AND S FOR CHECKOUT AND TROUBLESHOOTIN...

Page 15: ...e Proper Response 1 CHECKOUT PREPARATION FOR ECONOMIZING ONLY Disconnect power at TR and TR1 All LED are off Exhaust Fan contacts are open Disconnect devices at P and P1 Jumper P to P1 defaults to on board MIN POS potentiometer Place 5 6K ohm resistor across T and T1 Blue sleeve provides input to economizer that the MAT is between 50 55F Jumper TR to 1 call for cooling from the thermostat W7212 on...

Page 16: ...at 45 degrees open Adjust DCV MAX towards CW Motor will move to position set by DCV MAX pot Adjust DCV MAX to fully CCW Motor will drive closed Reconnect jumper to N terminal Adjust DCV MAX and MIN POS pots Motor will drive to the most open position of the pots Adjust DCV MAX and MIN POS pots to fully CCW Remove power from N terminal adjust MIN POS towards CW Motor should not move Adjust DCV MAX t...

Page 17: ...pplications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice We are committed to using environmentally conscious print practices 2022 18 HE85D1 1D EN 09 Sep 2022 Supersedes 18 HE85D1 1C EN May 2022 ...