Performance and Electrical Data

Table 1. Air Flow Performance

TEM6A0D48H41SB, TEM6A0D60H51SB COOLING AIRFLOW PERFORMANCE, WET COIL, NO FILTER, NO HEATER

OUTDOOR
UNIT SIZE

(TONS)

SPEED

SETTING

AIRFLOW

SETTING

DIP SWITCH SETTING

AIRFLOW

POWER

EXTERNAL STATIC PRESSURE

SW1

SW2

SW3

SW4

0.1

0.3

0.5

0.7

0.9

3

LOW

323 CFM/

ton

ON

ON

OFF

ON

CFM

Watts

979

87

978
126

959
170

922
217

867
269

NORMAL

367 CFM/

ton

ON

ON

OFF

OFF

CFM

Watts

1111

124

1113

168

1101

215

1075

265

1036

317

HIGH

415 CFM/

ton

ON

ON

ON

OFF

CFM

Watts

1252

165

1259

214

1254

264

1239

314

1212

364

3.5

LOW

315 CFM/

ton

OFF

ON

OFF

ON

CFM

Watts

1111

124

1113

168

1101

215

1075

265

1036

317

NORMAL

358 CFM/

ton

OFF

ON

OFF

OFF

CFM

Watts

1259

167

1266

217

1261

267

1246

317

1220

368

HIGH

404 CFM/

ton

OFF

ON

ON

OFF

CFM

Watts

1419

223

1428

279

1425

334

1411

389

1386

444

4

LOW

309 CFM/

ton

ON

OFF

OFF

ON

CFM

Watts

1241

161

1248

210

1243

259

1227

309

1201

359

NORMAL

351 CFM/

ton

ON

OFF

OFF

OFF

CFM

Watts

1407

218

1416

273

1413

328

1399

383

1373

437

HIGH

396 CFM/

ton

ON

OFF

ON

OFF

CFM

Watts

1583

296

1593

359

1594

422

1586

485

1570

547

5

LOW

295 CFM/

ton

OFF

OFF

OFF

ON

CFM

Watts

1478

249

1487

307

1486

365

1474

423

1452

481

NORMAL

(a)

335 CFM/

ton

OFF

OFF

OFF

OFF

CFM

Watts

1671

344

1681

412

1684

479

1678

545

1635

565

HIGH

379 CFM/

ton

OFF

OFF

ON

OFF

CFM

Watts

1880

476

1892

556

1900

635

1902

714

1760

650

(a)

Factory Default Setting

Table 2. Air Flow Performance

TEM6A0D48H41SB, TEM6A0D60H51SB HEATING AIRFLOW PERFORMANCE, NO FILTER, NO HEATER

OUTDOOR
UNIT SIZE

(TONS)

SPEED

SETTING

AIRFLOW

SETTING

DIP SWITCH SETTING

AIRFLOW

POWER

EXTERNAL STATIC PRESSURE

SW1

SW2

SW3

SW4

0.1

0.3

0.5

0.7

0.9

3

LOW

360 CFM/

ton

ON

ON

OFF

ON

CFM

Watts

1087

111

1091

153

1081

199

1055

249

1015

301

NORMAL

400 CFM/

ton

ON

ON

OFF

OFF

CFM

Watts

1205

139

1213

186

1211

234

1198

283

1173

333

HIGH

440 CFM/

ton

ON

ON

ON

OFF

CFM

Watts

1322

175

1333

227

1332

279

1321

332

1297

384

3.5

LOW

347 CFM/

ton

OFF

ON

OFF

ON

CFM

Watts

1219

143

1228

191

1226

240

1213

289

1189

339

NORMAL

386 CFM/

ton

OFF

ON

OFF

OFF

CFM

Watts

1351

184

1363

237

1363

290

1351

344

1328

397

HIGH

424 CFM/

ton

OFF

ON

ON

OFF

CFM

Watts

1482

232

1495

291

1497

349

1489

408

1471

466

4

LOW

351 CFM/

ton

ON

OFF

OFF

ON

CFM

Watts

1405

201

1417

256

1418

311

1408

367

1385

422

NORMAL

390 CFM/

ton

ON

OFF

OFF

OFF

CFM

Watts

1555

262

1568

323

1572

385

1567

447

1553

509

HIGH

429 CFM/

ton

ON

OFF

ON

OFF

CFM

Watts

1703

334

1717

403

1723

472

1722

540

1665

560

5

LOW

327 CFM/

ton

OFF

OFF

OFF

ON

CFM

Watts

1625

294

1639

359

1644

424

1641

489

1630

554

NORMAL

(a)

363 CFM/

ton

OFF

OFF

OFF

OFF

CFM

Watts

1797

384

1812

459

1820

533

1822

606

1750

615

HIGH

400 CFM/

ton

OFF

OFF

ON

OFF

CFM

Watts

1970

495

1986

581

1999

667

2010

740

1910

680

(a)

Factory Default Setting

Page 18 of 20  10/16/2019

MOHS, PLANS EXAMINER

REV #1                                                                                  .

2405 E AINSWORTH AVE                                  B19-2396

INSTALL HVAC SYSTEM/PORT OF PASCO    10/1/2019

Summary of Contents for BAYHTR1504BRKC

Page 1: ...UCT CONTAINS FIBERGLASS WOOL INSULA TION FIBERGLASS DUST AND CERAMIC FIBERS ARE BE LIEVED BY THE STATE OF CALIFORNIA TO CAUSE CAN CER THROUGH INHALATION GLASSWOOL FIBERS MAY ALSO CAUSE RESPIRATORY SKIN OR EYE IRRITATION GENERAL This accessory electric heater is designed to provide power directly to the unit from the accessory heater s power supply eliminating the need for additional circuits The p...

Page 2: ...he four tabs located at the center points of the edges of knock out plate 4 Discard knock out plate 8 Locate the two locking tabs on the top panel of the air handler shown as Left and Center in the drawing 9 Slide the breaker plate assembly into the appropriate tab Rotate the breaker assembly into place as shown in image 4 IMPORTANT The left side breaker mount location must be used for TEM8A0B24 3...

Page 3: ...ship with a Heater Breaker Seal Kit See Seal Kit Installer s Guide for install instructions Note Follow the instructions in the Breaker Seal Kit 18 GJ85D1 1 latest rev The Breaker Seal Kit will ship with the TEM8A0B air handlers 25 KW heaters and single power entry kits for TEM A4AH4 air handlers Center knockouts Use for all other 4 20 kW heaters installations with all TEM A4AH4 air handler except...

Page 4: ... L H TEM4A0C37S31SB A4AH4P37A1C030A L L L L L L H H L L TEM4A0C42S41SB A4AH4E42A1C030A L L L L L L L M L L TEM4A0C48S41SB A4AH4E48A1C030A TEM4A0C60S51SB A4AH4E60A1C030A L L L L L L L L L L L L Cooling HP Airflow Followed by one digit Note On the TEM4A0C42S41SB TEM4A0C48S41SB TEM4A0C60S51SB A4AH4E42A1C030A A4AH4E48A1C030A and A4AH4E60A1C030A models taps 1 3 Low tap 4 Med tap 5 High TEM6 MINIMUM HEA...

Page 5: ...del No BAYHTR1504BRK BAYHTR1504LUG BAYHTR1505BRK BAYHTR1505LUG BAYHTR1508BRK BAYHTR1508LUG BAYHTR1510BRK BAYHTR1510LUG BAYHTR1517BRK BAYHTR1523BRK BAYHTR1525BRK BAYHTR3510LUG BAYHTR3517LUG Electric Heat Stages 1 1 1 1 2 2 2 1 1 Stage 1 Capacity kW 3 84 4 8 7 68 9 6 9 6 9 6 12 0 9 6 14 4 Stage 2 Capacity kW 3 84 4 8 7 68 9 6 14 4 19 2 24 0 9 6 14 4 Page 5 of 20 10 16 2019 MOHS PLANS EXAMINER REV 1 ...

Page 6: ...Page 6 INSTALLER S GUIDE 18 HB22D1 14 Page 6 of 20 10 16 2019 MOHS PLANS EXAMINER REV 1 2405 E AINSWORTH AVE B19 2396 INSTALL HVAC SYSTEM PORT OF PASCO 10 1 2019 ...

Page 7: ...Page 7 INSTALLER S GUIDE 18 HB22D1 14 Page 7 of 20 10 16 2019 MOHS PLANS EXAMINER REV 1 2405 E AINSWORTH AVE B19 2396 INSTALL HVAC SYSTEM PORT OF PASCO 10 1 2019 ...

Page 8: ...9010 Since the manufacturer has a policy of continuous product and product data improvement it reserves the right to change design and specification without notice Page 8 of 20 10 16 2019 MOHS PLANS EXAMINER REV 1 2405 E AINSWORTH AVE B19 2396 INSTALL HVAC SYSTEM PORT OF PASCO 10 1 2019 ...

Page 9: ...r altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to the equipment June 2016 4A6H5060H SUB 1A EN Split System Heat Pump 4A6H5060H1000A N No ot te e Graphics in this document are for representation only Actual model may differ in appearance...

Page 10: ...VEL Model A Weighted Sound Power Level dB A Full Octave Sound Power dB 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz 4A6H5060H 72 77 75 72 70 67 62 59 52 Note Rated in accordance with AHRI Standard 270 2008 For reference only Page 10 of 20 10 16 2019 MOHS PLANS EXAMINER REV 1 2405 E AINSWORTH AVE B19 2396 INSTALL HVAC SYSTEM PORT OF PASCO 10 1 2019 ...

Page 11: ...ed in accordance with Natl Elec Codes Use only HACR circuit breakers or fuses d This value shown for compressor RLA on the unit nameplate and on this specification sheet is used to compute minimum branch circuit ampacity and max fuse size The value shown is the branch circuit selection current e No means no start components Yes means quick start kit components PTC means positive temperature coeffi...

Page 12: ...se C Co on nd de en ns se er r C Co oi il l The outdoor coil provides low airflow resistance and efficient heat transfer The coil is protected on all four sides by louvered panels L Lo ow w A Am mb bi ie en nt t C Co oo ol li in ng g As manufactured this system has a cooling capacity to 55 F The addition of an evaporator defrost control permits operation to 40 F The addition of an evaporator defro...

Page 13: ... and on the tags stickers and labels that are attached to the equipment March 2018 T TE EM M6 6A A0 0D D6 60 0 S SU UB B 1 1E E E EN N Variable Speed Convertible Air Handler 5 Ton TEM6A0D60H51SB N No ot te e The TEM6 series air handler is designed for installation in a closet utility room alcove basement crawlspace or attic These versatile units are applicable to air conditioning and heat pump app...

Page 14: ...D ON THE UNIT RATING NAMEPLATE PRODUCT DIMENSIONS Air Handler Model A B C D E F H Flow Control Gas Line Braze TEM6A0D60H51SB 53 87 26 50 24 50 24 75 7 01 9 66 27 19 TXV 7 8 All dimensions are in inches Page 14 of 20 10 16 2019 MOHS PLANS EXAMINER REV 1 2405 E AINSWORTH AVE B19 2396 INSTALL HVAC SYSTEM PORT OF PASCO 10 1 2019 ...

Page 15: ...z 208 230 1 60 F L Amps 6 8 FILTER Filter Furnished c No REFRIGERANT R 410A Ref Line Connections Brazed Coupling or Conn Size in Gas 7 8 Coupling or Conn Size in Liq 3 8 DIMENSIONS H x W x D Crated In 55 3 8 x 30 1 2 x 25 1 2 Uncrated 53 7 8 x 26 1 2 x 21 1 8 WEIGHT Shipping Lbs Net Lbs 181 168 a These Air Handlers are A H R I certified with various Split System Air Conditioners and Heat Pumps AHR...

Page 16: ...3517LUG 1300 1125 BAYHTR1523BRK 1380 1125 BAYHTR1525BRK 1550 1345 TEM6A0D60H51SB Airflow Performance with Auxiliary Heat Airflow Settings Dip Switch Settings Nominal Airflow See following tables for heater application Pressure Drop for Electrical Heaters Minimum Heating Airflow Matrix on unit nameplates Switch 7 Switch 8 Low ON ON 997 Med Lo OFF ON 1129 Med Hi ON OFF 1350 High OFF OFF 1597 Page 16...

Page 17: ...0 13 BAYHTR1510 2 1500 0 02 0 04 0 06 0 12 BAYHTR1516 3 1400 0 02 0 04 0 06 0 12 BAYHTR1517 3 1300 0 02 0 04 0 05 0 11 BAYHTR3510 3 1200 0 01 0 04 0 05 0 10 BAYHTR3517 3 1100 0 01 0 03 0 05 0 09 BAYHTR3515 3 1000 0 01 0 03 0 04 0 09 BAYHTR1522 4 900 0 01 0 03 0 04 0 08 BAYHTR1523 4 800 0 01 0 03 BAYHTR1525 4 700 0 01 0 02 600 0 01 0 02 Page 17 of 20 10 16 2019 MOHS PLANS EXAMINER REV 1 2405 E AINS...

Page 18: ... 476 1892 556 1900 635 1902 714 1760 650 a Factory Default Setting Table 2 Air Flow Performance TEM6A0D48H41SB TEM6A0D60H51SB HEATING AIRFLOW PERFORMANCE NO FILTER NO HEATER OUTDOOR UNIT SIZE TONS SPEED SETTING AIRFLOW SETTING DIP SWITCH SETTING AIRFLOW POWER EXTERNAL STATIC PRESSURE SW1 SW2 SW3 SW4 0 1 0 3 0 5 0 7 0 9 3 LOW 360 CFM ton ON ON OFF ON CFM Watts 1087 111 1091 153 1081 199 1055 249 10...

Page 19: ... 4 1 6 00 20500 25 0 40 40 4 50 15400 21 6 36 40 BAYHTR1525BRK Circuit 2 6 00 20500 25 0 31 35 4 50 15400 21 6 27 30 BAYHTR1525BRK Circuit 3 6 00 20500 25 0 31 35 4 50 15400 21 6 27 30 BAYHTR1525BRK Circuit 4 6 00 20500 25 0 31 35 4 50 15400 21 6 27 30 BAYHTR3510LUG 1 3 9 60 32800 23 1 36 40 7 20 24600 20 0 33 35 BAYHTR3517LUG 1 3 14 40 49100 34 6 51 60 10 80 36900 30 0 45 45 Motor Amps a MCA and ...

Page 20: ... and efficiency We are a global business committed to a world of sustainable progress and enduring results ingersollrand com Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice We are committed to using environmentally conscious print practices TEM6A0D60 SUB 1E EN 19 Mar 2018 Supersedes TEM6A0D60 ...