A. GENERAL

This accessory electric heater is designed to provide 
power directly to the air handler from the accessory 
heaters power supply eliminating the need for ad-
ditional circuits. The power and control wiring use 
a single polorized plug to connect the heater and the 
air handler. Single source power entry is provided  for 
single phase heaters with  two circuits using acces-
sory BAYSPEK140B. See the Heater Data table on 
page 2 for the number of circuits required. 
 1. Check the air handler heater label to comfirm that 

the selected Heater is approved for use with this 
air handler, in the installed configuration.

 2. Check the components received for damage. Re-

port any defects or shortages to the transportation 
company immediately.

 3. Be sure the power supply agrees with the listing 

shown on heater nameplate.

B. INSTALLATION 

1.  Remove the blower access panel from  the front 

of the air handler.

2.  Disconnect  the  female  polarized  plug  from  the 

wire  bundle  at  left  side  of  air  handler  near  the 
knockouts.  Discard the male polarized plug and 
power wire leads.

3.   

(TWG  &  TGB  models  only)  Remove  the  cover 

from the heater compartment of the air handler 
and discard.

ALL phases of this installation must comply with 

NATIONAL, STATE AND LOCAL CODES

4.    Remove  the  cover  from  the  heater  field  wiring 

and  control  compartment  box. 

For  heaters  up 

to 15 Kw, an adapter plate is provided which 

is used with air handlers that are 21.5” wide 

or wider.  When required, attach the adapter 

plate to the back of the heater on the side op-

posite the knockouts using 2 screws.  

 5.  Remove the appropriate knockouts in the heater 

field wiring compartment. See Figure 1 on page 
3. Remove the appropriate knockouts in the air 
handler for making electrical connections to the 
heater.  The holes in the air handler must align 
with the holes in the heater field wiring compart-
ment.

6.  Insert the heater assembly into the heater cavity 

of the air handler so that the field wiring holes in 
the air handler and the heater will align.  Secure 
the heater compartment to the air handler with 
the four screws removed from  the hardware en-
velope.

I

MPORTANT: Conduit must attach directly to 

the heater control box.

NOTE:  Air handlers approved to use the 1425 heater 

have a plate covering either the upper or lower 1.2” 
of the heater cavity.  This plate is removed 

ONLY

 

when the 1425 heater is used. Otherwise it must 
be left in place for a blower barrier seal.

7. Make all wiring connections per applicable field 

wiring diagrams in these instructions.  All instruc-
tions 

must

 conform to national, state and local 

electrical codes.

18-HB13D7-5

 

HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING