ACC-SVN150F-EN
9
Figure 10.
Install hinged access door assembly
14. Replace all the panels removed in step 2.
15. F
Fo
orr T
Th
hrro
ou
ug
gh
h tth
he
e B
Ba
asse
e E
Elle
eccttrriicc C
Co
on
nn
ne
eccttiio
on
nss::
Customer conduit connects to the unit disconnect.
The power wires from the disconnect are routed
under the unit control box, along the outdoor
section partition panel and into the electric heater
section. These wires need to be connected to the
terminal block provided in the electric heater
controls assembly.
Refer to the Installation Instructions provided with
the Through the Base Electric Accessory kit for
more details.
Table 4. Unit wiring with electric heat (single point connection) - 60Hz
Tons
Unit Model
Number
Heater Model
Number
Heater kW
Rating
Control
Stages
Standard Indoor
Motor
Oversized Indoor
Motor
MCA
Max Fuse
Size or
Max
Circuit
Breaker
MCA
Max Fuse
Size or
Max
Circuit
Breaker
208/230 Volts Three Phase
15
EBC180A3
BAYHTFC318A
13.5/18
1
75
100
79
100
BAYHTFC336A
27/36
2
106/120
110/125
111/125
125/150
BAYHTFC354A
40.5/54
2
125/142
150/175
130/147
150/175
17½
EBC210A3
BAYHTFC336A
27/36
2
111/125
125/150
116/130
125/150
BAYHTFC354A
40.5/54
2
130/147
150/175
135/152
150/175
BAYHTFC372A
54/72
2
167/190
200/225
172/196
200/225
20
EBC240A3
BAYHTFD336A
27/36
2
111/125
125/150
116/130
125/150
BAYHTFD354A
40.5/54
2
130/147
150/175
135/152
150/175
BAYHTFD372A
54/72
2
167/190
200/225
172/196
200/225