12
ACC-SVN150F-EN
Table 5. Unit wiring with electric heat (single point connection) - 50Hz
Tons
Unit Model
Number
Heater Model
Number
Heater kW
Rating
Control
Stages
Standard Indoor
Motor
Oversized Indoor
Motor
MCA
Max Fuse
Size or
Max
Circuit
Breaker
MCA
Max Fuse
Size or
Max
Circuit
Breaker
380-415 Volts Three Phase
15
EBC180AD
BAYHTFAK18AA
18
2
42
50
42
50
BAYHTFAK36AA
36
2
54
60
54
60
BAYHTFAK54AA
54
2
78
80
78
80
17½
EBC210AD
BAYHTFAK36AA
36
2
54
70
56
70
BAYHTFAK54AA
54
2
78
80
80
80
BAYHTFAK72AA
72
2
82
100
84
100
20
EBC240AD
BAYHTFBK36AA
36
2
61
80
66
80
BAYHTFBK54AA
54
2
80
80
86
90
BAYHTFBK72AA
72
2
84
100
90
100
25
EBC300AD
BAYHTFBK36AA
36
2
61
80
66
80
BAYHTFBK54AA
54
2
80
80
86
90
BAYHTFBK72AA
72
2
84
100
90
100
Note:
Max fuse size or max circuit breaker values do not include power exhaust accessory.