INSTALLER'S GUIDE
STEP
11
-
Replace Heater compartment panel on air
handler.
Section 6. Tables
Important:
The BAYEV* electric heat accessory may include up to a combination of three 60 amp circuit breakers to
provide an electrical disconnect for service personnel that is intended to help protect internal electrical components in
the event of a short circuit or ground fault. As designed, the circuit breakers supplied in the BAYEV* accessory
DO NOT
provide overcurrent protection of the branch circuit. Therefore, the branch circuit(s) shall be sized and protected according
to the unit nameplate.
Table 6.1 BAYEV -- HEATER DATA
Heater Model No.
Number of
Circuits
240 VOLT
208 VOLT
Capacity
Heater Amps
per Circuit
Capacity
Heater Amps
per Circuit
kW
BTUH
kW
BTUH
BAYEVCC25BK1
3
24.00
82000
40/40/20
18.00
61500
34.6/34.6/17.3
Table 6.2 MINIMUM HEATER AIRFLOW CFM - HEATER MATRIX
MODEL NO.
BAYECC25BK1
W/O HP / WITH HP
TAM7A0C48H41S
1625 -- 1813
TAM7B0C60H51S
1625
①
-- 1813
--
TAMGA0C48H41S
1625 -- 1813
TAMGA0C60H51S
1625
①
-- 1813
TAM8A0C48V41C
1625 -- 1813
TAM8B0C60V51C
1625
①
-- 1813
SEE AIR HANDLER NAMEPLATE OR PRODUCT DATA FOR EXCEPTIONS
①
Not approved for 208V when installed in horizontal left position without Heat Pump.