RT-SVN044A-EN

9

Table 3. Economizer module - right hand terminal

blocks

Label

Type

Description

Top Right Terminal Block

n/a

The first pin is not used

AUX2 I

24 Vac IN

Shut Down (SD) or Heat (W)
Conventional only or Heat Pump
Changeover (O/B) in Heat Pump mode

OCC

24 Vac IN

Occupied / Unoccupied Input

E-GND

EGND

Earth Ground - System Required

EXH1

24 Vac OUT

Exhaust Fan 1 Output

AUX1 O

24 Vac OUT

Programmable: Exhaust fan 2 Output or
ERV or System Alarm output

Bottom Right Terminal Block

Y2-I

24 Vac IN

Y2 in - Cooling Stage 2 Input from
Space Thermostat

Y2-O

24 Vac OUT

Y2 out - Cooling Stage 2 Output to
Stage 2 Mechanical Cooling

Y1-I

24 Vac IN

Y1 in - Cooling Stage 1 Input from
Space Thermostat

Y1-O

24 Vac OUT

Y1 out - Cooling Stage 1 Output to
Stage 1 Mechanical Cooling

C

COM

24 Vac Common

R

24 Vac

24 Vac Power (Hot)

Use of the Keypad When Working with
Menus

Navigate to the desired menu.

Press the

button (Enter) to display the first item

in the currently displayed menu.

Use the ∆ and

buttons to scroll to the desired

parameter.

Press the

button (Enter) to display the value of

the currently displayed item.

Press the ∆ button to increase (change) the
displayed parameter value.

Press the

button to decrease (change) the

displayed parameter value.

N

No

otte

e:: When values are displayed, pressing and

holding the ∆ or

buttons causes the display

to automatically increment.

Press the

button to accept the displayed value

and store it in non-volatile RAM.

‘CHANGE STORED’ displays.

Press the

button (Menu Up) to return to the menu

list.

Time-out and Screensaver

When no buttons have been pressed for 10 minutes,
the LCD displays a screensaver, which cycles through
the Status items. Each Status item displays in turn and
cycles to the next item after 5 seconds.

Controller Menu Structure

IIm

mp

po

orrtta

an

ntt::

Table 4, p. 10

illustrates the complete

hierarchy. Your menu parameters will be
different depending on your configuration.
For example if you do not have a DCV (CO

2

)

sensor, then none of the DCV parameters
appear and only MIN POS will display. If
you have a CO

2

sensor, the DCV MIN and

DCV MAX will appear AND if you have 2
speed fan DCV MIN (high and low speed)
and DCV MAX (high and low speed) will
appear.

The menus in display order are:

STATUS

SETPOINTS

SYSTEM SETUP

ADVANCED SETUP

CHECKOUT

ALARMS

E

Ecco

on

no

om

miizze

err C

Co

on

nttrro

olllle

err

Summary of Contents for BAYECON355 Series

Page 1: ...d or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that...

Page 2: ...r p pr ro op pe er r P PP PE E f fo or r t th he e j jo ob b b be ei in ng g u un nd de er rt ta ak ke en n c co ou ul ld d r re es su ul lt t i in n d de ea at th h o or r s se er ri io ou us s i in...

Page 3: ...ri ig ge er ra an nt t h ha an nd dl li in ng g e et tc c W Wh he er re e l lo oc ca al l r re eg gu ul la at ti io on ns s a ar re e m mo or re e s st tr ri in ng ge en nt t t th ha an n t th he es...

Page 4: ...he Keypad When Working with Menus 9 Time out and Screensaver 9 Controller Menu Structure 9 Sequence of Operation 15 Initiation of Operating Modes 16 Economizer Setup and Configuration Field and Factor...

Page 5: ...nspection for Concealed Damage Visually inspect the components for concealed damage as soon as possible after delivery and before it is stored If concealed damage is discovered Notify the carrier s te...

Page 6: ...installation Economizer Side Post Side Post 5 Connect the unit harness to the economizer harness See the figure that follows Additionally connect the green purple white and orange loose wires with mal...

Page 7: ...orange wire is provided for a fault alarm relay or light When the controller s AUX1 OUT is set to SYS this wire will provide 24V when a fault is detected See Figure 7 p 7 Figure 7 Low voltage control...

Page 8: ...emperature sensor is a system critical sensor if it is removed during the set up mode the controller will alarm After 60 minutes the controller will change to Operation mode and all components removed...

Page 9: ...the currently displayed item Press the button to increase change the displayed parameter value Press the button to decrease change the displayed parameter value N No ot te e When values are displayed...

Page 10: ...e OA TEMP c _ _ _ F 40 to 140 F N A Displays measured value of outdoor air temperature Displays F if sensor sends invalid value if not connected short or out of range OA HUM c _ _ 0 to 100 N A Display...

Page 11: ...80 F increment by 1 32 F Setpoint determines outdoor temperature when the mechanical cooling cannot be turned on Commonly referred to as the Compressor lockout At or below the setpoint the Y1 O will n...

Page 12: ...by CFM With 2 speed fan units VENTMIN L low speed fan and VENTMIN H high speed fan settings are required Default for VENTMIN L is 2 5V and VENTMIN H is 2 25V ERV OAT SP 32 F 0 to 50 F increment by 1...

Page 13: ...l briefly flash YES and change to NO but all parameters will change to factory default values MA LO SET c 45 F 35 to 55 F increment by 1 F 45 F Temp to activate Freeze Protection close damper or modul...

Page 14: ...increments 5 Minutes When in economizing mode this is the delay for the high speed fan to try to satisfy the call for second stage cooling before the first stage mechanical cooling is enabled DAMPER...

Page 15: ...are active The menu title ALARMS _ includes the number of active alarms in parenthesis Sequence of Operation Table 5 Dry bulb operation no DCV CO2 sensor 1 speed fan DCV OA Good to economize Y1 I FAN...

Page 16: ...cool when the damper is at 100 open The Economizer mode is controlled by the MAT getting above the MAT SET setting while the OAT is below the DRYBLB SET setting While the fans are not controlled by t...

Page 17: ...ot te e When using the enthalpy Sylk Bus sensors there will be a slight delay while the controller and the sensor communicate Analog sensors do not communicate on the Sylk Bus and output a 20k ohm sig...

Page 18: ...t all wiring connections at the Economizer module s terminals and verify compliance with the installation wiring diagrams For checkout review the status of each configured parameter and perform the ch...

Page 19: ...sh hu ut td do ow wn n b be et tw we ee en n c ch he ec ck ko ou ut t t te es st ts s c co ou ul ld d r re es su ul lt t i in n c co om mp pr re es ss so or r d da am ma ag ge e D Do o n no ot t s sh...

Page 20: ...20 RT SVN044A EN Figure 11 Ultra low leak economizer wiring diagram E Ec co on no om mi iz ze er r C Co on nt tr ro ol ll le er r...

Page 21: ...RT SVN044A EN 21 N No ot te es s...

Page 22: ...22 RT SVN044A EN N No ot te es s...

Page 23: ...RT SVN044A EN 23 N No ot te es s...