INSTALLER'S GUIDE

ALL phases of this installation must comply with

NATIONAL, STATE AND LOCAL CODES.

IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.

Concentric Vent Kit for 

Condensing Furnaces and Boilers

DO NOT APPLY TO A NON-CONDENSING FURNACE.

NOTE:  If these instructions differ from those packaged with 

the furnace or boiler, follow these instructions.

 

DESCRIPTION AND USAGE
Kit Contents:

 1 — Rain cap 
1 — 4" Diameter SDR-26 Pipe, 23.75" Long 
1 — 2

1

/

2

" Diameter SDR-26 Pipe, 33.12" 

1 — Wye concentric Fitting

Only one vent kit per each furnace or boiler is allowed. 

Vent kit is for 2, 2-1/2 or 3 in. diameter pipe systems, (See 
Figures 3, 4, 5, and 6 for the different applications.) Both 
the combustion air and vent pipes must attach to the vent 
kit.  The vent kit must terminate outside of the structure and 
should be installed vertically as shown in Figures 3 and 4, or 
horizontal as shown in Figures 5 and 6. 

NOTE:  The roof vent location is preferred since it is less 

susceptible to damage, has reduced chances to intake con-

taminants, and vent vapors are less visible.

NOTE:  Codes and local utility requirements governing the 

installation of gas fired equipment, wiring, plumbing, and 

flue connections must be adhered to. In the absence of local 

codes, the installation must conform with the Nation Fuel 

Gas Code ANSI Z223.1 "latest edition", or CAN/ CGA B149 

Installation Codes. The latest code may be obtained from the 

American Gas Association Laboratories  400 N. Capitol St. 

NW, Washington D.C.  20001, 1-800-699-9277 or  www.aga.

com

NOTE:  Read the Installer's Guide before starting the instal-

lation. Refer to the Furnace or boiler Installer's Guide for 

equivalent vent lengths. The BAYAIR30AVENTA is 5 equiva-

lent feet.

 

INTRODUCTION
This Installer's Guide covers installation of the concentric vent 
kit on all gas fired direct vent condensing furnaces. 

BAYAIR30AVENTA

WARNING

!

INSTALLATION OR REPAIRS MADE BY UNQUALIFIED 

PERSONS CAN RESULT IN HAZARDS TO YOU AND OTH-

ERS. INSTALLATION MUST CONFORM  WITH LOCAL CODES 

OR, IN THE ABSENCE OF LOCAL CODES, WITH CODES OF 

THE COUNTRY HAVING JURISDICTION. THE INFORMATION 

CONTAINED IN THESE  INSTRUCTIONS IS INTENDED FOR 

USE BY A QUALIFIED SERVICE TECHNICIAN FAMILIAR WITH 

SAFETY PROCEDURES AND EQUIPPED WITH THE PROPER 

TOOLS AND TEST INSTRUMENTS. FAILURE TO CAREFUL-

LLY READ AND FOLLOW ALL INSTRUCTIONS IN THESE 

INSTRUCTIONS CAN RESULT IN FURNACE OR BOILER 

MALFUNCTION, PROPERTY DAMAGE, PERSONAL INJURY 

AND/ OR DEATH.

RAIN CAP

4" SDR-26 PIPE

2-1/2" SDR-26 PIPE

WYE - CONCENTRIC FITTING

CONCENTRIC VENT KIT

WARNING

!

INSTALLING AND SERVICING HEATING EQUIPMENT CAN 

BE HAZARDOUS DUE TO GAS AND ELECTRICAL COMPO-

NENTS. ONLY TRAINED PERSONNEL SHOULD INSTALL OR 

SERVICE HEATING EQUIPMENT. FAILURE TO FOLLOW THIS 

WARNING CAN RESULT IN PRODUCT DAMAGE, PERSONAL 

INJURY AND/OR DEATH.

WARNING

!

THIS VENT KIT IS ONLY TO BE USED FOR VENTING CAT-

EGORY IV FURNACES AND CONDENSING BOILERS. DO 

NOT USE TO VENT CATEGORY I, II OR III VENT FURNACES 

OR BOILERS. FAILURE TO FOLLOW THIS WARNING COULD 

RESULT IN FIRE, PERSONAL INJURY OR DEATH.

Field supplied pipe and fittings are required to complete the 
installation.
The combustion air and vent pipe and fittings must conform to 
American National Standards Institute (ANSI) and American 
Society for Testing and Materials (ASTM) standards D1785 
(schedule-40 PVC), D2665 (PVC-DWV), D2441 (SDR-21 and 
SDR-26 PVC), D2661 (ABS-DWV), or F628 (schedule-40 ABS).  
Pipe cement and primer must conform to ASTM standards D2564 
(PVC) or D2235 (ABS).  In Canada, construct all combustion air 
and vent pipes for this unit of CSA or ULC certified schedule-40 
PVC/ABS-DWV pipe and pipe cement.

WARNING

!

DISCONNECT POWER SUPPLY BEFORE BEGINNING IN-

STALLATION TO PREVENT PERSONAL INJURY OR DEATH 

FROM ELECTRICAL SHOCK AND EQUIPMENT DAMAGE.

1

Service Literature 

Unitary 

Unitary Accessories 

Vents 

Installer's Guide 

02/12 

18-CH34D1-7

18-CH34D1-56 

Library                                                               
Product  Section                                                                  
Product                                                           
Model
Literature  Type                                                     
Sequence                                                                                
Date                                                                               
File No.
Supersedes

For use with *UH, *DH, M95, *UY, *DY, *UX, *DX, 
*UC, *DC model Furnaces and TGCW130A90M0A 
and TGXWW130A90M0A boilers  
* may be A or T or C

NOTE:   
Canada requires that all Category IV heating appliances use 
venting material that meets ULC S636. This kit does not meet 
these requirements and cannot be used. 