background image

BAS-SVP09B-EN

29

Object Data Points and Diagnostic Data Points

Multi-State Input, 44

Economizer System Status Indicates the operating state of the 

waterside economizer system.

1 = Disabled

 

2 = Enabled

 

3 = Not Present

Multi-State Input, 45

Service Test Status

Indicates the current Service Test state

1 = Inactive

2 = Fan On

 

3 = IGV Open

 

4 = IGV Close

5 = Min Vent

6 = Econ Open

 

7 = Cool 1

 

8 = Cool 2

 

9 = Cool 3

 

10 = Dehumidification/Reheat

 

11 = Heat 1

 

12 = Heat 2

 

13 = Heat 3

 

14 = Heat 4

 

15 = Defrost

 

16 = Emergency Heat

Table 8.

Binary Output

Object Identifier

Object Name

Description

Relinquish 

Default

Object States

Binary Output, 1

System Control Command

Command the unit to standalone- 

or BAS-controlled operation.

Inactive

Inactive = Standalone Control

 

Active = BAS Control

Binary Output, 5

Heat Lockout Command

Command the unit to prevent 

heating operation.

Inactive

Inactive = Allow Heating

 

Active = Heating Locked Out

Binary Output, 6

Cool Lockout Command

Command the unit to prevent 

cooling operation.

Inactive

Inactive = Allow Cooling

 

Active = Cooling Locked Out

Binary Output, 7

Economizer Minimum Position Enable 

Command

Command the unit to the minimum 

position operation.

Inactive

Inactive = Disabled

 

Active = Enabled

Binary Output, 8

Supply Fan Configuration Command

Command the unit supply fan to 

cycling or continuous operation.

Inactive

Inactive = Auto

 

Active = On

Binary Output, 13

Filter Timer Reset

Command the unit to reset the 

accumulated filter run hours.

Inactive

Inactive = Accumulating

 

Active = Reset

Binary Output, 14

Reset Diagnostic

Command the unit to reset and 

clear diagnostics.

Inactive

Inactive = Normal

 

Active = Reset

Binary Output, 15

Dehumidification Enable Command

Command the operating state of 

the dehumidification system.

Active

Inactive = Disabled

 

Active = Auto

Binary Output, 17

Service Test Command

Command the unit to step through 

service test

1 (Auto)

Inactive = Normal

 

Active = Service test

Binary Output, 18

Supply Air Tempering Enable Command Command the unit supply air 

tempering operation.

Inactive

Inactive = Disabled

 

Active = Enabled

Binary Output, 19

Lead-Lag Enable Command

Command the unit compressor 

startup order

Inactive

Inactive = Disabled

 

Active = Enabled

Binary Output, 20

Morning Warmup Enable Command

Command the unit morning 

warmup operation

Inactive

Inactive = Disabled

 

Active = Enabled

Binary Output, 21

Daytime Warmup Enable Command

Command the unit daytime 

warmup operation

Inactive

Inactive = Disabled

 

Active = Enabled

Table 9.

Binary Input 

Object Identifier

Object Name

Description

Object States

Binary Input, 1

System Control Status

Indicates the control system currently in 

command of the unit.

Inactive = Standalone control

 

Active = BAS control

Binary Input, 2

Compressor Lockout Status

One or more compressors are locked out with 

no diagnostic.

Inactive = Normal

 

Active = Locked Out

Binary Input, 9

VAV Box Command

Indicates whether VAV boxes should be in 

control or wide open.

Inactive = Auto

 

Active = Open

Binary Input, 11

Service Test Mode Status

Indicates if the unit is in service test mode.

Inactive = Inactive

 

Active = Active

Binary Input, 15

Supply Fan Configuration Status

Indicates the supply fan configuration.

Inactive = Cycling

 

Active = Continuous

Table 7.

Multistate Input (continued)

BCI-R Object 
Identifier

Object Name

Description

Object States

 

*not all states apply to all equipment

Summary of Contents for BACnet BCI-R

Page 1: ...cautions in the literature and on the tags stickers and labels that are attached to the equipment March 2011 BAS SVP09B EN Integration Guide BACnet Communication Interface for ReliaTel Controllers BCI...

Page 2: ...t the written permission of Trane Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change...

Page 3: ...ration 13 BAS Unit Control 13 Initiating System Control 13 Output and Input Object Data Points 13 Periodic Update of BAS Values 14 BAS Communication Failure 14 Input Output Commands and Calculations 1...

Page 4: ...ilding automation systems or components from different manufacturers to share information and control functions BACnet provides building owners the capability to connect various types of building cont...

Page 5: ...not have defaults the BST or Tracer TU will display the device units of the controller to which it is connected Setting Addresses on the Rotary Switches There are three rotary switches on the front o...

Page 6: ...Communication If using a wireless COMM interface WCI set the link select switch to IMC as shown in Figure 2 For wiring instructions refer to the BACnet Communication Interface for ReliaTel Controller...

Page 7: ...tup Tool Online help is available by clicking the help icon located in upper right portion of the screen 1 Open the Tracer BACnet Setup Tool The Controller Settings screen appears Figure 3 2 In the Pr...

Page 8: ...irect Connection USB cable radio button if it is not already selected 4 Click the Connect button and the Unit Summary page will appear after successful connection To configure the BCI R controller 1 S...

Page 9: ...ystems p 10 BACnet Device ID Tracer SC uses the rotary dial settings MAC address to create the BACnet device ID The Tracer SC adds an SC rotary dial address and a link number to artificially create a...

Page 10: ...rom the rotary dials Although 999 is possible from the dials the maximum allowed number by BACnet is 127 The Max Master is not adjustable in Trane SC systems For example if the MAC address is 101 and...

Page 11: ...OK When the controller is cleared the Select Device Units message box appears 5 Click OK and then expand the Controller Units box on the Controller Settings screen 6 Select the units SI IP or Custom...

Page 12: ...immediately often within one second Immediately after the points are created the device units are set and saved and appear on the Controller Units screen The values that correspond to the device unit...

Page 13: ...quest Multi State Output 8 Heat Cool Mode Request BAS Multi State Output 2 Emergency Override Command Analog Output 2 Space Temperature Setpoint BAS Analog Output 29 Occupied Offset Analog Output 30 S...

Page 14: ...pace CO2 Concentration BAS Space Humidity BAS Input Output Commands and Calculations This section will provide the following information about certain inputs and outputs that perform Filter timer and...

Page 15: ...points are calculated for space temperature control When the unit is in an occupied mode the active space temperature setpoint is calculated based on the space temperature setpoint and the two setpoin...

Page 16: ...ent Not illuminated The controller is off Link Tx Rx TX blinks green Data is being transferred received or transmitted RX blinks yellow Blinks at the data transfer rate when the unit receives data fro...

Page 17: ...Cnet Advanced Application Controller B AAC BACnet Application Specific Controller B ASC 9 BACnet Building Controller B BC BACnet Operator Workstation B OWS BACnet Smart Actuator B SA BACnet Smart Sens...

Page 18: ...nt Dynamic Device Binding A DM DDB A 9 Device Management Dynamic Device Binding B DM DDB B 9 Device Management Dynamic Object Binding B DM DOB B 9 Device Management List Manipulation B DM LM B 9 Devic...

Page 19: ...bility Min_Pres Value Max_Pres_Value Time_Delay Notification _Class High_Limit Low_Limit Deadband Limit_Enable Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Yes Yes only user created ob...

Page 20: ...set Elapsed_Active_Time Time_Of_Active_Time_Reset Priority_Array Relinquish_Default Minimum_On_Time Minimum_Off_Time Time_Delay Notification_Class Alarm_Value Event_Enable Acked_Transitions Notify_Typ...

Page 21: ...lue Status_Flags Event_State Out_Of_Service Number_Of_States Object_Name Description State_Text Out_Of_Service Present_Value Reliability Priority_Array Relinquish_Default Time_Delay Notification_Class...

Page 22: ...net Clause 7 10Base2 10Base5 10BaseT Fiber LonTalk Clause 11 Medium MS TP Master Clause 9 Baud Rate s 9600 19200 38400 and 76800 1 5 Nominal Baud Rate 9 MS TP Slave Clause 9 Baud Rate s Other Point to...

Page 23: ...s support for multiple characters sets but does not imply that all character sets are supported simultaneously Maximum supported string length is 64 bytes any character set Character Set Descriptions...

Page 24: ...a 53 0 3 inH2O 74 Pa 0 3 to 0 2 NA Analog Output 10 Space Static Pressure BAS BAS supplied space static air pressure sensor value 0 67 inH2O 167 Pa 53 0 67 inH2O 167 Pa 0 67 to 0 67 900 Analog Output...

Page 25: ...Discharge Air Temperature Active The discharge air temperature currently used for unit control Fahrenheit 64 Celcius 62 Analog Input 25 Mixed Air Temperature The mixed air temperature value from a uni...

Page 26: ...Major software version number of the RTRM module NA Analog Input 92 RTRM Minor Version Minor software version number of the RTRM module NA Analog Input 93 RTOM Major Version Major software version num...

Page 27: ...states apply to all equipment Multi State Input 2 Trane Unit Type General description of the equipment type classification 1 1 Heat 1 Cool 2 Heat Pump 3 Blower Coil 4 Unit Ventilator 5 Fan Coil 6 Roof...

Page 28: ...tate Input 29 Heat Output 1 Indicates the commanded state of heating output 1 1 Off 2 On 3 Not Present Multi State Input 30 Heat Output 2 Indicates the commanded state of heating output 2 1 Off 2 On 3...

Page 29: ...d clear diagnostics Inactive Inactive Normal Active Reset Binary Output 15 Dehumidification Enable Command Command the operating state of the dehumidification system Active Inactive Disabled Active Au...

Page 30: ...Pressure Setpoint Failure Diagnostic SA Pressure Setpoint Failure 002 Service Required Binary Input 55 Diagnostic Space Pressure Setpoint Fail Diagnostic Space Pressure Setpoint Fail 002 Service Requ...

Page 31: ...Disable Input HPC 004 Information Binary Input 270 Diagnostic Comp 2 Disable Input HPC Diagnostic Comp 2 Disable Input HPC 004 Information Binary Input 271 Diagnostic CO2 Low Limit Setpoint Fault Dia...

Page 32: ...e Command Command the operating state of the dehumidification system Analog Input 58 Dehumidification High Limit Setpoint Humidity setpoint value that starts dehumidification control Analog Output 6 D...

Page 33: ...morning warmup mode Multi State Output 7 Occupancy Request Command the unit into an occupancy mode Multi State Input 20 Occupancy Status Indicates the current occupancy mode of the unit Analog Output...

Page 34: ...Setpoint Input Cooling temperature setpoint from space sensor module Analog Input 75 Space Temperature Heating Setpoint Input Heating temperature setpoint from space sensor module Analog Input 87 Spac...

Page 35: ...n Binary Input 252 Diagnostic Default Defrost Flag Diagnostic Default Defrost Flag 004 Information Binary Input 287 Diagnostic Defrost Default Mode Ckt 1 Diagnostic Defrost Default Mode Ckt 1 004 Info...

Page 36: ...od Dehumid Config Error Diagnostic Mod Dehumid Config Error 004 Information Binary Input 239 Diagnostic Morning Warmup Setpoint Fail Diagnostic Morning Warmup Setpoint Fail 002 Service Required Binary...

Page 37: ...ail Diagnostic Space Pressure Setpoint Fail 002 Service Required Binary Input 36 Diagnostic Supply Air Press Sensor Fail Diagnostic Supply Air Press Sensor Fail 002 Service Required Binary Input 30 Di...

Page 38: ...cks Building Automation Control network BACnet and ANSI ASHRAE Standard 135 2008 An interoperable protocol developed specifically for the building controls industry The American National Standards Ins...

Page 39: ...BAS SVP09B EN 39 Glossary...

Page 40: ...Trane offers a broad portfolio of advanced controls and HVAC systems comprehensive building services and parts For more information visit www Trane com Trane has a policy of continuous product and pro...

Reviews: