Object Data Points and Diagnostic Data Points
Table 6.
Multistate Output
BCI-R Object Identifier
Object Name
Description
Object States
*not all states apply to all equipment
Multi-State Output, 1
Economizer Airside Enable BAS
Command the state of the airside economizer
system.
1 = Disabled
2 = Enabled
3 = Auto
Multi-State Output, 2
Emergency Override Command
Command the unit into an emergency mode of
operation.
1 = Normal
2 = Pressurize
3 = Depressurize
4 = Purge
5 = Shutdown
6 = Fire
Multi-State Output, 7
Occupancy Request
Command the unit into an occupancy mode.
1 = Occupied
2= Unoccupied
3 = Occupied Bypass
4 = Occupied Standby
Multi-State Output, 8
Heat Cool Mode Request BAS
Command the unit to a specific application
mode.
1 = Auto
2 = Heat
3 = Morning Warmup
4 = Cool
5 = Night Purge
6 = Precool
7 = Off
8 = Test
9 = Emergency Heat
10 = Fan Only
11 = Free Cool
12 = Ice Making
13 = Max Heat
14 = Economy Mode
15 = Dehumidifying
16 = Calibrate
Table 7.
Multistate Input
BCI-R Object
Identifier
Object Name
Description
Object States
*not all states apply to all equipment
Multi-State Input, 2
Trane Unit Type
General description of the equipment-type
classification.
1 = 1 Heat/1 Cool
2 = Heat Pump
3 = Blower Coil
4 = Unit Ventilator
5 = Fan Coil
6 = Rooftop
7 = Air Handler
8 = Vertical Self Contained
9 = Unitary
10 = VAV Box
11 = Fan Coil
Multi-State Input, 9
Economizer Type
General description of the equipment
economizer system.
1 = None
2 = 2 Position Ventilation
3 = Modulation Economizer
4 = 2 Position Ventilation/Waterside Economizer
5 = Waterside Economizer
6 = Airside/Waterside Economizer
7 = TRAQ Damper
8 = Airside Economizer and TRAQ Damper/Sensor
9 = Waterside Economizer and TRAQ Damper/Sensor
10 = Airside/Waterside Economizer and TRAQ Damper/Sensor
Multi-State Input, 17
Cooling Reset Type Status Indicates the type of cooling reset.
1= None
2= Outdoor Air
3= Zone
Multi-State Input, 19
Heat Cool Mode Status/
Application Mode Status
Heat Cool Mode Status: matches the
defined system display name and the
display name used in TU.
Application Mode Status: the point name
used in the device.
1 = Auto
2 = Heat
3 = Morning Warm-up
4 = Cool
5 = Night Purge
6 = Pre Cool
7 = Off
8 = Test
9 = Emergency Heat
10 = Fan Only
11 = Free Cool
12 = Ice-Making
13 = Max Heat
14 = Economy Mode
15 = Dehumidifying
16 = Calibrate