BAS-SVP09B-EN
Object Data Points and Diagnostic Data Points
Analog Input, 71
Exhaust Enable Damper Position Setpoint
Status
Exhaust air damper minimum position to enable
exhaust sequence.
Percent (98)
Analog Input, 74
Space Temperature Cooling Setpoint Input
Cooling temperature setpoint from space sensor
module.
Fahrenheit (64)
Celcius (62)
Analog Input, 75
Space Temperature Heating Setpoint Input
Heating temperature setpoint from space sensor
module.
Fahrenheit (64)
Celcius (62)
Analog Input, 78
Space Temperature Setpoint Local
The local space temperature setpoint.
Fahrenheit (64)
Celcius (62)
Analog Input, 79
Dehumidification Capacity Status
Indicates the unit dehumidification capacity being
utilized.
Percent (98)
Analog Input, 80
Cabinet Style
Describes the cabinet style of the unit.
NA
Analog Input, 81
Cool Type
Describes the cooling type installed in the unit.
NA
Analog Input, 82
Preheat Type
Describes the heating type installed in the unit.
NA
Analog Input, 83
Reheat Type
Describes the reheat type installed in the unit.
NA
Analog Input, 86
Economizer Minimum Position Setpoint Local Indicates the local economizer minimum position
setpoint.
Percent (98)
Analog Input, 87
Space Temperature Local
The space air temperature measured by a unit-
mounted sensor.
Fahrenheit (64)
Celcius (62)
Analog Input, 88
Unit Energy Demand
Indicates the current heat/cool energy demand of the
unit.
Percent (98)
Analog Input, 89
Supply Fan Type
Describes the supply fan type installed in the unit.
NA
Analog Input, 90
Exhaust or Return Fan Type
Describes the exhaust or return fan type installed in the
unit.
NA
Analog Input, 91
RTRM Major Version
Major software version number of the RTRM module
NA
Analog Input, 92
RTRM Minor Version
Minor software version number of the RTRM module
NA
Analog Input, 93
RTOM Major Version
Major software version number of the RTOM module
NA
Analog Input, 94
RTOM Minor Version
Minor software version number of the RTOM module
NA
Analog Input, 95
BCI-R Major Version
Major software version number of the BCI-R module
NA
Analog Input, 96
BCI-R Minor Version
Minor software version number of the BCI-R module
NA
Analog Input, 97
RTAM Major Version
Major software version number of the RTAM module
NA
Analog Input, 98
RTAM Minor Version
Minor software version number of the RTAM module
NA
Analog Input, 99
RTEM Major Version
Major software version number of the RTEM module
NA
Analog Input, 100
RTEM Minor Version
Minor software version number of the RTEM module
NA
Analog Input, 101
RTDM Major Version
Major software version number of the RTDM module
NA
Analog Input, 102
RTDM Minor Version
Minor software version number of the RTDM module
NA
Analog Input, 103
RTVM Major Version
Major software version number of the RTVM module
NA
Analog Input, 104
RTVM Minor Version
Minor software version number of the RTVM module
NA
Analog Input, 105
RTCM Major Version
Major software version number of the RTCM module
NA
Analog Input, 106
RTCM Minor Version
Minor software version number of the RTCM module
NA
Analog Input, 107
Space Static Pressure Setpoint Active
Space pressure setpoint currently used for unit control Inches-of-water (58)
Table 5.
Analog Value
Object Identifier
Object Name
Description
Units
Valid Range
Analog Value, 1
Filter Runtime Hours Setpoint
The setpoint value used by the
filter run hours calculation.
Hours (71)
0 to 10,000
Table 4.
Analog Input (continued)
Object Identifier
Object Name
Description
Units of Measure
IP/SI