WSHP-SVX02E-EN
Dimensions and Clearances
WARNING
Improper Unit Lift!
Failure to properly lift unit in a LEVEL position could
result in unit dropping and possibly crushing operator/
technician which could result in death or serious injury,
and equipment or property-only damage.
Test lift unit approximately 24 inches (61 cm) to verify
proper center of gravity lift point. To avoid dropping of
unit, reposition lifting point if unit is not level.
Table 1.
Unit weights
Size
Approximate Shipping
Weight with pallet (lb)
Approximate Weight
without pallet (lb)
EXW*060
326
296
EXW*120
653
613
EXW*240
1222
1156
Unit Location and Clearances
Locate the unit in an indoor area. The ambient
temperature surrounding the unit must not be less than
45°F. Do not locate the unit in areas subject to freezing.
Attention should be given to service clearance and
technician safety. The unit access panels may be easily
removed. There must be enough space for service
personnel to perform maintenance or repair. Provide
sufficient room to make water, and electrical
connection(s). Local and national codes should be
followed in providing electrical power connections. Refer
to the figure below for mechanical clearances.
Figure 1.
Unit location and clearances
CONTROL BOX
FRONT OF UNIT
TOP VIEW
EXW*060
EXW*120
EXW*240
36"
(914)
18"
(457)