Table 13. Water volume
Unit Size
Water Volume Cubic Inches
Water Volume Cubic Feet
Water Volume Gallons (U.S)
EXW*060
359.6
0.21
1.57
EXW*120
719.2
0.42
3.14
EXW*240
2079.0
1.20
8.98
Note:
The above water volume is the total unit water volume ( Load), divide the above volume by 2 to obtain source or load side volumes individually.
Operating Data
WSHP-SVX02E-EN
25
Flow Checks
For the operating temperature drop (heating) and rise
(cooling), refer to Table 7 through Table 12 for the proper
water temperature change. Depending on the unit size
entering water temperature and water flow rate, the
cooling temperature rise is from 8°F-16°F. Based on the
same criteria for heating, the temperature drop is from
2°F-13°F.
Pressure
Using the P/T ports and one 0-60 psi pressure gauge with
the P/T port adapter, measure the pressure difference
between the water-in and water-out connections.
Compare the pressure differential to Table 7 through Table
12 to determine flow.
Start-up Checklist and Log
In order to minimize troubleshooting and costly system
failures, complete the following checks and data entries
before the system is put into full operation.
Job Name:
Model Number:
Date:
Serial Number:
Installing Contractor: Use this form to thoroughly check-
out the system and units before and during start-up. (This
form need not be returned to the factory unless requested
during technical service support).
MODE
Heat
Cool
Source
Load
Source
Load
Entering fluid temperature
°F
°F
°F
°F
Leaving fluid temperature
°F
°F
°F
°F
Temperature differential
°F
°F
°F
°F
Water coil heat exchanger (Water Pressure IN)
°F
°F
°F
°F
Water coil heat exchanger (Water Pressure OUT)
°F
°F
°F
°F
Pressure Differential
°F
°F
°F
°F
COMPRESSOR
Amps
Volts
Discharge line temperature
(after 10 minutes)
°F
°F
°F
°F