14
WSHP-SVX014F-EN
Figure 2.
Clearance – EXVG/DXVG 0.75 to 6 Tons
36"
1"
1"
UNIT FRONT
LEFT
RETURN
TOP/BACK
SUPPLY
1"
1"
24"
UNIT FRONT
36"
RIGHT
RETURN
TOP/BACK
SUPPLY
24"
A 24 inch clearance from other mechanical and electrical equipment
(where shown) is recommended for most unit configurations. This
will enable panel removal from the unit for service/maintenance.
The 24 inch side clearance on EXVG/DXVG 0.75-6T models is for
optimal access only. Side clearance is not a requirement as most
components can be accessed from the front of the unit.
A 1 inch minimum clearance between the filter rack and any
obstacle is required for units in a free return application to provide
proper air flow to the air-to-refrigerant coil. A 12 inch minimum
clearance between the filter rack and any obstacle should be
provided to properly attached ductwork.
The 1 inch dimension shown in the back of the unit represents the
supply duct collar for the back supply option. This clearance is
needed to clear these flanges.
Unit Dimensions
Figure 3. Left return/left supply (EXHF/DXHF)
TOP
BACK
LEFT SIDE
FRONT
RIGHT SIDE
B
P
N
A
C
H
H
E
D
J
1"
K
1
/
2
"
DRAIN
3/4" NPTI
BLOWER
ACCESS
PANEL
F X G
OPENING
COMP/CONTROL
ACCESS
HI VOLT
L (W.O.)
M (W.I.)
LO VOLT
14"
Q
R
S
1"
1
3/8"
6
3/4
"
7"
WCI mounting location
Table 4. Left return/left supply (EXHF/DXHF)
Unit
A
B
C
D
(a)
E
F x G
H
J
K
L
NPTI
M
NPTI
N
P
Q
R
(b)
S
EXHF006-009
40
20
15
20
15
6-7/8 x 8 11-1/2
4-1/2
1-3/4
1/2
1/2
38-3/4
18-3/4
13-5/8
18-1/2
3-1/4
EXHF012-015
40
20
15
20
15
8-1/4 x
9-3/4
11-1/2
4-1/4
3/4
1/2
1/2
38-3/4
18-3/4
13-5/8
18-1/2
3-1/4
EXHF018
EXHF/DXHF024
46
23
18
23
18
8-1/4 x
11-3/8
13-1/2
4-3/4
1-3/8
3/4
3/4
44-3/4
21-3/4
16-5/8
18-1/2
4-1/4