62
ARTC-SVX006A-EN
Logical Flow Diagrams
The following section presents the simplified logical flow
block diagrams for the principal systems in the AXM air-to-
water modular heat pump.
High Voltage Logical Flow
AXM heat pump models are available in a range of voltage/
amperage/phase configurations to meet the demands of a
worldwide market. The high voltage configuration for a heat
pump module is listed on each module’s name plate. The
heat pump is designed to operate with high voltage power
supplied to the unit at all times. See
Figure 24.
High voltage logical flow of single module
PDB1
CB1
.
40A
MS1
M1A
OL1
34.6 RLA (1.56)
38.6 RLA (1.4)
460V, 3PH, 60 Hz
15T/15HP
REFRIGERATION
COMPRESSOR
M1
174 LRA
CB2
.
40A
MS2
M2A
OL2
34.6 RLA (1.56)
38.6 RLA (1.4)
460V, 3PH, 60 Hz
15T/15HP
REFRIGERATION
COMPRESSOR
M2
174 LRA
2A
FU1
MS1
CRANKCASE HEATER
93VA
460V
REFRIG COMP M1
HTR1
2A
FU2
MS1
ACCUMULATOR HEATER
93VA
460V
REFRIG COMP M1
HTR2
2A
FU3
MS2
CRANKCASE HEATER
93VA
460V
REFRIG COMP M2
HTR3
2A
FU4
MS2
ACCUMULATOR HEATER
93VA
460V
REFRIG COMP M2
HTR4
HTR1A
HTR3A
HTR4A
HTR2A
3A
FU5
250 VA
XF1
480/24 VAC
3A
FU6
POWER SUPPLY
10A
OUTPUT: 24VDC
1.9A
INPUT: 200-500VAC
24V DC
PWS1
*PRIMARY
MODULE
ONLY*
10A
FU7
M3A
EC AXIAL FAN
1195 RPM
5.0 FLA
460V, 3PH, 60 Hz
FB1
FAN #1
M3
10A
FU8
M4A
EC AXIAL FAN
1195 RPM
5.0 FLA
460V, 3PH, 60 Hz
FB1
FAN #2
M4
460 VAC, 60 HZ, 3 PHASE
MOP 124A, MCA 90A
SELECT CONDUCTOR SIZE RATED @ 75°C
DEVICES
TO 24V AC
DEVICES
TO 24V DC
MONITOR
PHASE
3-PH
VM1
400 - 480 VAC
PDB2
HEAT TAPE POWER SUPPLY
FROM DISTRIBUTION PANEL
120 VAC, 60 HZ, 1 PHAS
HEAT
HTC
TAPE
X WATTS
Control Logical Flow
The heat pump uses low voltage for controller and sensor
circuits. See following figure.