ARTC-SVX006A-EN
55
Table 11.
Interface panel diagnostic code key (continued)
ALARM
RESET
ACTION
EVD Driver B Alarm
Auto
Warning
EVD 2 offline
Auto
Warning
EVD 2 System Alarm
Auto
Warning
EVD 2 Driver A Alarm
Auto
Warning
EVD 2 Driver B Alarm
Auto
Warning
Evaporator Freezing Alarm
User
Locks out module
Phase Monitor Alarm
Auto
Locks out module
Load Flow Alarm
User
Locks out module
HP Alarm
User
Shuts down Circuit 1 / 2
HP Switch Alarm
Auto
Shuts down Circuit 1 / 2
LP Alarm
Auto
Shuts down Circuit 1 / 2
LP Lockout Alarm
User
Shuts down Circuit 1 / 2
Ebm Papst Fan 1 Warning
Auto
Warning
Ebm Papst Fan 1 Failure
User
Shuts down Fan 1
Ebm Papst Fan 1 Offline
Auto
Shuts down Fan 1
Ebm Papst Fan 2 Warning
Auto
Warning
Ebm Papst Fan 2 Failure
User
Shuts down Fan 2
Ebm Papst Fan 2 Offline
Auto
Shuts down Fan 2
Ebm Papst Fan 3 Warning
Auto
Warning
Ebm Papst Fan 3 Failure
User
Shuts down Fan 3
Ebm Papst Fan 3 Offline
Auto
Shuts down Fan 3
Ebm Papst Fan 4 Warning
Auto
Warning
Ebm Papst Fan 4 Failure
User
Shuts down Fan 4
Ebm Papst Fan 4 Offline
Auto
Shuts down Fan 4
Rosenberg Fan 1 Warning
Auto
Warning
Rosenberg Fan 1 Failure
User
Shuts down Fan 1
Rosenberg Fan 1 Offline
Auto
Shuts down Fan 1
Rosenberg Fan 2 Warning
Auto
Warning
Rosenberg Fan 2 Failure
User
Shuts down Fan 2
Rosenberg Fan 2 Offline
Auto
Shuts down Fan 2
Rosenberg Fan 3 Warning
Auto
Warning
Rosenberg Fan 3 Failure
User
Shuts down Fan 3
Rosenberg Fan 3 Offline
Auto
Shuts down Fan 3
Rosenberg Fan 4 Warning
Auto
Warning
Rosenberg Fan 4 Failure
User
Shuts down Fan 4
Rosenberg Fan 4 Offline
Auto
Shuts down Fan 4
Secondary 1 communication lost
Auto
Warning