background image

 

Page 11

Installer’s Guide

Figure 7. Typical Ground Level Applications

Note: 

Use the extreme mount-

ing kit, BAYEXMK003A, to 
secure the unit to the slab.

Step 4—Unit Installation

 NOTE: 

The factory ships this unit for horizontal installation.

Install Flue Hood

1.  Locate the Flue Hood in the literature package.

2.  Remove the two Flue Hood mounting screws from the unit. 

They  
are located to the right of the Power Entry connection panel.  

3.  Attach the Flue Hood to the unit with the two screws removed 

in 
 step 2. See Figure 2 on page 5 or Figure 5 on page 8 for cor-
rect orientation of the Flue Hood.

Ground Level Installation

To install the unit at ground level:
1.  Place the unit on a pad the size of the unit or larger.  The unit must 
   be mounted level for proper drainage of water through the holes  
  in the base pan. To securely attach the unit to the slab, use 
 

extreme mounting kit, BAYEXMK003A.

 

The pad must not come in contact with the structure (see Figure 

  7.) Be sure the outdoor portion of the supply and return air  
 

ducts are as short as possible.
Unit requires vibration support as indicated in Figure 7 below 
and in Figure 9 on page 13.

2.  The louvers above and below the Flue Hood in the side  

 

 

panel must have adequate clearance around the air  

 

 

opening into the combustion area. 

3.  Location of the unit must allow service clearance around it.  

Clearance of the unit must be given careful consideration.  See 
Figures 1 to 6, pages 4-9.

  

NOTE: 

Any reduction of the unit clearances indicated in these 

illustrations may result in condenser coil starvation or the 
recirculation of warm condenser air.  Actual clearances, which 
appear to be inadequate should be reviewed with a local 
engineer.

   IMPORTANT: 

A minimum 0” clearance to combustible mate-

rial shall be maintained on air outlet duct.

Rooftop Installation -- Curb Mounting

Convert Horizontal Airflow to Down Airflow

The factory ships the unit  for horizontal airflow.  Perform  this 
procedure to convert the unit to down airflow:

1.  Remove the three (3) sheet metal screws securing the supply 
aircover and the four (4) sheet metal screws securing the return 
air  cover from the base of the unit. Remove the covers from the 
base. See Figure 8, page 12.

2.  Place the covers over the horizontal supply and return open-
ings (painted side out). Align the screw holes, and secure using 
the same screws removed in step 1.

4.   Attach the supply and return air ducts to the unit as explained 

in the following Ductwork Installation section on page 16.

5.  Flexible duct connectors must be of a flame retardant material. 

Insulate any ductwork outside of the structure with at least two 
(2) inches of insulation and weatherproof. There must be a 
weather proof seal where the duct enters the structure.

6.   Do not expose the unit to direct roof water runoff.
7.   Seal all holes through exterior walls in accordance with local 

codes.

8.   Continue with the following installation sections to complete 

the installation: Ductwork on page 16, Gas Piping on page 16, 
Filter on page 19, and Electrical Wiring on page 19.

Install Full Perimeter Roof Mounting Curb

1.  Verify that the roof mounting curb is correct for the unit. There 
are two curbs depending on the unit cabinet sizes: 

    • 

4YCZ6024-036 uses model BAYCURB050A.

    • 

4YCZ6048 through 4YCZ6060 use model BAYCURB051A.

2. Assemble and install the curb following the instructions in the 
     Installer's Guide included with the curb.  

SIDING

RETURN 
AIR 
DUCT

SUP-
PLY AIR 
DUCT

EXTERIOR 
WALL

INSULATE WEATH-
ERPROOF OR RAIN 
SHIELD

FLEXIBLE DUCT 
CONNECTORS

3/4" VIBRATION ISOLATORS, USE 7 ISOLATORS 
AS SHOWN IN FIGURE 9, PAGE 13.

SUPPORT PAD FOUNDA-
TION

OUTDOOR AIR DIS-
CHARGE

Summary of Contents for 4YCZ6024

Page 1: ...ures on the fan Operating the unit without the access panels properly installed may result in severe personal injury or death WARNING SAFETY HAZARD This information is for use by individuals having adequate backgrounds of electrical and mechanical experience Any attempttorepairacentralairconditioningproductmayresult inpersonalinjuryand orpropertydamage Themanufacturer or seller cannot be responsib...

Page 2: ...R 410A operating pressure exceeds the limit of R 22 Proper service equipment is required Failure to use proper service tools may result in equipment damage or personal injury SERVICE Use only R 410A Refrigerant and approved POE compres sor oil IMPORTANT Wear appropriate gloves arm sleeve protectors and eye protection when servicing or maintaining this equipment PRECAUTIONARY MEASURES Avoid breathi...

Page 3: ...g 16 Gas Piping Installation 16 Pipe Delivery Schedule natural gas only 17 Gas Pressure Set up Precautions 17 Gas Supply Line Pressure all fuels 17 Verify Manifold Pressure 18 Input Check and Adjustment 18 High Altitude Installation 19 Air Filter Installation 19 Electrical Wiring 19 Electrical Connections 18 Electrical Power 19 Disconnect Switch 19 Over current Protection 19 Power Wiring 19 Contro...

Page 4: ... Determine Unit Clearances Figure 1 4YCZ6024 6036 1 of 3 Figures 1 through 6 show the unit critical dimensions DWG NO D673947G01_REVC NOTE The view labeled Bottom Side represents the Base as viewed looking up from underneath the unit ...

Page 5: ...Page 5 Installer s Guide Figure 2 4YCZ6024 6036 2 of 3 ...

Page 6: ...uide Step 2 Determine Unit Clearances Figure 1 4YCZ6024 6036 3 of 3 Figures 1 through 6 show the unit critical dimensions NOTE The view labeled Bottom Side represents the Base as viewed looking up from underneath the unit ...

Page 7: ...Page 7 Installer s Guide Figure 4 4YCZ6048 through 4YCZ6060 1 of 3 NOTE The view labeled Bottom Side represents the Base as viewed looking up from underneath the unit ...

Page 8: ...Page 8 Installer s Guide Figure 5 4YCZ6048 through 4YCZ6060 2 of 3 ...

Page 9: ...Page 9 Installer s Guide Figure 6 4YCZ6048 through 4YCZ6060 3 of 3 ...

Page 10: ...r to the Installation section for instruction on converting the supply and return airflow covers to down airflow 3 The field assembled Roof Mounting Curb BAYCURB050A or BAYCURB051A or a field fabricated curb should be in place before the unit is hoisted to the roof top The Roof Mounting Curb frame must be installed on a flat level section of the roof maximum of 1 4 per foot pitch and provide a lev...

Page 11: ...clearance to combustible mate rial shall be maintained on air outlet duct Rooftop Installation Curb Mounting Convert Horizontal Airflow to Down Airflow The factory ships the unit for horizontal airflow Perform this procedure to convert the unit to down airflow 1 Remove the three 3 sheet metal screws securing the supply aircover and the four 4 sheet metal screws securing the return air cover from t...

Page 12: ...tabs or flanges Failure to observe these warnings may result in equipment damage 1 Before preparing the unit for lifting check the unit dimension drawings for center of gravity for lifting safety Figures 1 to 6 page 4 9 Because of placement of internal components the unit s weight may be unevenly distributed Approximate unit weights are also provided in the unit drawings NOTE When unit rigging and...

Page 13: ... roof top applications using field fabricated ducts and sleeper rails rather than a curb or frame use the following procedure 1 Locate and secure the sleeper rails to the roof Three 3 sleeper rails are required One on each end to support the edges of the unit and one across the center of the unit The center rail must run inside both drip lips Vibration isolators should be installed as indicated on...

Page 14: ...sible for the unauthorized use of this drawing and expressly disclaims any liability for damages resulting from such unauthorized use Gasket Seal Spreader Bars Base of unit rest on top of curb rails Drip lip on perimeter of unit Top shipping skid attached to unit IMPORTANT To prevent damage to the sides and top of the unit when hoisting retain the top shipping skid on the unit or use spreader bars...

Page 15: ...orizontal Airflow Application with Frame Supply Air Return Air Roof Flashing Channel Iron Center Support Center Sup port required on all Frame Applications Angle Iron Frame Roof Flashing Return Air Angle Iron Frame Roof Flashing Supply Air Channel Iron Center Support Center Support required on all Frame Applications ...

Page 16: ...oise and vibration transmission Elbows with turning vanes or splitters are recommended to minimize air noise and resistance The first elbow in the ductwork leaving the unit should be no closer than two 2 feet from the unit to minimize noise and resistance To prevent leaking do not attach the ductwork to the bottom of the unit base refer to the bottom example in Figure 14 A 3 4 inch female NPT cond...

Page 17: ...e making the gas pipe connection give serious consideration to providing the clearance necessary to remove the accesspanelsontheunit e g economizerandfilteraccesspanels NOTE In the absence of local codes the installation must con form with American National Standard Z223 1 National Fuel Gas Code Latest Revision The available gas supply must agree with the required gas supply marked on the unit nam...

Page 18: ...nchonthegasvalveinletboss connect the gas piping to the unit Check the completed piping for leaks using a soap and water solution or the equivalent 6 After installation of the gas pipe in the unit the pipe opening should be closed with the filler barrier plug provided Manifold Pressure Check the manifold pressure at the unit gas valve Do not exceed the recommended pressure shown on the unit namepl...

Page 19: ...hat require 49 orifices for altitudes from 7000 8000 orifices must be changed to 50 HIGH ALTITUDE DERATE CHART NAT Altitude In Feet Inputs shown are with factory orifices 3 5 WC High Fire 1 8 WC Low Fire Natural Gas heating value of 950 btu cuft Electrical Power It is important that proper electrical power be available for the unit Voltage variation should remain within the limits found on the uni...

Page 20: ...itioning systems been checked at the service ports for charge and leak tested if necessary Does the condenser fan and indoor blower turn free without rub bing and are they tight on the shafts Has the indoor blower speed been determined and the proper speed been set See the Unit Wiring Diagram Has all work been done in accordance with applicable local and national codes Are all covers and access pa...

Page 21: ...Page 21 Installer s Guide Figure 22 4YCZ6 Field Wiring Diagram NOTE For economizer wiring instructions see the Installer s Guide that came with your economizer ...

Page 22: ...cooling setpoint to above room temperature Heating Cycle Theseunitsareequippedwithasolid stateignitioncontrolthatlights the burners each time the thermostat calls for heat The burners are extinguished during the OFF cycle The gas heating section of the unit can be started using the follow ing procedure 1 Be sure the thermostat is at its lowest setting and the power to the unit is off a Turn the ma...

Page 23: ...ond postpurge The indoor blower motor will continue to operate at the current speed for 60 or 90 seconds after the flames are extinguished Sequence of Operation Safety Sequences This product is equipped with safety devices to protect against abnormal conditions The temperature limit switch TCO is located on the blower barrier andcanbeaccessedthroughtheblowercompartment Thisautomatic reset device p...

Page 24: ... damage Do not store combustible materials gasoline or other flammable vapors or liquids near the unit WARNING Someoftheperiodicmaintenancefunctionsofthe4YCZ6unitcan beperformedbytheowner thisincludesreplacingthedisposable or cleaning the permanent air filters cleaning the unit cabinet and conducting a general unit inspection on a regular basis Filters When the system is in constant operation insp...

Page 25: ... Hood and Combustion Blower Cleaning Manifold Pressure Check and Adjust 1 Connect a manometer to the pressure tap at the outlet side of the unit s gas valve remove the Control Heat access panel Read the manifold pressure with the burners firing See Figure 16 on page 17 for gas valve connections 2 If the manifold pressure reading does not match the value indicated on the unit s nameplate the unit s...

Page 26: ... 3 Flashes Pressure switch problem detected Fast Flash Rate Not used 4 Flashes High Limit switch protection device open Steady ON Normal No Call for Heat 5 Flashes Flame sensed and gas valve not energized or flame sensed and no W signal 6 Flashes Flame Rollout Switch open 7 Flashes Thermostat miswired W1 W2 Fast Flash Rate The LED will flash on for 1 4 second and off for 1 4 second Slow Flash Rate...

Page 27: ...Page 27 Installer s Guide ...

Page 28: ...uide Trane 6200 Troup Highway Tyler TX 75707 9010 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specification without notice 2017 Trane 09 18 ...

Reviews: