Product Specification
MODEL
4WCC4024
4WCC4030
4WCC4036
4WCC4042
4WCC4048
4WCC4060
RATED Volts/PH/Hz
208–230/1/60
Performance Cooling BTUH
(a)
23800
29800
35200
43000
47000
57000
Indoor Airflow (CFM)
770
985
1105
1355
1590
1835
Power Input (KW)
2.09
2.55
3.03
3.54
4.10
4.85
EER2/SEER2 (BTU/Watt-Hr.)
(b)
11.0 / 13.4
Sound Power Rating [dB(A)]
(c)
66.4
70.0
69.4
71.5
72.5
77.3
PERFORMANCE HEATING
208–230/1/60
(High Temp.) BTUH
23200
28600
34400
39000
45000
55000
Power Input (KW)
1.95
2.31
2.93
3.43
3.94
4.71
(Low Temp.) BTUH
14700
17200
22000
23400
26200
35400
Power Input (KW)
1.78
2.16
2.76
3.15
3.61
4.34
HSPF2 (BTUH/Watt-Hr)
7.0
POWER CONN. — V/Ph/Hz
208–230/1/60
Min. Brch. Cir. Ampacity
(d)
LOCATED ON UNIT NAMEPLATE
Fuse Size — Max. (amps)
LOCATED ON UNIT NAMEPLATE
Fuse Size — Recmd. (amps)
LOCATED ON UNIT NAMEPLATE
COMPRESSOR
SCROLL
VOLTS/PH/HZ
208–230/1/60
R.L. Amps — L.R. Amps
LOCATED ON UNIT NAMEPLATE
OUTDOOR COIL — TYPE
SPINE FIN
Rows/F.P.I
2 / 24
Face Area (sq. ft.)
13.32
13.32
15.49
20.54
20.54
22.90
Tube Size (in.)
3/8
Refrigerant Control
EXPANSION VALVE
INDOOR COIL — TYPE
PLATE FIN
Rows/F.P.I 3 / 15
3/15
4/15
4/15
3/15
3/15
4/15
Face Area (sq. ft.)
3.5
5.0
Tube Size (in.)
3/8
Refrigeration Control
EXPANSION VALVE
Drain Conn. Size (in.)
3/4" FEMALE NPT
OUTDOOR FAN — TYPE
SWEPT
DIA. (IN.)
23.4
28.3
DRIVE/NO. SPEEDS
DIRECT / 1
CFM @ 0.0 in. w.g.
(e)
2550
3270
3250
4400
4400
5500
Motor — HP/R.P.M
1/12 /850
1/6/842
1/5/855
1/4/798
1/4 /825
1/3/825
Volts/Ph/Hz
208–230/1/60
F.L. Amps/L.R Amps
LOCATED ON UNIT NAMEPLATE
INDOOR FAN — TYPE
Constant Torque ECM
Dia. x Width (in.)
10.62 x 10.68
10.62 x 10.62
11.87 x 10.68
Drive/No. Speeds
DIRECT / 4
CFM @ 0.0 in. w.g.
(f)
SEE FAN PERFORMANCE TABLE
Motor — HP / R.P.M.
1/2/1050
1/2/1050
1/2/1050
3/4/1050
3/4/1050
1/1050
Volts/Ph/Hz
208–230/1/60
F.L. Amps
LOCATED ON UNIT NAMEPLATE
FILTER / FURNISHED
NO
Type Recommended
THROWAWAY
Recmd. Face Area (sq. ft)
(g)
2.7
4
5.3
REFRIGERANT
R-410A
Charge (lbs.)
LOCATED ON UNIT NAMEPLATE
Subcooling
16°
14°
11°
9°
8°
6°
(a)
Rated in accordance with AHRI Standard 210/240.
(b)
Rated in accordance with D.O.E. test procedure.
(c)
Sound Power values are not adjusted for AHRI 270–95 tonal corrections.
(d)
Calculated in accordance with currently prevailing Nat’l Electrical Code.
(e)
Standard Air — Dry Coil — Outdoor.
(f)
Standard Air — Dry Coil — Indoor
(g)
Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per
manufacturer’s recommendation with a clean resistance of 0.05” W.C.