4
18-AC51D1-10E-EN
2.3 Suggested Locations for Best Reliability
Ensure the top discharge area is unrestricted for
at least five (5) feet above the unit.
Three (3) feet clearance must be provided in
front of the control box (access panels) and any
other side requiring service.
Do not locate close to bedrooms as operational
sounds may be objectionable.
Min. 12” to
Shrubbery
Avoid Install
Near Bedrooms
Min 5’ Unrestricted
Access Panel
Min 3’
Unrestricted
2.2 Refrigerant Piping Limits
1. The maximum length of refrigerant lines
from outdoor to indoor unit should NOT
exceed sixty (60) feet.
2. The maximum vertical change should not
exceed sixty (60) feet.
3. Service valve connection diameters are
shown in Table 5.1.
Note:
For line lengths greater than sixty (60)
feet, Refer to Refrigerant Piping Application
Guide, SS-APG006-EN or Refrigerant Piping
Software Program, 32-3312-03 (or latest revi-
sion).
60’
Max
Vertical
Change
Standard
Line Set
60’ Max
Line Length
60’
Max
Vertical
Change
Summary of Contents for 4TTR4018-060
Page 25: ...18 AC51D1 10E EN 25 PRINTED FROM D158513P01 018L Models PRINTED FROM D158515P01 060L Models...
Page 26: ...26 18 AC51D1 10E EN Section 17 Wiring Diagrams 018N 019N 024N 025N 042N 049N Models...
Page 27: ...18 AC51D1 10E EN 27 018N 019N 024N 025N 042N 049N Models...
Page 28: ...28 18 AC51D1 10E EN PRINTED FROM D157362P05 REVB 030N 036N 048N Models...
Page 29: ...18 AC51D1 10E EN 29 PRINTED FROM D157362P05 REVB 030N 036N 048N Models...
Page 30: ...30 18 AC51D1 10E EN 060N Models...
Page 31: ...18 AC51D1 10E EN 31 060N Models...
Page 34: ...34 18 AC51D1 10E EN 060L Models...