Trane Technologies WIR10523 Installer'S Manual Download Page 1

 

HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING

WARNING:

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT — This Document is customer property and is to remain with this unit.  Please return to service information 

pack upon completion of work.

Installer’s Guide

18-BC107D1-1A-

EN

T.V.S. Harness for LSOV

WIR10523 

GENERAL:

The new wire harness (WIR10523) needs to be installed 

where the existing latching switchover valve (LSOV) harness 

is. This new wire harness has a transient voltage suppressor 

and is used to eliminate a potential voltage spike to the LSOV 

solenoid when the LSOV gets commanded (This is NOT a 

safety concern).

 

This kit is used with the following variable speed heat pump 

models: 

4TWV

4TWL9

4A6V

4A6L9

KIT CONTENTS:

Open and inspect contents for damage or missing items

.

Qty. Description

Part Number

1

LSOV Wire Harness

WIR10523

1

Wiring Diagram (Danfoss 
Drive)

D157619P05

1

Wiring Diagram (VSPD Side 
Discharge Units)

D160092P01

1

Installer Guide

18-BC107D1-1A-EN

INSPECTION:

1.  Unpack all components of the kit.                   
2.  Check carefully for any shipping damage. If any damage 

is found, this must be reported immediately and a claim 

made against the transportation company.

3.  Check to be sure all components are in the package. Any 

missing components should be reported to your supplier 

at once and replaced with authorized components only.

This information is intended for use by individuals 

possessing adequate backgrounds of electrical and 

mechanical experience. Any attempt to repair a central 

air conditioning product may result in personal injury and/

or property damage. The manufacture or seller cannot 

be responsible for the interpretation of this information, 

nor can it assume any liability in connection with its use.

HAZARDOUS VOLTAGE!

Disconnect all electric power, including remote 

disconnects before installing or servicing. Follow proper 

lockout/tagout procedures to ensure the power can not 

be inadverantly energized. Failure to disconnect power 

before servicing could result in death or serious injury.

INSTALLATION:

 

1.  Disconnect all the electrical power to the unit.

a.  Wait two (2) minutes after disconnecting power as 

the electrical components may hold a dangerous 

voltage. Verify the DC Voltage is less than 42 VDC 

as measured from the test points at the bottom of 

the drive before servicing the drive.

2.  Remove the unit control box cover.
3.  Remove the unit top which allows access to the wire 

routing (step not required for side discharge units).

4.  Remove the unit side panel to gain access to the LSOV 

solenoid.