Configuration Option Setup
Installation Options
Table 7.
Installer configuration setup menu
Opt.
No.
Name
Def
Values/Descriptions
Notes
0100
Temperature indication/
Resolution
0
• 0= °F, 1 degree resolution
• 1= °F, 0.5 degree resolution
• 2= °C, 1 degree resolution
• 3= °C with 0.5 degree
resolution
• 4= °C with 0.1 degree
resolution
This setting affects indoor temperature display and setpoint
display resolutions. Outdoor temperature display area is
always ±1 resolution for both F and C. Refer to Option 0210.
0110
Clock Format
12
• 12= 12-hour clock
• 24= 24-hour clock
0120
Year
11
• 11–99
Available year range: 2011–2099. This value is updated to the
real time clock after setting. Day of the week is updated
0121
Month
1
• 1–12
This value is updated to the real time clock after setting. Day
of the week is updated automatically.
0122
Day
1
• 1–31
Month dependent: this value is updated to the real time clock
after setting. Day of the week is updated automatically.
0125
Daylight Savings
2
• 0= Disabled
• 1= US (1987), changeover at
2:00am
• 2= US (2007), changeover at
2:00am
• 3= Europe, changeover at
1:00am
• 4= Manual, changeover at
2:00am
0126
0127
0128
0129
• Spring Ahead Month
• Spring Ahead Day
• Fall Back Month
• Fall Back Day
• 03
• 01
• 11
• 01
• 01-12
• 01-31
• 01-12
• 01-31
Options available only if 0125 is set to 4.
0130
System Selection
8
• 1= 1H/1C (Conv) 1st Stage
Heat (W), 1st Stage Comp (Y),
Fan (G)
• 2= 1H/1C (HP) 1st Stage Comp
(Y), Changeover (O/B), Fan (G)
• 3= 1H (Conv) 1st Stage Heat
(W), without fan
• 4= 1H (Conv) 1st Stage Heat
(W), Fan (G)
• 5= 1C (Conv) 1st Stage Comp
(Y), Fan (G)
• 6= 2H/1C (HP) 1st Stage Comp
(Y), Changeover (O/B),
Auxiliary Heat (W1), Fan (G)
• 7= 2H/2C (Conv) 1st & 2nd
Stage Heat (W,W2), 1st & 2nd
Stage Comp (Y,Y2), Fan (G)
• 8= 2H/1C (Conv) 1st & 2nd
Stage Heat (W,W2), 1st Stage
Comp (Y), Fan (G)
• 9= 1H/2C (Conv) 1st Stage
Heat (W), 1st & 2nd Stage Comp
(Y,Y2), Fan (G)
• 10= 2H/2C (HP) 1st & 2nd
Stage Comp (Y,Y2), Changeover
(O/B), Fan (G)
• 11= 3H/2C (HP) 1st & 2nd
Stage Comp (Y,Y2), Changeover
(O/B), Auxiliary Heat (W1), Fan
(G)
0140
Schedule Options
1
0=Non-programmable
1= Programmable
0150
TOD/Economizer Output
(Terminal A)
0
• 0= Unused
• 1= TOD energizes terminal
A
during occupied period, not
during unoccupied period.
• 2= Economizer energizes
terminal
A
during a call for cool.
TOD is not available in Non-programmable Mode. (Refer to
Option 0140)
0151
Heat Fan Operation
0
0= System controls fan
1= Thermostat controls fan
Only shown for conventional system with heat stages and fan
capability. For heat pump, the fan relay operates with
thermostat control.
0153
Reversing Value O/B
0
0= O/B
ON
when call for cool
1= O/B
ON
when call for heat
Only shown for heat pump systems.
0160
Cycles Per Hour (CPH) [First
Stage Compressor]
3
1–5
Only for systems with cool or HP stage. (Refer to Option 0130.)
Selection in this stage changes 2nd stage cool default CPH.
0161
CPH (Second Stage
Compressor)
3
1–5
Only for systems with 2-cool or HP stages. (Refer to Option
0130.)
0162
CPH (First Stage
Conventional Heat)
5
1–10
Only for conventional systems with heat stages. (Refer to
Option 0130.) Selection in this stage changes default CPH of
2nd stage heat.
0163
CPH (Second Stage
Conventional Heat)
9
1–10
Only for conventional systems with two stages of conventional
heat.
0164
CPH for Auxiliary Heat
9
1–10
Only shown for 2H/1C HP or 3H/2C HP systems. (Refer to
Option 0130.)
0165
CPH for Emergency Heat
9
1–10
Only shown for 2H/1C HP or 3H/2C HP systems. (Refer to
Option 0130.)
0170
Continuous Backlight
0
0= Backlight
ON
time is limited
1= Backlight
ON
continuously