36
TRIAD Boiler Systems, Inc.
West Chicago, IL
www.triadboiler.com
thermometers, and any other small lose items you ordered. Larger and heavier items are typically shipped
on pallets. For water boilers, an appropriate pressure and temperature gage or a tridicator is provided.
Install them in the instrumentation cluster.
An appropriate stack thermometer is provided. Install into a 1/2” coupling in the stack connector.
The safety relief valve(s) shall be installed at connections provided on the top of the boiler. Often this
takes place after the boil-out procedure. The safety relief valve(s) provided for your boilers are
documented in the ASME data reports provided with this manual.
See the safety relief valve installation
section
4.8 Electrical Installation
ELECTRICAL INSTALLATION SHALL BE IN
ACCORDANCE WITH LOCAL REGULATIONS.
THE FOLLOWING CODES SHALL BE FOLLOWED
AS APPLICABLE. CSA 22.1: CANADIAN
ELECTRICAL CODE PART 1, NFPA 70: NEC
A wiring diagram for the boiler and burner will be inside the burner control panel. The wiring diagram in
conjunction with this manual and O&M manuals for the burner and electrical components should provide
an electrician with everything required to properly installing the electrical components. Before installing,
modifying, or servicing the system, the main electrical disconnect switch must be in the OFF position.
There may be more than one disconnect switch. Lock out and tag switch with a suitable warning label.
The exact configurations of electrical panels vary. Additional small junction boxes are used when needed.
If for repair purposes wiring is run to any probes, that wiring shall be sufficient for 150°F. Grounding of
some components is conducted through the boiler and the mounting of burner to the boiler. Electrical
power requirement are listed on placards for the respective components. Wiring from any boiler mounted
control and the fuel train controls are pulled into the burner control panel. Wiring for sensors tend to be
specific to the manufacture of the burner management system; if maintenance is performed on this wiring
ensure the appropriate wire is used. Wires are mounted on terminal strips for ease of trouble shooting
and maintenance.
Power for Electrically Operated Controls.
All controls are powered with a potential of 150 V or lower with one side grounded. A separate equipment
ground conductor should be brought to the control panel frame with ground continuity assured to the
fuel valve. All operating coils of control devices should be connected to the neutral side of the control
circuit, and all control limit switches or contacts should be in the ungrounded (hot) side of the control
WARNING
The improper installation, adjustment, service,
maintenance, or operation of this equipment can
result in fire, explosion, series injury, or death.