background image

http://www.tracopower.com

Rev: 5.6/4915

INSTALLATION INSTRUCTIONS

TEX 120 Series        Industrial Power Supply

Table 1

Order Code

Rated Input

Voltage

Output

Power max.

Output

** Output Voltage

Adjustment Range

recommended Circuit

breaker (Characteristic C)

TEX 120-112

100 – 240Vac

50 / 60Hz

Universal Input

96 Watt

12.0VDC / 8.0A

12.0 – 15.0VDC

5A

TEX 120-124

120 Watt

24.0VDC / 5.0A

24.0 – 28.0VDC

5A

** Adjustable by potentiometer with a screwdriver.

The equipment can be connected to TN-S, TT and IT power systems

Table 2

Input current:

@ Vin=115VAC

@ Vin=230VAC

Power Consumption

@ Vin=115VAC @ Vin=230VAC

TEX 120-112

2.2A typ.

1.0A typ.

TEX 120-112

114 Watt typ.

112 Watt typ.

TEX 120-124

2.4A typ.

1.2A typ.

TEX 120-124

140 Watt typ.

136 Watt typ.

Table 3

Output Voltage adjustment:

Note: The  integrity  of  the  seal cannot be  guaranteed  once  the  cover
has been removed in the field!

T

o adjust the output voltage, the case cover must be removed. Carefully loosen

and remove all six screws, then remove the cover. The output voltage of the unit
can  be  adjusted  by  turning  the  potentiometer  screw,  using  an  insulated
screwdriver. By turning the screw clockwise (cw) the output voltage will increase;
by  turning the  screw  counter-clockwise  (ccw),  the  output voltage  will  decrease.
The output voltage level should only be adjusted with the output connected to a
load,  (similar  to  the  load  used  in  the  application).  After  adjusting  the  output
voltage to the required value, the case must be carefully reassembled. Place the
cover  over  the  case  and  ensure  that  the  rubber-sealing  gasket  is  undamaged,
and is correctly positioned. Secure the lid with the six screws. Tighten the screws
gradually, moving diagonally from one to another. The recommended tightening
torque is 0.6Nm (5.310lb·in).

Operational Input Voltage

AC: 85Vac – 264Vac, 50 / 60Hz. DC: 85Vdc* – 375Vdc (*Observe derating)

Operating temperature range:

Natural Air Convection

Cooling

-40°C – +85°C max (Atex: -40°C - +70°C) (*Observe derating)

-40°F – +185°F max (Atex: -40°F - +158°F) (*Observe derating)

Output Power Derating:

above +60°C

2

%

/

K

above 140°F

2

%

/

K

Storage temperature range:

-40°C – +85°C max

-40°F – +185°F max

Parallel Operation

:

Only possible with external decoupling diode.

Connectors on the user side:

(see Fig. 2 & Fig. 3)

Input Cable Assembly: See Fig.2 (

Tracopower P/N: TEX–IP–ASSY, 3 x 1.3mm²

)

Input Connector: Binder Circular Connector Series 693: 99-4222-14-04

Output Cable Assembly: See Fig.3 (

Tracopower P/N: TEX–OP–ASSY, 7 x 0.8mm

²)

Output Connector: Binder Circular Connector Series 693: 99-4217-160-07

Wiring: Material

Copper

Temp: -40°C – +125°C (-40°F – + 257°F)

Input: 3 x 0.8mm

2

– 2mm

2

max (AWG 18 – AWG 14)

(1 x Live; 1 x Neutral; 1 x Protective Earth)

Output: 7 x 0.8mm

2

– 1.3mm

2

max (AWG18– AWG 16)

(3 x +V

out

; 3 x –V

out

; 1 x Protective Earth).

Input:

TEX-IP-ASSY Cord Diameter = 10 – 12mm /

Output:

TEX-OP-ASSY Cord Diameter = 12 – 14mm

Case protection:

IP67 (according to IEC 60529), NEMA 6P, UL50 4X

Case material:

Die-Cast Aluminium (chassis and cover)

Fig. 1

Reviews: