http://www.tracopower.com
Rev: 2.6 /4113
INSTALLATION INSTRUCTIONS
TCL-DC Series Industrial DC-DC Converter
Order Code
DC-Input
Voltage Range
Output
Power max.
Output
* Output Voltage
Adjustment Range
recommended Circuit
breaker (Characteristic C)
TCL 012-124 DC
9.5 - 18Vdc
24 Watt
24.0Vdc / 1.0A
24.0 - 28.0Vdc
6 – 16A
TCL 024-105 DC
18 - 75Vdc
24 Watt
5.0VDC / 5.0A
5.0 – 5.25Vdc
TCL 024-112 DC
12.0VDC / 2.0A
12.0 – 15.0Vdc
TCL 024-124 DC
24.0VDC / 1.0A
24.0 – 28.0Vdc
TCL060-112 DC
18 - 75Vdc
4.0-1.0A
60 Watt
12.0VDC / 5.0A
12.0 – 15.0VDC
TCL 060-124 DC
24.0VDC / 2.5A
24.0 – 28.0VDC
* Adjustable by potentiometer with a screwdriver.
General:
Input current:
@ V
in
= 12Vdc
Power Consumption
@ V
in
= 12Vdc
I
out
= 0%
I
out
= 100%
I
out
= 0%
I
out
= 100%
TCL 012-1xx DC
80mAmax
2.5Amax
TCL 012-1xx DC
0.96Watt typ.
30Watt typ.
Input current:
@ V
in
= 24Vdc
@ V
in
= 48Vdc
Power Consumption
@ V
in
= 24Vdc
@ V
in
= 48Vdc
I
out
= 0% / 100%
I
out
= 0% / 100%
I
out
= 0% / 100%
I
out
= 0% / 100%
TCL 024-1xx DC
80mA / 1.3A max
60mA / 0.7A max
TCL 024-1xx DC
1.92W / 31.2W typ.
2.88W / 33.6W typ.
TCL 060-112 DC
31mA / 2.9A max
19mA / 1.4A max
TCL 060-112 DC
0.74W / 69.5W typ.
0.89W / 68.8W typ.
TCL 060-124 DC
45mA / 3.1A max
25mA / 1.54A max
TCL 060-124 DC
1.08W / 74.4W typ.
1.2W / 74.0W typ.
Operating temperature range:
Natural Air Convection Cooling
-25°C – +70°C max
14°F – +158°F max
Output Power Derating:
above +50°C
1.5
%
/
K
above 122°F
1.5
%
/
K
above +40°C
2.0
%
/
K
TCL 060-112DC & TCL060-124DC only
above 104°F
2.0
%
/
K
TCL 060-112DC & TCL060-124DC only
Storage temperature range:
-25°C – +85°C max
-13°F – +185°F max
Parallel Operation:
No parallel operation
Connections:
Screw type plug-in connector (standard).
Recommended tightening torque 0.5 to 0.7Nm (4.5 to 6.2lb.in.)
Wiring:
0.21mm
2
- 3.16mm
2
(AWG 24 - AWG 12)
Case material:
Grey plastic
UL 94V-0 rated