PMO-40, C40k & VLC40 for Sinewave Systems
5-9
11
10”
Drill two half-shears at distance shown with 11/64” bit for lower
mounting holes only. Fasten with 10-32 x 1/2” bolts,
9”
3.5”
10
From PV Array Positive (+)
4
5
6
WIRE
Wire Length Table. Wire length is based upon the mounting
location of the C40. Do not exceed four C40’s with DC175
disconnect, or five C40’s with a DC250 disconnect. Do not
exceed DC disconnect’s current rating
.
16
6
INVERTER ( )
−
13
15
INVERTER (+)
12
14
PMO-40, C40k & VLC40 for Sinewave Systems
The wiring scheme shown in this view meets NEC code requirements by
using the battery disconnect of the inverter as the overload/disconnect
device. Alternative methods of wiring the C40’s may be needed depending
upon your application. Kits are shipped with maximum wire lengths
pre-cut. Trimmed the uncrimped end to the length found in the Wire
Length table according to the C40’s mounting position.
Place double-sided tape on the back panel of the C40 in the location
shown. Drill the dimples in the back plane of the PM in the approximate
location shown. When installing multiple C40’s, install them in the
sequence shown above the wire length table. Bundle excess or loose
wires. This option requires the use of a bare grounding conductor between
the DCBB and a rod or pipe driven into the earth.
#
Qty
Part No.
Description
1
AR
PMO-C40/K
charge, load, or diversion controller
2
2
3220
1.375” thermoplastic knockout bushing
3
1
PMO-BTS
battery temperature sensor with cable
4
AR
2323
6 AWG THHN red cable to inverter positive terminal
5
AR
2323
6 AWG THHN Black negative cable to inverter
negative terminal
6
AR
2323
6 AWG THHN Red positive cable to PV circuit breaker
7
2
442
6-32 HH SS nut
8
2
486
#10 starwasher
9
1
1974-1
2/0 barrel lug Connect the PV (+) to this lug.
10
4
492
#6 starwasher
11
2
401
6-32 HH SS bolt
12
AR
3240
decal “Inverter (+)”
13
AR
3238
decal “Inverter (-)”
14
AR
2430
#6 AWG ring terminal
15
AR
2430
#6 AWG ring terminal
16
AR
716-1
#6 AWG ring terminal w/ ¼” hole
17
XXX
wire tie (not shown)
*Refer to wire length table to determine length of each cable by its position.
Mount C40s in sequence shown above table. AR = as required.
Wiring Instructions
1. Follow the assembly instructions before wiring. Route
the PV array positive wire through conduit (not included)
to the DC side of the PM and connect to the top of the PV
array disconnect. Do not connect the array positive
directly to the C40 charge controller. If more than one
charge controller is utilized, the modules in the array
should be divided equally between the controllers.
2. Connect the PV array negative to the ground bonding
block (DCBB). Connect the frames of the PV modules to
the ground bonding block through the negative array
cables. The PV negative and battery negatives are
connected at the ground bonding block. Do not connect
the charge controller battery negative directly to the
battery.